NEP BDM-600 Installation And Operation Manual Download Page 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7. COMMISSIONING   

WARNING:

 

ENSURE THAT ALL AC AND DC WIRING IS CORRECT. ENSURE THAT NONE OF THE 

AC AND DC WIRES ARE PINCHED OR DAMAGED AND THAT ALL JUNCTION BOXES ARE 

PROPERLY SEALED CLOSE.   

Following these steps to commission the BDM-600 PV system:   
1. Turn on the circuit breakers for each of the BDM-600 AC branch circuits.   
2. Turn on the main service panel u

lity-grid AC circuit breaker. Your system will start 

producing powe

r a�

er no more than 5 minutes.   

3.  The  BDM-600  will  start  to  send  performance  data  over  the  power  lines  using 

power  line  communica

on  (PLC)  to  the  BDG-256.  The 

me  required  for  each 

BDM-600 in the system to communicate to the BDG-256 will vary with the number 

of microinverters in the system. For a typical residen

al system data acquisi

on 

should take no more than 20-25 minutes. 

 

 

8. OPERATING INSTRUCTIONS

 

The BDM-600 begins opera

on only a

er su

cient DC voltage from the PV module 

is received. At this point the status LED will star

t fla

shing.   

Status: standby   

The LED light toggles on and o

 at two (2) second intervals

 

Red

: error detected

 

Orange

: no error, but not yet communica

ng to the BDG-256

 

Green

: no error, and communica

ng to the BDG-256 

Status: producing power   

The LED light toggles on and o

 at one (1) second intervals

 

Orange

: not communica

ng to the BDG-256

 

Green

: communica

ng to the BDG-256 

Status: grounding fault 

The LED light is in 

solid red

 color.   

In case of a fault, the BDM-600 enters a protec

ve mode and stops outputing power.   

The  fault  message  is  usually  sent  to  a  connected  BDG-256  gateway  through  the 

power line communica

on.    The error message is  then displayed on the screen of 

BDG-256 gateway by a 16-bit error code. The table below shows the codes:   

Error code 

Error 

Bit-0 

DC over voltage 

Bit-1 

DC under voltage 

Bit-2 

hardware error 

Bit-3 

Inverter over voltage 

Bit-4 

Frequency over 

Bit-5 

Frequency under 

Bit-6 

AC voltage RMS over 

Bit-7 

AC voltage RMS under 

Bit-8 

Peak AC voltage over 

Bit-9 

AC current RMS over 

Bit-10 

Peak AC current over 

Bit-11 

Temperature over 

Bit-12 

ADC error 

Bit-13 

GFDI fault indicator 

Bit-14 

Relay fault (BDM-250-AU/BDM-250-EU only) 

Bit-15 

PLC Communica

on Error   

 

9. TROUBLESHOOTING AND MAINTENANCE 

WARNING: 

DO NOT ATTEMPT TO REPAIR THE BDM-600; IT CONTAINS NO 

USER-SERVICEABLE PARTS. IF TROUBLESHOOTING METHODS FAIL, PLEASE CONTACT NEP FOR 

FURTHER ASSISTANCE. 

WARNING: 

NEVER DISCONNECT THE DC WIRE CONNECTORS UNDER LOAD. ENSURE THAT 

NO CURRENT IS FLOWING IN THE DC WIRES PRIOR TO DISCONNECTING. AN OPAQUE 

COVERING MAY BE USED TO COVER THE MODULE PRIOR TO DISCONNECTING.   

WARNING: 

BDM-600 IS POWERED BY DC POWER FROM PV MODULES. MAKE SURE YOU 

DISCONNECT THE DC CONNECTIONS AND RECONNECT DC POWER TO WATCH FOR THE TWO 

SECONDS LED ON/OFF TOGGLE AFTER DC IS APPLIED.   

11

10 

Summary of Contents for BDM-600

Page 1: ...433 3252 FAX 81 092 433 3171 China Address No 1 Anhe Rd Tsingtao Export Processing Zone Tsingtao China 266113 TEL 86 532 87963900 FAX 86 532 81100917 Email info northernep com Web h p www northernep com h p www nep japan com h p www micro inverter jp Rev 2017 01 12 North American Version Dual Module Microinverter BDM 600 Installa on and Opera on Manual ...

Page 2: ...Shipping Informa on 05 6 INSTALLATION 05 6 1 Pre installa on 05 6 2 Installa on Steps 06 Step 1 System Layout 06 Step 2 Connect the Wiring Harnesses 07 Step 3 Install the AC Branch Circuit Junc on Box 08 Step 4 Ground the System 08 Step 5 Complete the Connec on Map 09 Step 6 Connect the PV Modules 09 Step 7 Install the BDG 256 Monitoring Gateway 09 7 COMMISSIONING 10 8 OPERATING INSTRUCTIONS 10 9 ...

Page 3: ...ds of power electronics automa c control signal processing and communica ons each holding mul ple U S and world patents in their specialty areas NEP has a complete product line of grid ed solar inverters including 180W 600W micro inverters 1 5kW 5kW single phase solar inverters 10kW 500kW three phase solar inverters and rapid shutdown devices Field deployment results demonstrated high system efficie...

Page 4: ...THIS MANUAL IS NOT COVERED BY THE WARRANTEE INSTALLATIONS SHOULD BE DONE ONLY BY CERTIFIED ELECTRICIANS NOTHING INSIDE THE INVERTER SHOULD BE MODIFIED ONLY NEP APPROVED CABLING SHOULD BE USED TO CONNECT MICROINVERTERS ALL INSTALLATIONS SHOULD FOLLOW THE LOCAL ELECTRICAL CODES ADDITIONAL PROTECTION FOR THE AC WIRING FROM THE INVERTERS SHOULD BE PROVIDED AND MAY BE REQUIRED BY LOCAL AND NATIONAL WIR...

Page 5: ...rail or frame a ach clamps 2 per microinverter AC junc on boxes mul ple op ons possible Cordgrip with locknut or strain relief fi ng one per branch circuit A subpanel may be required for systems with mul ple branch circuits Cable clips Sockets wrenches torque wrench mul meter small flat head screwdriver and mirror with extension rod Lightning and surge suppressor recommended 5 3 Lightning and Surge ...

Page 6: ...NSTALLED ON ALL UNUSED AC CONNECTORS UNUSED AC BDM 600 WIRE HARNESS CONNECTORS ARE LIVE WHEN THE SYSTEM IS ENERGIZED BY T The AC branch circuit should look as pictured below 6 2 Installa on Steps WARNING CONNECT BDM 600S TO THE ELECTRICAL UTILITY GRID ONLY AFTER RECEIVING PRIOR APPROVAL FROM THE UTILITY COMPANYAND LOCAL AHJ WARNING BE AWARE THAT ONLY QUALIFIED PERSONNEL CAN CONNECT BDM 600 TO THE ...

Page 7: ...ou create Step 6 Connect the PV Modules Connect all AC all system inter wiring connec ons prior to installing the PV modules 1 Mount the PV modules in the posi ons corresponding to their associated BDM 600 microinverter Each BDM 600 comes with two sets of oppositely sexed DC connectors 2 Connect the posi ve DC wire from the first PV module to the nega vely marked DC connector male pin on the BDM 60...

Page 8: ...nica ng to the BDG 256 Green communica ng to the BDG 256 Status grounding fault The LED light is in solid red color In case of a fault the BDM 600 enters a protec ve mode and stops outputing power The fault message is usually sent to a connected BDG 256 gateway through the power line communica on The error message is then displayed on the screen of BDG 256 gateway by a 16 bit error code The table ...

Page 9: ...talled to reduce the interference to PLC communica on If there are two or more separate BDM systems close by it is highly recommended to install LCF for each micro inverter system to block interference from adjacent other systems 7 If the problem persists please call customer support at NEP WARNING DO NOT ATTEMPT TO REPAIR THE BDM 600 IT CONTAINS NO USER SERVICEABLE PARTS IF TROUBLESHOOTING METHOD...

Page 10: ...ower Grid Frequency Hz 59 3 60 5 Adjustable THD 3 at rated power Power Factor 0 99 at rated power SYSTEM EFFICIENCY CEC Efficiency 95 5 Night Time Tire Loss W 0 11 PROTECTION FUNCTIONS Over Under Voltage Protec on Yes Over Under Frequency Protec on Yes An Islanding Protec on Yes Over Current Protec on Yes Reverse DC Polarity Protec on Yes Overload Protec on Yes Ground Fault Detec on Integrated Prote...

Page 11: ... NEP product specifica ons including high input voltage from generators and lightning strikes c the product if repairs have been done to it other than by NEP or its authorized service centers herea er ASCs d the product if it is used as a component part of a product expressly warranted by another manufacturer e the product if its original iden fica on trade mark serial number markings have been defa...

Page 12: ...or Code s Brief Fault Descrip on and Photos monitoring gateway is required for verifica on Installa on Informa on Modules Used Modules Quan ty Inverters quan ty per string Installa on Company Name Installer Name For the informa on on our warranty terms and condi ons please see our website www northernep com en All fields must be completed in order to process claim Customer Signature Date All rights ...

Page 13: ...12 0011 福岡市博多区博多駅前 3 10 24 藤井ビル 1F TEL 81 092 433 3252 FAX 81 092 433 3171 China Address No 1 Anhe Rd Tsingtao Export Processing Zone Tsingtao China 266113 TEL 86 532 87963900 FAX 86 532 81100917 Email info northernep com Web h p www northernep com h p www nep japan com h p www micro inverter jp ...

Reviews: