In this case, the system prevents the charge only by alternator. The alarm stops being
displayed when the temperature returns within the range of 0°C/45°C.
..
5
52
2
DISCHARGE
3Lion
allow a higher discharge than the current supported by the internal BMS. Please refer
to the following table.
DISCHARGE
CURRENT*
MAXIMUM DISCHARGE TIME
L100/L100B
L100P
L150P
100A
55
MINUTES
60
MINUTES
90
MINUTES
125A
25
MINUTES
50
MINUTES
70
MINUTES
150A
5
MINUTES
20
MINUTES
25
MINUTES
175A
2
MINUTES
9
MINUTES
10
MINUTES
200A
30
SECONDS
30
SECONDS
30
SECONDS
* Measurements performed at an ambient temperature of 20 °C, and starting temperature of
the lithium battery of 20 °C.
It is recommended to discharge the
3Lion
battery with temperatures between -20°C e
+60°C.
6.
OPERATION CHECK
Once the system is installed, you can test its functionality by performing the following
tests:
1) With the engine switched off, and with all the equipment powered off, check that the
voltage shown on the display relative to the 3Lion battery, is equal to the voltage
measured with the tester positioned on the 3lion poles (tolerance of ± 0.15V).
2) With the engine switched off, and with all the equipment powered off, check that the
voltage shown on the display relative to the engine is equal to the voltage measured
with the tester positioned on the engine battery poles (tolerance ± 0.15V).
3) With the engine switched off, turn on some pieces of equipment on the vehicle, and
check that a negative current is displayed on the display. With the ammeter clamp,