SLAVE ENERGIZER PRESENT
5 0 0 _ * #
Enable or disable whether a slave energizer should be present.
? = 0 (Master only 2 zone system) or 1 (Slave connected 4 zone system)
Factory default value is
5000*#
(Master only 2 zone installation)
The master energizer needs to be configured as to whether a slave energizer is connected, creating
a four zone system, or if it is a master only two zone system. This is required so that a
communication failure (service alarm) can be generated should the slave energizer not respond to
the master’s request for information, and so that the keypad can be dealt with correctly as either a
two or four zone installation.
EXPANSION CARD CONFIGURATION
5 0 2 _ * #
Selects the configuration used in assigning a function to each of the ten relays and each of
the four inputs on the expansion card.
? = configuration to select (contact NEMTEK for customized configurations)
Programmable range is
5020*#
to
5022*#
Factory default value is
5020*#
(Configuration 0)
The expansion card address jumper must be set to 1for the master energizer info or 2 for the slave.
Configuration 0.
Relay 1 = Expansion card communication timeout.
Relay 6 = Mains fail.
Relay 2 = Zone 1 On/Off status.
Relay 7 = Battery low or Service alarm.
Relay 3 = Zone 2 On/Off status.
Relay 8 = Zone 1 in “Check”.
Relay 4 = Zone 1 in low voltage mode.
Relay 9 = Zone 2 in “Check”.
Relay 5 = Zone 2 in low voltage mode.
Relay10 = Energizer tamper state.
Input 1 = Zone 1 On / Off control.
Input 3 = Zone 1 Low / High voltage select.
Input 2 = Zone 2 On / Off control.
Input 4 = Zone 2 Low / High voltage select.
Configuration 1.
Relay 1 = Expansion card communication timeout.
Relay 6 = Zone 1 in “Check”.
Relay 2 = Zone 1 On/Off status.
Relay 7 = Zone 2 in “Check”.
Relay 3 = Zone 2 On/Off status.
Relay 8 = Mains fail, battery low, service, tamper.
Relay 4 = Zone 1 in low voltage mode.
Relay 9 = Zone 1 in alarm.
Relay 5 = Zone 2 in low voltage mode.
Relay10 = Zone 2 in alarm.
Input 1 = Zone 1 On / Off control.
Input 3 = Zone 1 Low / High voltage select.
Input 2 = Zone 2 On / Off control.
Input 4 = Zone 2 Low / High voltage select.
Configuration 2.
Relay 1 = Expansion card communication timeout.
Relay 6 = Mains fail.
Relay 2 = Zone 1 On/Off status.
Relay 7 = Battery low, service alarm.
Relay 3 = Zone 2 On/Off status.
Relay 8 = Zone 1 high voltage alarm.
Relay 4 = Zone 1 in low voltage alarm.
Relay 9 = Zone 2 high voltage alarm.
Relay 5 = Zone 2 in low voltage alarm.
Relay10 = Tamper.
Input 1 = Zone 1 high voltage activate.
Input 3 = Zone 1 low voltage activate.
Input 2 = Zone 2 high voltage activate.
Input 4 = Zone 2 low voltage activate.
Programmable options