Page 17
306-0008-002-001 Rev500 Neets 4 relay
Relay=2,Action=Set,Time=20\CR
Command to be used when manually moving the screen up:
Relay=2,Action=Release\CR
Relay=3,Action=Set,Time=26\CR
Adding additional security
The system we have designed now is working and with the screen and lift wired up in high security mode,
there are no chances for shortening the motors.
Many motors specifies that a certain time is required from power is disconnected from one direction to
power is connected in the other direction.
By grouping the relays that controls the screen and lift, it is possible to define the time that must elapse
from one relay is “Released” to the next is “Set”.
Device
Minimum time for changing
from one direction to
another
Screen
1,0 seconds
Lift
2,5 seconds
The commands the must be used to achieve this function is:
Group=1,Action=Lock\CR
Group=2,Action=Lock,Delay=2.5\CR
It is only necessary to send the two commands one time, the settings will be stored in the relay box, also
after power has been removed.