background image

EW089.309_en 

 rev.B 

Gas detection Control Unit 

 UCE1    

27/04/2021 

Gas detection systems for industrial environments 

3 of 4 

 

 

Detector failure test 

 

Simulate a failure in the detector as follows: 

-

 

disconnect  the  cable  of  the  detector  and  verify  the  following 

alerts: 

 

 

 

 

 

 

 

-

 

reconnect the detector and press the “Reset/Test” to return the 

control  unit  to  normal  operating  mode,  making  the  sure  the 

conditions of the various interfaces are reset 

 

Normal operation 

 

This is the normal operating phase of the control unit during which 

both  gas  alarm  monitoring  and  self-testing  of  the  instrument 

(detector)  and  the  system  (control  unit)  are  active.  During  this 

phase,  where  there  are  no  alarms  and/or  abnormalities,  the 

control unit display shows the following: 

 

 

 
 

 

 

 

 

 

 

When  dangerous  concentrations  of  gas  are  detected,  the  control 

unit  enters  the  gas  alarm  phase  and  carries  out  the  following 

operations: 

 

 

 

 

 

 

 

 

 

 

Once the gas alarm condition is normalised, the control unit needs 

to  be  reset  to  its  normal  operating  status.  Press  the  “Reset/Test 

button on the front of the control unit to reset it. 

If  there  are  abnormalities  (detector  and/or  control  unit),  the 

control unit will show the following display: 

 

 

 

 

 

 

 

Once the failure is fixed, the control unit needs to be reset to its 

normal 

operating status. Press the “Reset/Test button on the front 

of the control unit to reset it. 
 

Caution:

 

it is advisable to repeat the operating test at least 

once  a  year,  or  after  a  prolonged  period  of 

stoppage and in any case, every time the detector 
is replaced. 

 

 

Caution 

The  average  lifetime  of  the  URx13  and 

URx20/21..  detectors  is  5 years from  installation 

date.  They  must  be  replaced  before  the  end  of 
the  5th  year  of  use.  The  average  lifetime  of 

detectors  is  calculated  for  use  in  a  typical 

environment, normally free from polluting agents 

(gases,  solvents  etc.).  More  frequent  and  higher 

concentrations 

of 

these 

substances 

can 

accelerate  the  normal  oxidisation  process  of  the 

sensing  element,  subsequently  shortening  its 

lifetime. 

 

 

GAS ALARM 

 

If  an  alarm  signals  a  gas  leak  or  the  presence  of  carbon 

monoxide, proceed as follows: 

-

 

put out flames and switch off all gas equipment 

-

 

do not for any reason switch on or off lights or any electrical 

equipment 

-

 

open doors and windows to air the environment 

-

 

look  for  and  eliminate  the  cause  of  the  alarm.  If  this  is  not 

possible,  leave  the  building  and  contact  emergency  services 

from outside. 

 
 

ENVIRONMENTAL COMPATIBILITY AND DISPOSAL 

 

This product has been designed and constructed  

using materials and processes that take into account  

the environmental issue. Refer to the following notes for disposal 

of the product at the end of its working life, or when it is replaced: 

-

 

for  disposal  purposes,  this  product  is  classified  as  an  electric 

and  electronic  device:  do  not  dispose  of  it  with  normal 

household waste, in particular as regards the printed circuit 

-

 

comply with all local laws in force 

-

 

as far as possible reuse basic materials to keep environmental 

impact to a minimum 

-

 

use local depots and waste recycling companies, or contact the 

supplier or manufacturer to return used products or to ask for 

information on environmental compatibility and waste disposal 

-

 

the product packaging can be reused. Keep it for future use or 

to return the product to the supplier. 

 

 

TROUBLESHOOTING 

 

Problem 

Possible cause 

 

NC valve does not open 

 

-

 

Valve not connected 

-

 

Alarm in progress 

-

 

Detector  warm-up  phase  in 

progress 

-

 

Defective detector 

-

 

Presence of failure 

 

 

NO valve does not close 

 

-

 

Valve not connected 

-

 

Connection cables cut 

-

 

No alarm active 

 

 

“Reset/Test”  button  does  not 

reset to initial conditions 

 

-

 

Alarm in progress 

-

 

Failure  occurring  in  control 

unit  

 

Sensor  in  alarm  immediately 

after the end of the preheating 

phase 

During  the  preheating  phase, 

the  sensor  did  not  reach 

thermal stabilization. 

Wait  further  minutes  and  then 

reset the alarm with the "Reset 

/ Test" button 

 

Interface  

Positive logic 

Negative logic 

Detector Failure LED 

Yellow 

Off 

On 

Alarm buzzer 

 

Intermittent 
sound 

Intermittent sound 

Failure output 

 

Off  

On 

 

Interface  

Positive logic 

Negative logic 

Power supply LED 

Green 

On 

On 

Failure LED 

Yellow 

On 

Off 

Gas alarm LED 

Red  

On 

Off 

Alarm buzzer 

 

No sound 

No sound 

Alarm relay 

 

Energised 

De-energised 

Failure output 

 

On 

Off 

 

Interface  

Positive logic 

Negative logic 

Detector alarm LED 

Red 

Off 

On 

Alarm buzzer 

 

Continuous 
sound 

Continuous sound 

Alarm relay 

 

De-energised 

Energised 

(permanently 

or 

pulsed  depending 
on E2) 

Failure output 

 

On  

Off 

 

Interface  

Positive logic 

Negative logic 

Failure LED 

Yellow 

Off 

On 

Alarm buzzer 

 

Intermittent 
sound 

Intermittent 
sound 

Failure output 

 

On  

Off 

 

 

Reviews: