Vendor Information – Navien
Point Name
LonWorks Name
LonWorks SNVT
Sub31 Number of CH operation
nvo31NmCH_Op_XXX
SNVT_count_f
Sub31 Total time of CH operation
nvo31TotTmCH_XXX
SNVT_time_hour
Sub31 Current amount of gas
nvo31CurGas_XXX
SNVT_count_f
Sub31 Total amount of gas
nvo31TotGas_XXX
SNVT_count_f
Boiler On/Off command
nviBlOnOfCmd_XXX
SNVT_count_f
SH supply setpoint setting
nviSHSupSPSt_XXX
SNVT_temp_p
SH return setpoint setting
nviSHRetSPSt_XXX
SNVT_temp_p
DHW setpoint setting
nviDHW_SP_St_XXX
SNVT_temp_p
Error reset command
nviErrResCmd_XXX
SNVT_count_f
Boiler setpoint in DHW operation
nviBlSPDHWOp_XXX
SNVT_temp_p
Outdoor reset curve heatload setting
nviOtRsCvHtS_XXX
SNVT_count_f
Maximum outdoor temperature setting
nviMxOtTmpSt_XXX
SNVT_temp_p
Minimum outdoor temperature setting
nviMnOtTmpSt_XXX
SNVT_temp_p
WWSD temperature setting
nviWWSDTmpSt_XXX
SNVT_temp_p
WWSD On differential setting
nviWWSDOnDif_XXX
SNVT_temp_p
Boost interval time setting
nviBstIntTme_XXX
SNVT_time_min
Cascade Initial op units setting
nviCsInOpUnt_XXX
SNVT_count_f
CH supply min temperature setting
nviCHSupMnTp_XXX
SNVT_temp_p
CH supply max temperature setting
nviCHSupMxTp_XXX
SNVT_temp_p
CH return min temperature setting
nviCHRetMnTp_XXX
SNVT_temp_p
CH return max temperature setting
nviCHRetMxTp_XXX
SNVT_temp_p