background image

 

Networkable VAV Controller 

Specification and Installation Instructions 

 

www.neptronic.com 

 

Page | 13

 

Operation Menus  

This menu is accessible through normal operation mode. The Mode Selector jumper (JP1) of the thermostat must be set to the 
“RUN” position (Operation Mode). Refer to Wiring on page 6.  
 
7.  Press the 

[*]

 and 

[

buttons simultaneously for 5 seconds. The 

“Enter Password”

 screen appears. 

8.  Enter the password within 1 minute by using the arrow keys to increase or decrease the value and the 

[*]

 and 

[

 buttons to 

toggle between the digits.  

a.  Password 

372

 = Temperature Offset Menu 

b.  Password 

637

 = Network Settings Menu 

c. 

Password 

757

 = Airflow Balance Mode 

9.  If

 

you enter the wrong password, the thermostat displays “

Eror

” and returns to Operation Mode. The thermostat will return to 

normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5 
minutes. The changed values will be saved automatically. 

Menu 372 

– Temperature Offset 

1.

 

tS1

 

(temperature sensor offset)

 

 

 

Range: 

 

Offset: 
Increment: 

10 to 40ºC  

[50 to 104ºF]   

Max ± 5ºC  

 

0.1ºC    

 

[0.2ºF] 

Compare the displayed temperature reading with a known value from a thermometer. To offset or calibrate the sensor, use the 
arrows key to set the desired temperature reading. This is useful for thermostats installed in areas where the temperature read 
is s

lightly different than the room’s actual temperature. For example, a thermostat placed right under the air diffuser.  

If the thermostat is set to use an external temperature sensor (

EtS

), the thermostat displays “OFF”.  

2.

 

Ets" 

(external temperature sensor offset)

 

 

 

Range: 

 

Offset: 
Increment: 

0 to 50ºC   

[41 to 122ºF]   

Max  ± 5ºC 
 0.1ºC   

 

[0.2ºF] 

This option appears if you

’ve set one of the analog inputs to 

EtS

 (External temperature sensor). When the thermostat is 

connected to the appropriate analog input, the display shows the temperature read by the external temperature sensor. Adjust 
the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, then the unit 
displays the sensor's limit.  

3.

 

Prs

 

(input 3 reading)

 

 

 

Range: 

 

250mV (0") to 4000mV (1")   

Displays the voltage output value in mV of the pressure sensor. Does not appear for EVCB14NDT4S and EVCB14NDT4X 
(pressure dependant) models. 

4.

 

PRS MIN" 

(input 3 minimum reading)

 

 

 

Range: 

 

Default: 

10mV to 180mV 
60mV 

This setting represents the deadband of the pressure sensor in mV. For advanced users or special applications only. We 
recommend that you use the default setting of 60mV. Does not appear for EVCB14NDT4S and EVCB14NDT4X (pressure 
dependant) models. 

Menu 637 

– Network Settings 

End 

(exit menu)

CP

Y

 

(copy config)

bAC 

(BACnet)

Md 

(Modbus)

nEt

tY

P

 

(Type)

= scroll menu items

nEt 

(Network choice)

bA

C

 

(BACnet)

Md

 (Modbus)

= select / set value

Abr

 (Modbus auto baud rate)

No 

(Manual)

Yes

 (Automatic)

= select / set value

Abr

 

(BACnet auto baud rate)

No 

(Manual)

Yes

 (Automatic)

= select / set value

= select / set value

Add 

(Start address)

(0-254)

If type = bAC, menu contains 
“tYpe”, “bAC” and “CPYc”

If type = mOd, menu contains 
“tYpe and “mOd”

bA

u (Modbus baud rate)

57.6k 

(9.6k, 19.2k, 38.4, 57.6k)

bA

u (Bacnet baud rate)

76.8k 

(9.6k, 19.2k, 38.4, 76.8k)

Add 

(MSTP MAC address)

(0-254)

Modifiable only if Auto Baud Rate 
set to “No”.

Modifiable only if Auto Baud Rate 
set to “No”.

Modifiable only if all DS2 DIP 

switches are set to OFF.

Go to “CPYc"

M

 (MSTP MAX master)

127

 

(1-127)

OP1

 (odd parity, 1 stop bit)

CFG

 (Modbus comport config)

NP2

 (no parity, 2 stop bits)

EP1

 (even parity, 1 stop bit)

MA (Modbus address)

(1-246)

Modifiable only if all DS2 DIP 

switches are set to OFF.

Go to “ENd"

Add 

(End address)

(0-254: max=start + 63)

Cpy 

(Confirm copy)

No

 (cancel)

Yes

 (confirm)

Copy Config

in 

(in progress)

Returns to run mode

SCd 

(Config succeed)

(done)

Go to 

“ENd"

1001

AV.166

AV.165

1000

BV.90

AV.167

Exit menu and return 

to normal operation

Go to “Abr" (BACnet auto baud rate)

Go to “Abr" (Modbus auto baud rate)

Refer to Copy Config Annnex for 
a complete list of messages and 
error codes.

 

Summary of Contents for EVCB Series

Page 1: ...CB14NDT4X Control external actuators using analog 0 10Vdc adjustable or floating signals with feedback models EVCB14NIT4X and EVCB14NDT4X On board differential pressure sensor select models Simple air...

Page 2: ...perature 0 C to 50 C 32 F to 122 F Storage temperature 30 C to 50 C 22 F to 122 F Relative Humidity 5 to 95 non condensing Weight 1 26 kg 2 8 lb The actuator performs an auto stroke on power up When c...

Page 3: ...an setting Alarm status Heating ON A Automatic Menu set up Lock Energy saving mode Minimum Maximum or C Celsius scale F Fahrenheit scale Dimensions EVC with a built in 70 in lb Actuator A 1 50 39mm B...

Page 4: ...r blades and position the actuator to 0 or 90 2 Slide the actuator onto the shaft 3 Tighten the nuts on the U bolt to the shaft with an 8mm wrench to a torque of 150 in lb 17 Nm 4 Slide the mounting b...

Page 5: ...rew BACnet or Modbus Address DIP Switch DS1 MAC address for communication are selectable by DIP switch using binary logic If you do not change device instance in program mode it will be automatically...

Page 6: ...2 1 AO2 AO1 COM 2 analog outputs config Cool ramp 1 or 2 heat ramp 1 or 2 CO2 setpoint airflow 3 2 1 DI2 DI1 COM 2 digital inputs config DI2 Override normally cool heat DI1 OCC open close NSB open cl...

Page 7: ...d PCH Pres mode auto change OFF disabled PoS C Motor mIn pos cooling 10 0 100 10 0 100 CH cool heat APP Control apps CL cool only scroll menu items YES confirm APP Confirm control apps NO cancel The A...

Page 8: ...uT MM Go to OuT MM dI2 Main Menu Sub Menu Configuration rNP MM Ramps NEt MM Network BtN MM Buttons HrS MM Time Date SEt MM Settings Mt MM Motor tNP MM Temperature OUT MM Outputs InP MM Inputs scroll m...

Page 9: ...changeover ramp StF setpnt airflow 0 10Vdc ANA analog 0 10Vdc Aut fan follows demand On fan continuously on CH1 cool heat 1 tO2 Go to tO3 Go to t2C TO2 Close Percent Go to to2 TO2 DIR REV to2 TO2 dire...

Page 10: ...set value 0 0 Vdc 0 10 Vdc Go to tNP MM 10 0 Vdc 0 10 Vdc Go to tNP MM AFL airflow reading Main Menu Sub Menu Configuration AO1 AO2 tO4 tO3 tO2 Out Output config tO1 scroll menu items AFL airflow read...

Page 11: ...mp 1 Mr Motor signal ramp OFF select set value Mr Motor direction dIr direct rEv reverse Go to SEt MM Air Airflow integral time 0 0 60 min Pb2 Heat prop band2 2 0 C 4 0 F 0 5 5 C 1 9 F db2 Heat dead b...

Page 12: ...1 127 OP1 odd parity 1 stop bit CFG Modbus comport config nP2 no parity 2 stop bits EP1 even parity 1 stop bit MA Modbus address 1 1 246 Modifiable only if all DS2 DIP switches are set to OFF Go to Hr...

Page 13: ...rature read by the external temperature sensor Adjust the offset by comparing it with a known value e g thermometer If the sensor is not connected or short circuited then the unit displays the sensor...

Page 14: ...99 5 100 1 0 99 9 When balancing use only two of the four modes available either Close Motor and Open Motor or Minimum Airflow and Maximum Airflow more precise You must press the button to save any ch...

Page 15: ...e Control Mode appears for 5 seconds Press the button to scroll through the following control modes These options can vary depending on the options selected in Temp Control Mode and Enable OnOff Contr...

Page 16: ...pe On Off On Off On Off On Off On Off On Off On Off TO3 Close Pos 40 40 40 40 40 40 40 TO3 Open Pos 0 0 0 0 0 0 0 TO4 Ramp HR2 HR2 HR2 HR1 OFF HR1 HR1 TO4 Signal Type Pulse On Off Pulse On Off On Off...

Page 17: ...Notes...

Page 18: ......

Page 19: ......

Page 20: ...need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 51...

Reviews: