ZONE-3
+
-
ZONE-4
+
-
ZONE-5
+
-
ZONE-6
+
-
ZONE-7
+
-
ZONE-8
+
-
HTR-1
+
-
HTR-2
+
-
HTR-3
+
-
HTR-4
+
-
HTR-5
+
-
HTR-6
+
-
HTR-7
+
-
COM
HTR
C
FIRE
NO NC
RELAY
ZONE LINE For Detector & Manual Call Box Connection
+
-
24V
+
-
HTR-8
HOOTER(D.C.)
HOOTER
CUM SPEAKER
+
-
ZONE-1
+
-
ZONE-2
+
C
FAULT
NO NC
RELAY
Terminal Connection Diagram
HOOTER LINE FOR Announcement Cum Hooter
5
ZONE-1 TO ZONE-8 Connector :-
These are the input terminal to connect the manual call box & DETECTOR. In case of smoke detected or glass
break at any manual call box then system provide 100volt A.C. to respective hooter & potential free contact
changes it state .Be sure for EOL at appropriate point for right function of manual call box.
HTR-1 to HTR-8 :-
In announcement case HTR-1 to HTR-8 provide out put to speaker as 100volt.
HTR-1 to HTR-8 are operate by selector switch -1 to HTR-1 manner.So this panel work both hooter &
public address system.This panel also act for conducting further operation for air handling unit or BMS use etc.
other associated gadgets. Be sure for EOL at appropriate point for right function of manual call box.
short circuit of HTR line can damage the product.
COMMON ANNOUNCEMENT SPEAKER:-
This terminals provide 100A.C. Output .Connecting LMT type HTR with this terminal provide direct output of
hooter our sound.
COMMON HOOTER:-
This terminals provide output 24 D.C. in case of fire from any zone line.
FIRE POTENTIAL FREE CONTACT :-
These are relay contact that change over its position in case of fire either it is multi zone or single zone.
FAULT POTENTIAL FREE CONTACT :-
These are relay contact that change over its position in case of fault either it is cross zone or single zone.
+
-
100V
COMMON
Announcement
SPEAKER
COMMON