44 Reference
Appendix D.1.1 Compliance with UL Regulations
For UL compliance, the following instructions must be met when
operating gateway.
●
The units shall be powered by listed LPS or Class 2 power supply
suited to the expected operating temperature range.
●
The interconnecting power connector and power cable shall:
-
Comply with local electrical code
-
Be suited to the expected operating temperature range
-
Meet the current and voltage rating for gateway
●
Furthermore, the interconnecting power cable shall:
-
Be of length not exceeding 3.05 m (118.3”)
-
Be constructed of materials rated VW-1, FT-1 or better
●
If the unit is to be installed in an operating environment with a
temperature above 65°C, it should be installed in a Restricted
Access Area requiring a key or a special tool to gain access.
●
This device must not be connected to a LAN segment with
outdoor wiring.
Appendix D.1 Specifications
Gateway Part Number GXXX001933
Electrical
Connections
One 6-pin Phoenix connector with:
RS-485 port (+ / - / gnd)
Power port (+ / - / Frame-gnd)
One 2-pin Phoenix connector with:
One FTT-10 LonWorks port
One Ethernet 10/100 BaseT port
Approvals
CE certified; UL 916 approved; WEEE
compliant; EN 60950-1,
EN 50491-3 and CSA C22-2 standards; FCC
Class A Part 15;
RoHS compliant; CSA 205 approved
LonMark Certified
Power
Requirements
9-30 VDC or 12 - 24 VAC
Physical
Dimensions
11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2
x 1.6 in.)
Weight
0.2 kg (0.4 lbs)
Operating
Temperature
-40°C to 75°C (-40°F to167°F)
Surge
Suppression
EN61000-4-2 ESD EN61000-4-3 EMC
EN61000-4-4 EFT
Humidity
5 - 90% RH (non-condensing)
(Specifications subject to change without notice)
Figure 40: Specifications
Appendix D. Reference