background image

TRUE ROUND FIRE & FIRE/SMOKE DAMPER INSTALLATION, 
OPERATION & MAINTENANCE INSTRUCTIONS

IOM  -  TRUE  ROUND  FIRE  &  FIRE/SMOKE  DAMPERS  -  1016                      

NCA MANUFACTURING INC. • 1985 CARROLL ST. • CLEARWATER, FL 33765 • 727.441.2651 • www.ncamfg.com

4

2 ANGLE METHOD INSTALLATION:

Guidelines:

The Two Angle Method (Figure 4) is approved for the

following:

    

A.

 Masonry/concrete or stud/gypsum partitions

    

B.

 1 ½ Hour rated True Round Fire or Fire/Smoke Dampers

    

C.

 Vertical or horizontal orientation

    

D.

 All UL approved sizes shown in Table 1 on page 2 of this

        IOM

In this install method, the damper shall be installed in a stud/

gypsum or masonry fire partitition in the vertical or horizontal

position (blade shaft running horizontally within the parameters 

of Detail A) with a retaining plate flush against both sides of the 

fire partition (see Figure 4).

Installation:

1.

 With the factory installed retaining plate flush to the fire

     partition, place another retaining plate (if manufactured

     in the field - see Figure 5) on the opposite side of the damper

     sleeve and slide it forward until it becomes flush with the

     opposite side of the partition.

2.

 Place the Splice Clip (see Figure 3 on page 3) over the cut   

     portion of the retaining plate and secure it with 4 - #10 sheet 

     metal screws or rivets as shown in Figure 4.

3.

 Secure the clip angles (see Figure 3 on page 3) to the 

     retaining plate and damper sleeve as illustrated in Figure 4, 

     6 and 7.

D

B

2

Cut (Cover with

         Splice Clip)

A

B

D

2

+ 1-1/2”

(38 mm)

All dimensions in inches

A and B = Damper Dia.

plus 3” (76 mm)

Blade

Shaft

Auxiliary

Operating

Jackshaft

1” Min. Typ.

(25.4 mm)

Clearance

Factory Supplied

Plate

Angle

Damper

Sleeve

Retaining

Plate

Fastener

Clip

Angle

UL Approved Wall 

or Floor Design

Figure 4: Angles on 2 Sides

with Splice Clips

Typical masonry or metal stud opening. (Refer to the Framing 

Requirements for Wood or Steel Stud Walls For Fire and Fire/

Smoke Dampers In Drywall Partitions).

Figure 5: Retaining Plate Detail

Figure 6:

Figure 7: Cross Section of

Damper in a Wall (Floor Similar)

Axle

30˚

+/- 30˚ Max. Off Horizontal

(in either direction)

Detail A

2 Angle

Installation Method

Splice Clip

(see Fig. 3)

Reviews:

Related manuals for FSD-RD-211