TRANSIT Ultimate | installation guide
15/40
3.3
TRANSIT configuration
This chapter describes how to configure the TRANSIT Ultimate reader for OSDP installations.
TRANSIT firmware requirements
The OSDP Interface Board / PCC485 requires to use one of the standard TRANSIT firmware versions, since these
support the manual LED and relay control function.
•
P80 v3.00 (no configuration required, use default settings)
•
P81 v3.35
•
P82 v3.08
•
P83 v3.04
•
P84 v3.06
•
P85 v3.01
Newer versions are also supported as they will be backwards compatible.
Configuration settings
The relay activation and LED control must both be set to manual mode.
This is best done using the NEDAP P81TEST software. Download this software from our partner portal
https://portal.nedapidentification.com
Start NEDAP P81TEST software and connect to the reader using the USB or RS232 interface.
1.
Click Options, Digital I/O.
2.
Disable automatic relay activation.
3.
Disable automatic LED control.
Figure 10: TRANSIT configuration for OSDP applications.