TRL5x 

Specification & Installation Instructions

 

 

 

         

2

 

Mounting Instructions 

 

B

A

C

D

E

 

 

CAUTION: Risk of malfunction. Disconnect power prior to separating thermostat cover from its base. 

A. 

Remove the screw (captive) holding the front cover to the base of the thermostat. 

B. 

Lift the front cover of the thermostat to separate it from the base. 

C. 

Pull wire through the base hole. 

D. 

Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections. 

E. 

Mount the control module on the base and secure using the screw (from step A). 

 

Settings on PC Board

 & 

Connections

 

Mode Selection (JP1) 

PGM

RUN

JP1

 

Jumper (JP1) on RUN: 

Thermostat is in 

Operation Mode

Thermostat must be set in this mode to operate properly. 
If not locked, setpoint and control mode (Heating & Cooling 
ON, Cooling only ON or Heating only ON) can be modified by 
end user.

 

PGM

RUN

JP1

 

Jumper (JP1) on PGM: 

Thermostat is set in 

Programming Mode

Refer to following section about all settings description

 

TRL54 – 3 wire cable (TB1 #1, 2 & 3)

 

Connect TB1 #6 (A+) & #7 (B-) to EVCB for BACnet service port to work 

TRL55 – RJ45 Ethernet cable 

BACnet service port works only if TRL5x is connected to EVCB 

JP

1

Mode selector

COM

PGM

Connecting 

strip

COMM. 

BUS

24V

Temperature 
sensor

RU

N

TB1

BACnet 

service port

1 2

 3 4

 5

 6

 7

AI1

B-

A+

DI1

 

JP

1

Mode selector

PGM

Temperature 
sensor

RU

N

BACnet 
service port

RJ45 connector

 

 

Recycling at end of life

 

 

At end of life, please return the thermostat to your Neptronic

®

 local distributor for recycling. If you need to find the nearest Neptronic

®

 

authorized distributor, please consult 

www.neptronic.com

 