Networkable VAV Controller
Specification and Installation Instructions
www.neptronic.com
Page | 16
Page | 16
Annex A: Control Apps
Refer to Pressure & Applications
– Menu Overview (1 of 6) on page 7 for more information. The available
Control Apps
vary
according to the model.
Description
CL
(cool only)
CLHt
(cool/heat)
CHrH
(cool/heat/reheat)
CO2
(CO2)
ITOS
(ITOS)
FPbo
(fan powered ON)
FPbA
(fan powered Auto)
Min. Setpoint
20°C (68°F)
20°C (68°F)
20°C (68°F)
20°C (68°F)
15°C (59°F)
15°C (59°F)
15°C (59°F)
Max. Setpoint
28°C (82°F)
28°C (82°F)
28°C (82°F)
28°C (82°F)
30°C (86°F)
30°C (86°F)
30°C (86°F)
Changeover Setpnt
24°C (75°F)
20°C (68°F)
20°C (68°F)
20°C (68°F)
24°C (75°F)
24°C (75°F)
24°C (75°F)
TO1 Ramp
HR1
CR1
HR1
CR1
OFF
HR1
HR1
TO1 Signal Type
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
TO1 Close Pos.
40%
40%
40%
40%
40%
35%
35%
TO1 Open Pos.
0%
0%
0%
0%
0%
0%
0%
TO2 Ramp
HR1
HR1
HR1
CO2
OFF
HR1
HR1
TO2 Signal Type
Pulse
On/Off
Pulse
On/Off
On/Off
On/Off
On/Off
TO2 Close Pos.
40%
40%
40%
40%
40%
70%
70%
TO2 Open Pos.
0%
0%
0%
0%
0%
35%
35%
TO3 Ramp
HR2
CR2
HR2
HR1
OFF
Fan ON
Fan Auto
TO3 Signal Type
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
TO3 Close Pos.
40%
40%
40%
40%
40%
40%
40%
TO3 Open Pos.
0%
0%
0%
0%
0%
0%
0%
TO4 Ramp
HR2
HR2
HR2
HR1
OFF
HR1
HR1
TO4 Signal Type
Pulse
On/Of
f
Pulse
On/Off
On/Off
On/Off
On/Off
TO4 Close Pos.
40%
40%
40%
40%
40%
40%
40%
TO4 Open Pos.
0%
0%
0%
0%
0%
0%
0%
Motor Ramp
CR1
COr
COr
COr
CR1
CR1
COr
AO1 ramp
HR1
CR1
HR1
CR1
HR1
HR1
HR1
AO2 Ramp
HR2
HR1
HR2
HR1
OFF
HR2
Fan Auto
AI1 Input
OFF
SENS
SENS
SENS
OFF
OFF
SENS
AI2 Input
OFF
OFF
OFF
CO2
OFF
OFF
OFF
DI1 Input
nSb.o
nSb.o
nSb.o
Occ.o
Occ.o
nSb.o
nSb.o
Heat Prop Band 2
2°C (4°F)
2°C (4°F)
2°C (4°F)
2°C (4°F)
2°C (4°F)
1°C (2°F)
1°C (2°F)
Heat Deadband 2
1.3°C (2.6°F)
1.3°C (2.6°F)
1.3°C (2.6°F)
1.3°C (2.6°F)
0.3°C (0.6°F)
1.3°C (2.6°F)
1.3°C (2.6°F)
Cool Deadband 2
1.3°C (2.6°F)
1.3°C (2.6°F)
1.3°C (2.6°F)
1.3°C (2.6°F)
0.3°C (0.6°F)
0.3°C (0.6°F)
0.3°C (0.6°F)
Legend
Grey Text
= Standard default value
Bold Text
= Special default value for selected application
HR
= Heating ramp
CR
= Cooling ramp
COr
= Changeover ramp
SENS
= Changeover temperature sensor
Fan ON
= Fan powered box in continuous mode
Fan Auto = Fan powered box in automatic mode (follows demand)
nSb.o
= Night Set Back (normally open)
Occ.o
= Occupancy mode (normally open)
TO
= TRIAC output
AO
= Analog output
AI
= Analog input
DI
= Digital input