62
IF THE ERROR OCCURS
DURING A TEMPERATURE
CONTROLLED
BLAST
CHILLING CYCLE – the
needle probe functions as both
needle
probe
and
chiller
compartment probe and the
blast chilling cycle continues;
we recommend that parameter
i0 is set to 2 (COMPRESSOR
PROTECTION)
IF THE ERROR OCCURS
DURING STORAGE – the
needle probe functions as the
chiller compartment probe and
storage continues
PARAM MIN.
MAX.
U.M.
DEF.
DEFROSTING
d0
0
99
h
8
defrosting interval (3)
0 = interval defrosting is never
activated
d3
0
99
min
30
defrosting time
0 = defrosting is never activated
d7
0
15
min
2
dewatering time
PARAM MIN.
MAX.
U.M.
DEF.
TEMPERATURE ALARMS
A1
0
99.0
°C/°F
(1)
10.0
temperature below alarm limit
the minimum temperature alarm
is activated; refer to A2 (5)
A2
0.0
1
---
1
type of minimum temperature
alarm
0 = no alarm
1 = refers to parameters r9 and
rA (namely “r9 – A1” and “rA –
A1”)
A4
0.0
99.0
°C/°F(1
)
10.0
temperature above alarm limit
the maximum temperature alarm
is activated; refer to A5 (5)