38 Installing the Water Heater
3.5.3 Measuring Vent Length (Indoor Models Only)
Refer to the table to find the maximum vent length based on the number of elbows. (Two 45 degree elbows
count as one 90 degree elbow.)
Vent type
Diameter
Max number of 90° Elbows Max. Vertical and Horizontal (Total) Vent Length
Concentric
3 in. / 5 in.
(80 mm / 125 mm)
4
43 ft (13 m)
Number of 90° Elbows
Maximum vent length
0
43 ft (13 m)
1
38 ft (11.5 m)
2
33 ft (10 m)
3
28 ft (8.5 m)
4
23 ft (7.0 m)
Note
The Maximum Length does not include any elbows.
3.5.4 Terminating the Vent
Before installing the water heater, determine what type of vent termination is appropriate for the installation
location and situation. Examples in this section describe typical venting configurations, but they do not include
all possible options.
The following terminations can be used. Refer to the vent manufacturer’s instructions for detailed installation
procedures.