Mechanical installation

 

 

1. 

Manually  close  the  damper  blades  and  positioned  the 
actuator at 0º or 90º.

 

2. 

Slide the actuator onto the shaft. 

 

3. 

Tighten  the  nuts  on  the  “U”  bolt  to  the  shaft  with  a  8mm 
wrench to a torque of 60 in.lb. [6,7 Nm].

 

4. 

Slide the mounting bracket under the actuator. Ensure free 
movement  of  the  slot  at  the  base  of  the  actuator.  The 
bracket pin must be placed in the mid distance of the slot.

 

5. 

Fix the bracket to the ductwork with #8 self-tapping screws.

 

 

Wiring Diagrams 

Models ST000S, 005S, 020S 

Models ST060S, 065S, 080S 

3 wire / 2 position

 

(ON-OFF) 

 

2 wire / 2 position 

(ON-OFF)

 

 

3 wire / 3 point floating

  

 

4 wire / 3 point floating 

 

 

PC Board 

 

Dip switch settings 

 
 

Rotation direction (SW1) 

 
 

CW

(0 to 90º)

CCW
(90 to 0º)

 

 
 

Fail safe direction (SW2) 

 
 

Fail safe

return at 0º

Fail safe
return at 90º

 

 

Stroke adjustment 

To adjust the stroke, move the adjustment screws at the desired position.

 

 

CLUTCH

MOUNTING
BRACKET

COMMON (-)

SUPPLY (+)

DRIVE

CW

1

2

3

4

DRIVE
CCW

TB1

COMMON (-)

SUPPLY (+)

DRIVE CW

1

2

3

4

TB1

COMMON (-)

SUPPLY (+)

DRIVE

CW

1

2

3

4

DRIVE
CCW

TB1

COMMON (-)

SUPPLY (+)

DRIVE

CW

1

2

3

4

DRIVE
CCW

TB1

Potentiometer

Only on model 05S & 65S

BT060S

1    2    3    4

Feedback or switches terminal

Only on model 05S, 20S, 65S
& 80S

6   7   8

Terminal

TB3

TB1

S

W

2

Rotation direction

Fail safe direction

Only on model 60S,
65S & 80S

SW1