background image

 

 

2.2 

Positioning the Heater

 

First review the necessary clearances specified below before 
considering where to position the heater along with the 
appliance dimensions in Section “8. Technical Drawings”.  

Also check the practicability of installing the flue system in 
relation to any obstructing roof beams before positioning the 
heater. 

These clearance distances can only be reduced if the 
surrounding walls are made of non-combustible material, eg. 
stone, brick, or concrete.  If non-combustible material, 
distance can be reduced to 100 mm. Alternatively, shielding 
of the wall(s) can reduce clearances (refer to next section for 
more detail). 

Depending on the type of flue shielding used, the clearances 
to combustible surfaces varies. 

 

2.2.1  Standard Installation:

  

 

 

 

Flue shielding 

A (mm) 

B (mm) 

C (mm) 

900mm rear flue shield 

750 

(*450) 

175 

(*125) 

300 

Decro-mesh with 
900mm inner reflector 

750 

(*450) 

175 

300 

(Note: 

*

 when fitted with side shields) 

 

 

 

 

2.2.2  Corner Installation: 

 

 

 

 

Flue shielding 

C (mm) 

D (mm) 

900mm rear flue shield 

300 

750 

(*225) 

Decro-mesh with 
900mm inner reflector 

300 

750 

(*225) 

   (Note: 

*

 when fitted with side shields)

 

 

2.3 

Floor Protector (Hearth)

 

Unless the heater will be standing on a heat resistant floor 
such as concrete slab with slate or tiles, it will be necessary to 
provide a floor protector (hearth). 

The dimensions given in above (Section 2.2) are the minimum 
required for the floor protector. It must extend no less than 
300 mm in front of the door opening, no less than 275mm 
either side of the door opening, and extend under the heater. 
Minimum dimensions for floor protector are 900mm wide by 
900mm deep.  It may be desirable, for example aesthetic 
reasons, for the floor protector to be larger than these 
minimum dimensions. 

The floor protector shall be constructed of non-combustible 
material no less than 15mm thick and with a thermal 
conductivity not greater than 0.33W/m 

º

K, eg. compressed 

cement sheet. The floor protector may be laid directly on the 
combustible floor. 

For more details and variations on floor protectors refer to 
AS/NZS 2918:2001 Clause 2.2, 3.3.1, & 3.3.2. 

 

 

 

Reviews: