Ness R8
- Installation and Programming Manual
27
PROGRAMMING
The Entry Delay Time is the time given to Disarm the Panel on entry
through an entry delay zone.
PROGRAMMING SEQUENCE
1. Press:
P26E
The digits of the existing value will be displayed.
2. Press:
[new time] E
The digits of the new value will be displayed.
EXAMPLE
To program the entry delay time to be 25 seconds:
P26E 25E
PROGRAM MODE LEVEL:
User, Installer, Remote by PC.
FACTORY DEFAULT:
20 = 20 seconds.
NOTES:
• Programmable range is
1–99 seconds.
• To view the programmed
value without making
changes, press P26E.
P26E
ENTRY DELAY TIME
The Exit Delay Time is the time given to secure and exit the premises
after the R8 is Armed. All zones (except 24hr zones) are inactive
during the Exit Delay time.
PROGRAMMING SEQUENCE
1. Press:
P28E
The digits of the existing value will be displayed.
2. Press:
[new time] E
The digits of the new value will be displayed.
EXAMPLE
To program the exit delay time to be 50 seconds:
P28E 50E
PROGRAM MODE LEVEL:
User, Installer, Remote by PC.
FACTORY DEFAULT:
60 = 60 seconds.
NOTES:
• Programmable range is
1–99 seconds.
• To view the programmed
value without making
changes, press P28E.
P28E
EXIT DELAY TIME
The Siren Reset Time sets the alarm duration of the Siren and
Reset outputs.
PROGRAMMING SEQUENCE
1. Press:
P29E
The digits of the existing value will be displayed.
2. Press:
[new time] E
The digits of the new value will be displayed.
EXAMPLE
To program the siren reset time to be 4 minutes:
P29E 4E
PROGRAM MODE LEVEL:
Installer, Remote by PC.
FACTORY DEFAULT:
5 = 5 minutes.
NOTES:
• Programmable range is
1–10 minutes.
• To view the programmed
value without making
changes, press P29E.
P29E
SIREN RESET TIME