17
FG7C CONTROLLER
Mapping
MAPPING ENERGIZER ALARM(S) TO IO CARD
A text file, etoimapplus.txt, i.e. energizer to io card mapping file is used to map each energizer
address to a relay card address.
This file can be made in notepad and has to be uploaded to the FG7 with the use of the web
interface.
The notation used is that Energizer#4 corresponds to Energizer with address 4
Table 1
: How the etoimap.txt file is structured
Line
Number
Function associated with the line
Lines of
etoimap.txt
file
Explanation
1
The IO Card Address that Energizer#1 will
communicate with
33
Energizer#1 alarms via IO
Card 33
2
The combination of any alarm condition(note 1)
that will activate relay 1
2
Only Fence 1 Alarm
activates relay 1
3
The combination of any alarm condition(note 1)
that will activate relay 2
6
Fence 1 or Fence 2 alarm
activates relay 2 (2+4)
4
The combination of any alarm condition(note 1)
that will activate relay 3
14
Fence 1 or Fence 2 or Gate
Alarm activates relay3
(2+4+8)
5
The combination of any alarm condition(note 1)
that will activate relay 4
32
Only Tamper Alarm
activates relay 4
6
The combination of any alarm condition(note 1)
that will activate relay 5
4
Only Fence 2 Alarm
activates relay 5
7
The combination of any alarm condition(note 1)
that will activate relay 6
2048
Mains present activates
relay 6
8
The combination of any alarm condition(note 1)
that will activate relay 7
65
Comms fail or Sync fail
activates relay 7 (1+64)
9
The combination of any alarm condition(note 1)
that will activate relay 8
4096
Panic alarm activates relay 8
10
Latching or not latching of relays with alarm
condition
38
Fence 1, Fence 2 and
Tamper Alarm conditions
are not latched (2+4+32)
11
The IO Card Address that Energizer#2 will
communicate with
34
Energizer#1 alarms via IO
Card 34
12
The above sequence repeated etc. etc.
Notes:
1)
Table 2 has a number associated with each alarm condition on an energizer. Select the
desired alarm condition(s) that can activate any relay and add the numbers together.