device in an NI chassis that has been evaluated as Ex nC IIC T4,
Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
Caution
You must make sure that transient
disturbances do not exceed 140% of the rated voltage.
Caution
The system shall only be used in an area of
not more than Pollution Degree 2, as defined in
IEC 60664-1.
Caution
The system shall be mounted in an
ATEX/IECEx-certified enclosure with a minimum
ingress protection rating of at least IP54 as defined in
IEC/EN 60079-15.
Caution
The enclosure must have a door or cover
accessible only by the use of a tool.
Wiring the NI 9852
The NI 9852 has two 9-pin male D-Sub connectors that provides
connections to a CAN bus. Each port on the NI 9852 has pins for
CAN_H and CAN_L, to which you connect the CAN bus signals.
Connect these signals using twisted-pair cable.
NI 9852 Getting Started Guide
|
© National Instruments
|
5