background image

If you have any questions concerning these instructions, please call National Customer Service 

800.482.1717

.

 

Assembly Instruction

 

1610 Royal Street

 

Jasper, Indiana  47546 

 

 

Telephone 800.482.1717

 

Fax 812.482.8800

 

www.NationalOfficeFurniture.com

 

 

3248959

 

Rev, B

 

 

 

LOCHLYN

 

FREESTANDING FRAME 

BUILD

 

9

 

Wall Anchoring Method

 

WARNING: Tip Over Hazard. Do not 

install shelves, modules, or tops onto the frame 

until it is leveled and permanently anchored. Installation before permanent anchoring 
can lead to instability and injury from unit tipping over.

 

Wall anchors are only to be used when unit is parallel to the wall. Floor anchoring must 
be used for perpendicular layouts. If choosing the wall anchoring method, the floor 
anchor plates can be removed from the unit.

 

All 

frame units from three (3) tiers through six (6) tiers are 

required 

to be permanently anchored

 to the floor (see Floor Anchoring 

Method pgs. 7 

-

 8; steps F1

-

F7) or wall (see Wall Anchoring Method 

pgs. 9 

-

 12; steps W1

-

W9) regardless of configuration, usage, or if 

multiple units are ganged together. 

 

Note 1: 

National defines a structural wall as a load

-

bearing wall constructed of materials such as: 

poured concrete, concrete block, or studs. Wood studs must be a nominal 2" x 4" size minimum. 
Metal studs must be 

C

” 

channel, 20

-

gauge thick minimum. Metal or wood studs must be on 

centers no greater than 24" and have maximum height of 

14’ 

restrained at floor and ceiling. 

Interior walls shall be designed to resist not less than a force of 5 lbs. per square foot applied 
perpendicular to wall. The deflection of such wall under a load of 5 lbs. per square foot shall not 
exceed 1|240 of the span for walls with brittle finishes, and 1|120 of the span for walls with 
flexible finishes (per uniform building code section 2390B). If you have any questions concerning 
your load

-

bearing structures, please consult your architect or structural engineer.

 

All frames will have one (1) wall anchor hardware set per vertical upright frame section, included in 
the hardware kit. All wall anchor sets must be attached to a stud, or drywall or concrete anchors.

 

Note 2: 

If joining multiple units with a ganging kit, build and position all frames in their final 

location, then install ganging kits prior to anchoring. 

 

Contact Customer Service if wall anchor hardware is missing or damaged. 

Do not 

install frames 

with less than the required number of anchors.

 

Note 3: 

Align the wall anchor plates behind the vertical frame members (Figure T) to reduce 

visibility.  However, if necessary to attach an anchor properly to a wall stud, the wall anchor 
brackets can be installed horizontally (Figure U), where a small portion of the bracket will be visible.

 

 

 

FIGURE T

 

 

FIGURE U

 

Summary of Contents for LOCHLYN

Page 1: ...instructions before using this product Failure to follow the instructions and safety precautions in this manual can result in injury or damage to equipment KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE...

Page 2: ...ss and identification in the later steps of assembly Figure A Model Assembly Instruction Sheet Model AI Sheet includes frame dimension references and parts list for specific model 2Select a frame sub...

Page 3: ...s noted in step 3 There shouldn t be any remaining junction blocks from the hardware bag or open 3 hole patterns after these steps are complete Figure G 6Retrieve the Model AI Sheet with image of asse...

Page 4: ...re are different length horizontal bars from one column to the next Reference the Model AI Sheet to determine which length bar is correct CAUTION Do not deviate from the provided Model AI Sheet and in...

Page 5: ...evels until all junction blocks are fully secured to the horizontal bars of the frame The vertical sub assembly should be flush with the horizontal bars of the frame Figure K Note While assistance is...

Page 6: ...their midpoint CAUTION Do not extend glides beyond 13mm 0 5in from the glide s fully retracted position Extending glides more than 13mm 0 5 in can make the shelving unit unstable If installing a one 1...

Page 7: ...drawers above three 3 tiers can lead to instability and injury from unit tipping over Floor Anchoring Method All frames will have at least four 4 anchor plates mounted to the floor glides on both end...

Page 8: ...impact of required anchors align the anchor plate in line and directly underneath the cross bar of the sub assembly frame section that runs front to back A bolt is required in this scenario as there i...

Page 9: ...studs must be C channel 20 gauge thick minimum Metal or wood studs must be on centers no greater than 24 and have maximum height of 14 restrained at floor and ceiling Interior walls shall be designed...

Page 10: ...Reference fastener table Figure V for recommended hardware for various wall construction types Select the hardware and install to the wall using all of the wall anchors provided following the next ste...

Page 11: ...tionalOfficeFurniture com 3248959 Rev B LOCHLYN FREESTANDING FRAME BUILD 11 W4Mark the wall to locate the wall brackets vertically in line with the frame tubing or horizontally where necessary to reac...

Page 12: ...nal installation position so all mounting brackets are in line vertically or horizontally based on required installation orientation Check that the frame is still level and wall anchor brackets align...

Reviews: