background image

10

  Appendix A - Controller Programming:  

Parameters Explained

Parameter  

 

 

Value  

Range  

Example

Input Switch Behaviors

Tank Level Switch delay (actuation and de-actuation)  

 

 

Seconds  

 

2.0

 

 This specifies the time that the tank switch must be closed or open before the controller accepts it as a valid 

condition. The function is to prevent nuisance tripping of the RO especially in small tanks or turbulent tanks

Pressure Switch delay (actuation and de-actuation)  

 

 

Seconds  

 

3

 

 This specifies the time that the pressure switch must be closed or open before the controller accepts it as a valid 

condition. Since pressure switches usually have built-in hysteresis this value is set at 0.

Pretreat Switch delay (actuation and de-actuation)  

 

 

Seconds  

 

2

 

This is the time that the pretreat switch must be OPEN before the controller accepts it as a valid condition.

Pump/Inlet Solenoid Behaviors

Pump start delay 

 

 

Seconds  

 

10

  

On RO start-up, after the tank switch opens, the inlet solenoid valve is energized. When the inlet pressure switch 

closes this begins the “Pump start delay”. If the pressure switch remains closed, the pump will start after 10 seconds.

Inlet Solenoid stop delay Seconds 1

 

 This value sets the delay for the inlet solenoid valve to be de-energized following the de-energizing of the motor on RO 

shut down. The purpose is to prevent the pump from operating against a closed suction as the pump spins down.

Low Inlet Pressure Behaviors

Pump start retry interval (restart delay after LP fault)  

 

 

Seconds  

 

60

 

 When the inlet pressure switch opens, the controller de-energizes the motor and the inlet solenoid valve remains open. 

The controller will continue to monitor the inlet pressure switch. After the switch is closed for the duration of the 

“Pump start retry interval” the motor is reenergized.

Low pressure fault shutdown, # of faults  

 

 

Faults 

 

5

Low pressure fault shutdown, time period to count faults   

 

Minutes  

 

10

Low pressure fault shutdown, reset after shutdown  

 

 

Minutes  

 

60

  

These three values work together to determine how the RO handles Low Pressure conditions. The first two values, 

“# of faults” and “time period to count faults”, sets the limit for the number of low fault conditions over time that are 

required to place the RO in “Low Pressure Fault Shutdown”. The third value sets the duration of the “Low Pressure 

Fault Shutdown” which is the period that the RO will remain idle before trying to restart. The purpose of the Low 

Pressure Fault Shutdown is to prevent an RO from turning OFF/ON repeatedly without any limit. 

Low pressure time-out fault  

 

 

Seconds  

 

60

 

 If the inlet valve is open, but the pressure isn’t sufficient to close the inlet pressure switch, the RO would run 

indefinitely on line pressure. This value sets the time limit for the RO to operate with the inlet valve open with Low 

Pressure as indicated by an Open inlet pressure switch before a Low Pressure Fault is added to the counter above

Summary of Contents for NRO ROC-3HE

Page 1: ...Nelsen NRO ROC 3HE System Controller Documentation Systems with 3 hp Motors and Above...

Page 2: ...CPU 4 5 Controller Detail TB 6 6 Conductivity Probe Installation Figure 5 7 Controller Programming Accessing Hidden Menus Figure 6 8 System Start up w Permeate Flush 8 Controller Programming Program...

Page 3: ...y Ratings relays are fused with a 6A fuse Feed Solenoid 0 5A Voltage is the same as motor supply voltage Flush Solenoid 0 5A Voltage is the same as motor supply voltage Motor Contactor Coil 0 5A Volta...

Page 4: ...2 Figure 1 Simplified Schematic...

Page 5: ...3 Figure 1 1 Field Wiring Diagram...

Page 6: ...al Run Manual Flush Supply Power Connections Motor Connections Terminal Board CPU4 Board Conductivity Probe Connections Display 4 line 20 character Clear concise feedback on the RO s status Alarm Disp...

Page 7: ...5 Typical Configuration Figure 3 Controller Detail CPU 4 Typical Configuration...

Page 8: ...6 Figure 4 Controller Detail Terminal Board TB 1 See Fig 1 for schematic...

Page 9: ...ductivity Probe Installation Install the Conductivity Probe in the Run of a Tee or equivalent location Orient the probe so that air can not become trapped in the area near the probe F L O W FLOW Condu...

Page 10: ...m On Off button This will switch to the Hidden Menus as shown above 3 If not already on the RO Presets Program Press the Up or Down Arrows until you reach this screen 4 Once on the RO Presets Program...

Page 11: ...stop delay Seconds 1 1 1 1 Pump start retry interval restart delay after LP fault Seconds 60 60 60 60 Low pressure fault shutdown of faults Faults 5 5 5 5 Low pressure fault shutdown time period to c...

Page 12: ...ng against a closed suction as the pump spins down Low Inlet Pressure Behaviors Pump start retry interval restart delay after LP fault Seconds 60 When the inlet pressure switch opens the controller de...

Page 13: ...ts the duration of the Idle Flush 0 disabled Timed Manual Run Duration of Manual Run Minutes 5 Timed Manual Flush Duration of Manual Flush Minutes 5 Conductivity Probe Sample Rate Seconds 2 Conductivi...

Page 14: ...t If RO Not Working and Display Shows Tank Full or Tank Full Draw Down 1 If using a single point high level float switch the jumper in the wiring instructions must be installed This needs to be checke...

Page 15: ...ing Programming Interface Overview The Programming interface is a Windows based tool for making changes to the ROC software This screen shows the RO settings available There are 4 field selectable set...

Page 16: ...rvice 1 To obtain warranty service contact your selling dealer for a Return Material Authorization RMA 2 You will be required to provide a Your name and address b A description of the problem 3 Packag...

Reviews: