Net Safety Monitoring Inc
Modbus Controller & 4-20 Fire Head
10
STEP 5 — M
ONITOR
There are a variety of ways to indicate the status of the connected detectors:
current output, LEDs and Display Messages.
Table 4:
Current Output, LEDs and Display Messages
RTU R
EGISTERS
Register 40001 = RTU Output (read only)
Register 40002 = RTU Status (read only)
Register 40101 = Reset latched relays (write)
Note:
Many registers are used by the controller. Please do not write outside
the three registers.
LED Status
Current
O/P
Status LED
(red) (green)
Display Messages
Internal Power Fault or
system power out of range
1.0 mA
Fast
Flash
-
S e n s o r F a u l t
Automatic or manual VI
Test Failure
2.0 mA
Fast
Flash
-
V I F a u l t
Start Delay (90 seconds)
3.0 mA
Blip
-
S t a r t D e l a y
M i l l e n n i u m
Normal Operation
4.0 mA
-
Blip
N O R M
Background radiation
source UV
6.0 mA
Flash
-
U V P r e s e n t
Background radiation
source IR
8.0 mA
Flash
-
I R P r e s e n t
Early Warning -
Intermittent radiation
detected
16.0 mA Flash
-
W a r n i n g ! !
Fire confirmed
20.0 mA Flash
-
F I R E ( f l a s h e s )
Writing to memory
-
-
Solid
B U S Y
Table 5:
RTU Output Register (40001) Read Only (binary)
RTUfire_power_up
0x0001
power up delay
RTUfire_vi_fault
0x0002
failed self test
RTUfire_normal
0x0004
normal operation
RTUfire_fault
0x0008
fire head fault
RTUfire_ir_present
0x0010
background IR
RTUfire_uv_present
0x0020
background UV
RTUfire_warning
0x0040
Warning Fire
RTUfire_alarm
0x0080
Fire present
Table 6:
RTU Status Register (40002) Read Only (binary)
RTUstat_fault
0x0001
fault (sensor...)
RTUstat_mem_error
0x4000
memory error
Summary of Contents for MAN-0069
Page 2: ......