background image

TRUE ROUND FIRE & FIRE/SMOKE DAMPER INSTALLATION, 
OPERATION & MAINTENANCE INSTRUCTIONS

IOM  -  TRUE  ROUND  FIRE  &  FIRE/SMOKE  DAMPERS  -  1016                      

NCA MANUFACTURING INC. • 1985 CARROLL ST. • CLEARWATER, FL 33765 • 727.441.2651 • www.ncamfg.com

3

FIRE & FIRE/SMOKE DAMPER SLEEVES & MOUNTING CLIPS:

Damper Sleeves:

All true round fire and fire/smoke dampers must have an 

integral sleeve (see Figure 1).

Guidelines:

1.

 Sleeves must be of the SAME GAUGE or heavier than

    the duct to which it is attached if one of the UL approved

    breakaway connections is used (see seperate “UL App-

    roved Breakaway Duct Connections” supplement).

2. 

Gauges shall conform to SMACNA or ASHRAE duct 

    standards.

3.

 Sleeves shall not extend beyond the fire barrier more

    than 16” (406mm) on the operator side or 6” (152mm) on the

    opposite side.

4.

 The connecting duct shall terminate at the

    integral sleeve and is connected by using either of the

    following:

        

A.

 Minimum of 3 - #10 sheet metal screws spaced equal

              distance around the sleeve for 22” (559mm) and ~

              smaller duct.

        

B.

 Minimum of 5 - #10 sheet metal screws spaced equal   

             distance around the sleeve for greater than 22”

              (559mm) duct.

        

C.

 4” (101mm) drawband.

5.

 Clearance between the damper sleeve and the round or

    square wall opening shall be a minimum of 1/2” (13 mm)

    and a maximum of 1” (25mm).

    Note:

 When installing the round damper into a square

    opening, these clearances refer to the middle point of each

    side of the square, not the corners.

6.

 Damper will be factory supplied with one retaining plate

    secured to the damper sleeve on the operator side of the

    damper.

Mounting Clips:

A minimum of 4 equally spaced 20 gauge galvanized steel clip

angles (see Figure 3) shall be attached to both the integral

sleeve and the retaining plate (see Figures 1 and 2). The clip

angles shall be attached with 1/8” (3.2mm) rivets, #10 x

1/2” (12.7mm) steel metal screws, bolts or welds.

Note:

 In metal stud/gypsum applications, the retaining plate

may be in front of or behind the gypsum, directly against the

metal studs.

1-1/2”

(38 mm)

Clip Angle Detail 20 Ga. 

(1) Galv. Steel

1-1/2”

(38 mm)

1-1/2”

(38 mm)

Splice Clip Detail

1-1/2”

(38 mm)

Same length as

cut in damper/

retaining plates

Figure 1: Angles on 2 Sides

Figure 2: Angle on 1 Side

Figure 3: Mounting Clips

Typical stud or masonry opening. (Refer to the Framing  Requirements for 

Wood or Steel Stud Walls For Fire and Fire/Smoke 

Dampers In Drywall Partitions)

Typical masonry or metal stud opening. (Refer to the Framing  Requirements 

for Wood or Steel Stud Walls For Fire and Fire/Smoke 

Dampers In Drywall Partitions)

Splice Clip

(see Fig. 3)

Splice Clip

(see Fig. 3)

Reviews: