background image

     

TEST REPORT

 

..............MANUAL ALARM CONTROL PANEL  ................... SPARE 
ZONES .......................

CONTRACTOR NAME

          :

CLIENT /SITE 

          :

BILL NO. / CHALLAN NO            :
QUANTITY

                       :

SERIAL NO.

                       :

AC FUSE

                                   : .5 AMP 

DC FUSE 

           : 6 AMP 

FIRE CONDITION                            : SYSTEM OK 
FAULT CONDITION 

            : SYSTEM OK 

FIRE & FAULT RELAY

            : SYSTEM OK 

DETECTION & HOOTER LINE 

:  SYSTEM OK

This is to certify that the manual alarm control panel Supplied as 

per detail has been manufactured by NATIONAL SECURITY DEVICE  
at Delhi -92 .Test producer are conducted as per guideline by costumer. 
Although all products tested as per IS:2189 stranded.

Test Report No . ERTL 

It is again certified that all the featured laid down in the panel as 

per customers  specification have been provided and checked . 

Date of Testing :

Date of Issued :

                     Q. C. MANAGER 

Client Copy 

(N)/90 (4)-2K 7/Q0094 dated 14 May 2007.

9

Summary of Contents for All-Safe 4 Zone P.A. SYSTEM

Page 1: ...S ec urity Devices OFFICE 485 14 SARPANCH KA BARA MANDAWALI FAZALPUR DELHI 110092 WORKS 2 A Patparganj Mayur Vihar Phase 1 Delhi 110091 PHONE 011 22751020 64603599 Fax 011 22751020 MOBIL 9891222660 E mail mailanilrawat gmail com NATIONAL SECURITY DEVICES ...

Page 2: ... Mechanical Construction 3 Installation Commissioning Installation Commissioning 4 Indicator and controls Indicator Controls 5 Input and Output Zone Monitor Power Monitor Output Controls 6 Technical Data 7 8 Warranty 9 Test Report About The product ...

Page 3: ...echnology computerized R D in house tool room assambly plant and of course our skilled workmanship with the strict quality control This manual intended as a complete guide to the model manual control panel This microprocessor based fire alarm control Panel is implemented with wide range of application required in basic alarm Automation This panel is designed to meet the general requirement of IS 2...

Page 4: ...visual warning with Audio able tone Zone wise fire fault Operating indication Facility Zone ON indication Facility P A Announcement Hooter Output with silence facility Manual test Evacute facility Selector with All Call facility Rugged CRCA sheet with powder coated finish Modular Construction Relay Output for associate gadgets Stand by battery backup with Built in charging MECHANICAL CONSTRUCTION ...

Page 5: ...ed clean the interior of the enclosure ensuring all masonry debris and drilling swords are removed COMMISSIONING Check all entered wiring is correctly identified and also check all free from fault condition by a multi meter Connect the external wiring into their respective terminal and ensure the end of line EOL resistor is placed at the last device of circuit Prior to the power up of the panel co...

Page 6: ...ILANCE RESET LOCK KEY ALL CALL SWITCH SELECTOR SWITCH 17 19 20 SELECTOR LED MIKE SWITCH MICROPHONE CONTROL FEATURES NATIONAL SECURITY DEVICES OFFICE 485 14 SARPANCH KA BARA MANDAWALI FAZALPUR DELHI 11092 PHONE 011 22751020 64603599 FAX 01122751020 MOBILE 9891222660 E MAIL MAILANILRAWAT GMAIL COM TITLE Fire Alarm With PA System Panel Controls Features ...

Page 7: ... are OFF state In case multiple zone indicates OPEN LCD alternately display the massage with zone no SHORT In case of zone line detector Short LCD Display the information of respective zone with single YELLOW LED glow Normally these LED are OFF state In case multiple zone indicates SHORT LCD alternately display the massage with zone no PA SYSTEM SELECTOR 1 SELECTOR INDICATION LED mounted with sele...

Page 8: ...larming By pressing this switch When needs evacuation of building in fire emergency this switch is used WALK TEST This switch is provided common for all zone It is maintance purpose switch This switch disable hooter for 15 minute At that 15 minute period detector call point will activated without alarming the hooters This is used for one man test purpose After 15 minute system goes automatically i...

Page 9: ... 100volt HTR 1 to HTR 8 are operate by selector switch 1 to HTR 1 manner So this panel work both hooter public address system This panel also act for conducting further operation for air handling unit or BMS use etc other associated gadgets Be sure for EOL at appropriate point for right function of manual call box short circuit of HTR line can damage the product COMMON ANNOUNCEMENT SPEAKER This te...

Page 10: ... HOOTER OUTPUT 24V 2Amax RELAY RATING 24V 3Amp POTENTIAL FREE CONTACT FIRE FAULT VOLTAGE CHARGER 26 6V ZONE POWER NORMAL 15 6MA ZONE ALARM CURRENT 35MA ZONE AC FUSE RATING 500MA DC FUSE RATING 6Amp BATTERY FUSE RATING 6Amp DIMENSIONS 420X325X120 MM WEIGHT 10 KG APPROX TECHNICAL DATA 6 ...

Page 11: ......

Page 12: ...e date of purchase______________________________ During this period any items found defective will be repaired at our works or though service center Terms Condition 1 Serial o Sticker should not be broken tempered mismatch as our record 2 Product not used as per described guideline or hassling with electronic part Serial No Stamp NATIONAL SECURITY DEVICES NATIONAL SECURITY DEVICES 8 ...

Page 13: ...y that the manual alarm control panel Supplied as per detail has been manufactured by NATIONAL SECURITY DEVICE at Delhi 92 Test producer are conducted as per guideline by costumer Although all products tested as per IS 2189 stranded Test Report No ERTL It is again certified that all the featured laid down in the panel as per customers specification have been provided and checked Date of Testing Da...

Page 14: ...Dealers Name Address Model No Manual alarm control SR No Sale date ...

Page 15: ...LE E Mail Website 485 14 SARPANCH KABARA MANDAWAL FAZALPUR DELHI 110092 2 A Patparganj MayurVihar Phase 1 Delhi 110091 011 22751020 6460359 9 011 22751020 09891222660 E mail mailanilrawat gmail com www agnialarms com Security Devices ...

Reviews: