background image

Net Safety Monitoring Inc

Modbus Controller & 4-20 Fire Head

8

T

HE

 M

AIN

 M

ENU

The Main Menu allows for:
• Modbus Setup - Select Node Address and Baud Rate
• Select a display language - English, Spanish or French

Note:

The current output will drop to 3.0 mA while in the Main Menu.

Accessing the Main Menu

There are two ways to activate the Main Menu: 
• Calibration Button found on the faceplate (the Housing cover must be 

removed to access)

• Magnetic Reed Switch (a magnet must be used to activate)

Calibration Button

The Calibration Button provides access to the Main Menu, which allows options 
to be reviewed and set. Refer to Figure 9 for more information.

Press and hold

 the Calibration Button to access Main Menu. 

Briefly press

 to make a selection (select 

YES?

).

WARNING:

 

Opening the Controller’s Housing should be avoided when the presence of gas 
is possible (when in a hazardous environment). Do not power up the system, 
with the Housing removed, unless the area has been de-classified. 

Magnetic Reed Switch

The Magnetic Reed Switch is provided to avoid opening the Housing in an 
environment where gas may be present. The Magnetic Reed Switch functions in 
the same manner as the Calibration Button but in a non-intrusive manner. Refer 
to Figure 9 for more information.
Attached to the side of the Controller is a magnet:

Place and hold

 the magnet to the Controller’s Housing (10 o’clock position) 

to access Main Menu.

Briefly place

 the magnet to the Controller’s Housing (10 o’clock position) to 

make a selection (select 

YES?

).

Main Menu Functionality

1. Ensure that the Controller has been turned on and no fault is present.
2. Hold the magnet against the Reed Switch or press and hold the Calibration 

Button until the message 

Switch On 

displays and the countdown (10 to 

0) finishes.

3. An option will scroll across the display followed by the prompt 

YES?

4. To select an option, momentarily place the magnet to the Reed Switch or 

press the Calibration Button at the 

YES?

 

prompt.

5. If you do not wish to select that option wait until the next option appears 

and then select 

YES?

.

6. A selection is acknowledged with a flashing 

YES

7. If no option is selected, the Controller returns to normal operation.

Power Up

Turn power switch On. A 90 second warm-up routine will begin. The display 
shows 

Start Delay Millennium Net Safety

, the Status LED is Red 

Slow Flash and current output displays 3.0 mA.
When power is applied, the system is automatically tested to ensure proper 
functionality. 
After warm-up, the Controller will enter normal operation, the display reads 

NORM

, Status LED will Green Blip/blink and analog output will change to 

4.0 mA. 

Current Loop Measurement (Test Jacks)

Use a standard meter to measure current loop during various states. The 
Controller’s Housing cover must be removed to access the Test Jacks.
Refer to Table 4, “Current Output, LEDs and Display Messages,” on page 10 
for a detailed list and Figure 9 for more information.

Status LED

The Status LED will remain solid, flash, blip and/or blink, in either Red or 
Green, to indicate various states. Refer to Table 4, “Current Output, LEDs and 
Display Messages,” on page 10 for a de
tailed list.

Summary of Contents for MAN-0069

Page 1: ...4 20 mA FIRE HEAD with Analog RS 485 Modbus AD CONTROLLER User Manual Part Number MAN 0069 Rev 2 May 2006...

Page 2: ......

Page 3: ...ed inspected and calibrated prior to shipment Failures can occur which are beyond the control of the manufacturer Failures can be minimized by adhering to the operating and maintenance instructions he...

Page 4: ...sitions Current Output 5 MODBUS Termination 6 Figure 8 Modbus Termination Jumpers 6 Step 4 Operate 7 Figure 9 Controller Functionality 7 The Main Menu 8 Accessing the Main Menu 8 Calibration Button 8...

Page 5: ...ps B C and D for hazardous applications It was designed for either a 1 man intrusive calibration or 2 man non intrusive calibration The Manual The manual has been designed to make installation of the...

Page 6: ...Figure 2 Components Note Refer to the specific Fire Head manual for components LOCATE CONTROLLER FIRE HEAD Fire Head Locate Fire Heads as per the manual provided with the specific product Controller T...

Page 7: ...eals are recommended to prevent water accumulation within the enclosure Seals should be located as close to the device as possible and not more than 18 inches 46 cm away Explosion proof installations...

Page 8: ...be used for separations up to 2000 feet Consult the factory if a greater separation distance is required Ensure the appropriate wire is used for Class 1 Division 1 hazardous applications Note If the...

Page 9: ...ote Unless otherwise specified all models ship with non Isolated current output Figure 7 Jumper Positions Current Output RST 24V COM 4 20 ISO Power to Monitor Supply Terminal Board Power Terminal Stri...

Page 10: ...ad 6 MODBUS TERMINATION Devices are networked in a daisy chain The device located at the end of the chain requires end of line termination Place both jumpers over the pins as shown in Figure 8 for end...

Page 11: ...s messages and prompts Refer to Table 4 Current Output LEDs and Display Messages on page 10 Pull Here knob unscrew the two screws and gently pull to remove faceplate Removal allows access to the PCB b...

Page 12: ...lock position to make a selection select YES Main Menu Functionality 1 Ensure that the Controller has been turned on and no fault is present 2 Hold the magnet against the Reed Switch or press and hold...

Page 13: ...3 Wait for the prompt New Address YES and press the Calibration Button or use the Reed Switch to select Step 4 Use the Calibration Button or Reed Switch to select each of three numbers in the new add...

Page 14: ...u l t Start Delay 90 seconds 3 0 mA Blip S t a r t D e l a y M i l l e n n i u m Normal Operation 4 0 mA Blip N O R M Background radiation source UV 6 0 mA Flash U V P r e s e n t Background radiatio...

Page 15: ...re specific you are regarding the problem the quicker our Service department can determine and correct the problem 3 A company name contact name and telephone number 4 A Purchase Order from your compa...

Page 16: ...ver 2 Turn the power to the detector off 3 Unscrew both the knobs marked Pull Here 4 Lift Controller faceplate from Housing and allow to hang from ribbon cable 5 Unscrew the two metal standoffs 6 Care...

Page 17: ...for an indefinite period of time followed by a sudden failure To eliminate potential ESD damage review the following guidelines Handle boards by metal shields taking care not to touch electronic comp...

Page 18: ...1 09 0 63 1250 12 70 7 99 5 03 3 16 1 99 1 25 0 79 1500 15 20 9 58 6 02 3 79 2 38 1 50 0 94 1750 17 80 11 20 7 03 4 42 2 78 1 75 1 10 2000 20 30 12 80 8 03 5 05 3 18 2 00 1 26 2250 22 80 14 40 9 03 5...

Page 19: ...at units power terminals Enclosure Material Powder coated Copper Free Cast Aluminum Certifications CSA and NRTL C certified for hazardous locations Class I Division 1 Groups B C and D Temperature T5...

Page 20: ...Net Safety Monitoring Inc 2721 Hopewell Place NE Calgary Alberta Canada T1Y 7J7 Telephone 403 219 0688 Fax 403 219 0694 E mail netsafe net safety com www netsafety com Distributed by...

Reviews: