MAN-0148, Rev 1
33
March 2016
Table 4: Typical Millennium II Relay Configurations
Relay Assignment Example
Channel # and selected
Alarm points (levels)
ALARM RELAY 1 (RL1)
ALARM RELAY 2 (RL2)
ALARM RELAY 3 (RL3)
CH1
POINT 1=20% lel
POINT 2=40% lel
RL1:CH1
POINT 1=20% lel
RL2:CH1
Disabled
RL3:CH1
POINT 2=40% lel
CH2
POINT 1=10 ppm
POINT 2=20 ppm
RL1:CH2
Disabled
RL2:CH2
POINT 1=10 ppm
RL3:CH2
POINT 2=20 ppm
Note 1: In above example, alarm relay 3 (RL3) will trigger whenever any alarm level 2(point 2) is reached.
Note 2: For the single channel relay model transmitter, all (3) alarm relays are available for channel 1.
4.2.7 Relay Alarm Mode setting (for Oxygen sensors only)
This option is available for detecting oxygen levels. The user is allowed to set up two Alarm points/level (normal oxygen
level is 20.9 %) under three available Alarm Modes. These Alarm Modes are: Above-Above, Below-Below and Below-Above.
The Alarm Mode chosen by the user depends on the particular application/operation. If surrounding air is to be used for
calibration, ensure that no contaminants are present. Refer to the Oxygen Sensor Manual (MAN-0093) for detailed
information.
4.2.8 Select Display Language
This option allows the display language to be selected. The default language is English. There are also options for Spanish,
French, and Portuguese.
1.
Enter the main menu by activating any key to get the
“enter main menu”
prompt then activate
switch 1
to select
“yes”
.
2.
Activate the up key
(
switch 1
) or down key (
switch 2
) until
“Select Display Language?”
is displayed.
3.
Activate the enter key (
switch 3
). The default language, ‘
English’
, will be displayed.
4.
Locate other languages by activating the enter key (
switch 3
)
.
5.
Once the desired language is displayed, select
“Exit”
at each menu stage (sub menu and main menu).