www.neptronic.com
Direct Steam Injection Humidifier
Installation Instructions and User Manual
Page | 11
Stage 4 – Steam Separator Installation
Any installation work must be carried out by suitably qualified personnel.
Steam Separator Positioning
The steam separator must be installed so that the steam inlet is always on top. The steam inlet and the
condensate outlet must be vertical.
Illustration 14 - Separator Proper Installation
Illustration 15 - Separator Incorrect Installation
Steam Separator Installation
Position the steam separator so that the steam inlet is always located on the top. The separator steam
outlet port must be aligned with the steam control valve inlet port and the distance between the two must
not exceed 8” (203 mm). Use the proper size of threaded pipe to connect the steam separator to the
control valve. Reducing coupling might be needed to perform the installation between the separator and
the steam control valve.
Illustration 16 - Separator Connection to Control Valve
Steam Separator Installation with Single Tube
Position the steam separator so that the steam inlet is always located on the top. The steam separator
must be connected to the outlet of the jacketed distribution tube and must be positioned below the tube to
avoid a build up of condensate in any area in the piping.
S T E A M IN L E T
M U S T A L W A Y S
B E O N T O P
S T E A M O U T L E T
C O N D E N S A T E O U T L E T
M U S T A L W A Y S B E O N
T H E B O T T O M
S T E A M IN L E T
C O N D E N S A T E
O U T L E T
S T E A M O U T L E T
Steam outlet
Separator
Control valve
with actuator
Steam header
Steam inlet
Condensate outlet
8" (203 mm)
Maximum