background image

 

 

 

 

If it is necessary to install a heater closer to a combustible 
surface than the stated requirements in Section 2 of this 
Installation Guide, it must be done in accordance with 
Australian Standard AS/NZS 2918:2001 Section 3, Tables 3.1 
& 3.2. 

Shield Construction:- The shield shall be constructed from a 
heat resistant material. The shield must be fixed to the 
surface that requires protection and NOT the heater. 

The Standard allows three options to reduce stated 
clearances. 

 

Single layer of continuous material with Minimum Air Gap of 

12mm—Clearance Factor = 0.40 

Single layer of continuous material with Minimum Air Gap of 

25mm—Clearance Factor = 0.30 

Two spaced layers of continuous material with Minimum Air 

Gaps of 12mm + 12mm—Clearance Factor = 0.20 

The shielding must be open at the top and bottom (vented) 
to allow a continuous air flow. It is this air flow that keeps 
the surface requiring protection cool. Fixings should not 
impede this air flow. 

The shielding needs to go far enough along and up the wall 
so that the original side and rear required clearances are not 
compromised. As the flue is now closer to the wall the 
shielding should also protect the wall from the flue pipe. 

 

For example: 

Side wall clearance for the Nectre 15 LE is 750 mm. 

A 12mm gapped shield on the wall with a factor of 0.40. 

Calculate:- 750 mm x 0.40 = 300 mm. This is the new side 
wall minimum clearance. 

The shielding needs to be large enough so that none of the 
original clearances of 750 mm are compromised. 

 

 

 

 

 

 

 

 

 

The flue system used when installing the heater MUST 
comply with the current installation standard AS/NZS 2918. 

Full instructions on the installation of the flue will be supplied 
with the flue kit. These MUST be followed closely, including 
the minimum exit height from the top of the floor protector 
being not less than 4.6m, and the minimum exit height above 
the roof line of roof ridge as detailed in the instructions. 

 

The flue must be fitted with either of the following: 

1)

 

Rear flue shield

 – 900 mm long, minimum 160

° arc, 

stainless steel unpainted 

rear flue shield with 25mm 

gap between it and the 150mm diameter active flue, OR 
 

2)

 

Decro-mesh with 900mm long inner shield :

–  

a)

 

A full length, half radius perforated decro-mesh flue 
shield extending from the heater through into the 
drop box penetrating the ceiling.  

b)

 

A 900 mm half round stainless steel inner reflector 
must be fitted inside the decro-mesh. Using tin-
snips, cut three 10mm tabs into the top and bottom 
of the inner reflector. Bend the centre tabs in, and 
the ones closest to the edge out to create an air gap 
between it, the outer decro-mesh, and the 150mm 
active flue. 

 
 
 

 

 

 

 

3. Reducing Clearances to Combustible Walls 

4. INSTALLING THE FLUE 

Tabs bent out 

Tab bent in 

Reviews: