FENCE STATE AT POWER ON
2 0 2 _ * #
Sets the operating state that the fence is returned to after a complete power failure has
ended.
? = 0 (off), 1 (on) or 2 (fence returns to on/off state at power loss)
Factory default value is
2022*#
(fence returns to on/off state at power loss)
A complete power failure occurs when the energizer shuts down due to the internal battery
running flat during a prolonged mains power failure.
*Can be directed to a specific zone, using KEYPAD ZONE FOCUS.
FENCE INTERFERENCE ALARM
2 0 3 _ * #
Enables or disables the fence interference detected alarm function.
? = 0 (disabled), 1 (enabled)
Factory default value is
2031*#
(enabled) for DRUID_18
Factory default value is
2030*#
(disabled) for DRUID_114
Fence interference may occur when a neighboring fence comes into contact with the fence
been driven by this energizer or when criminals attempt to defeat the energizer fence
alarm detection mechanism.
*Can be directed to a specific zone, using KEYPAD ZONE FOCUS.
FENCE HIGH POWER VOLTAGE
2 1 _ _ * #
Sets the energizer output voltage during high power operation.
k = kilo volts, v = x100 volts
Programmable range is
2160*#
(6.0kV) to
2197*#
(9.7kV)
Factory default value is
2197*#
(9.7kV)
The fence condition indication value is affected by this value. Setting this value to a lower
voltage will cause the fence condition indication to increase towards 9 (excellent) as the
energizer works less hard to maintain the lower set voltage on the fence.
*Can be directed to a specific zone, using KEYPAD ZONE FOCUS.
Programmable options
21
k v
?
?