background image

 

Actuator

 

Specification and Installation Instructions

 

 

STS-210804

 

         

 

 

Technical Data 

ST000S 

ST005S 

ST020S 

ST060S 

ST065S 

ST080S 

Auxiliary switches 

No 

No 

Yes (2) 

No 

No 

Yes (2) 

Feedback 

No 

Yes 

No 

No 

Yes 

No 

Fail safe - Enerdrive 

No 

Yes 

Power consumption 

8 VA 

20VA Max, 8VA 

Control signal 

3 wire / 2 position, 3 wire / 3 point floating 

2 wire / 2 position, 4 wire / 3 point floating 

Power supply 

22 to 26 VAC or 28 to 32 VDC 

Running time through 90º 

90 - 110 sec. (Fail-safe 20-35 sec) 

Torque 

70 in.lb. [8 Nm] at rated voltage 

Electrical connection 

18 AWG [0.8 mm

2

] minimum 

Inlet bushing 

2 inlet bushings: 13/16” [20.6mm] 

Angle of rotation 

0 to 90 degrees, mechanically adjustable (factory set with 90º stroke) 

Direction of rotation 

Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction) 

Ambient temperature 

-22ºF to +122ºF [-30ºC to +50ºC] 

Storage temperature 

-22ºF to +122ºF [-30ºC to +50ºC] 

Relative Humidity 

5 to 95 % non condensing. 

Ingress protection 

IP22 equivalent to Nema type 2, 

IP54 equivalent to Nema type 3R if water tight inlet bushings (not supplied NEP617) are installed 

Weight 

3 lbs. [1.4 kg] 

Warning: Do not press the clutch when actuator is powered 

 

Dimensions

 

 

 
 

Dimension 

Inches 

Metric (mm) 

1.50 

38.1 

3.64 

92.5 

6.60 

167.5 

3.02 

76.8 

 

 

Caution 

We  strongly  recommend  that  all  Neptronic

®

  products  be  wired  to  a  separate  transformer  and  that  transformer  shall  service  only  Neptronic

®

  products.  This  precaution  will 

prevent interference with, and/or possible damage to incompatible equipment. 
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance. 

 

1

 

Enerdrive System

 U.S.A. Patent #5,278,454 

 

Feature: 

  Mounts easy on round  

& square shaft (with option 

–8). 

  External clutch for manual adjustments. 

  Maintenance free. 

  Position indicator. 

  Fail safe by 

Enerdrive System