Floating Differential Connections

1 M

Resistor

NI 9207

AI0+

AI0–

COM

Voltage
Source

+

Grounded Connections

Voltage
Source

+

AI0+

AI0–

COM

NI 9207

Single-Ended Connections

+

AI0+

AI0–

COM

Voltage
Source

NI 9207

Connecting an External Power Supply

You must connect an external power supply with a 0 to 30 V voltage range to the

NI-9207. This power supply provides the current for the devices you connect to the

module. You can connect only one external voltage supply to the NI-9207.

1. Connect the positive lead of the power supply to V

sup

.

2. Connect the negative lead of the power supply to COM.

ni.com

8

NI-9207 Getting Started

Summary of Contents for NI-9207

Page 1: ...NI 9207 Getting Started 2022 07 01...

Page 2: ...e Applications 6 Preparing the Environment 6 NI 9207 7 Floating Differential Connections 7 Grounded Connections 8 Single Ended Connections 8 Connecting an External Power Supply 8 Connecting a Loop Pow...

Page 3: ...o the documentation for each component in the system to determine the safety and EMC ratings for the entire system Safety Guidelines Caution Observe all instructions and cautions in the user documenta...

Page 4: ...up to 5 000 m 500 V RMS verified by a 5 s dielectric withstand test Safety Guidelines for Hazardous Locations The NI 9207 is suitable for use in hazardous locations and hazardous locations and nonhaz...

Page 5: ...rdous locations in ambient temperatures of 40 C Ta 70 C If you are using the NI 9207 in Gas Group IIC hazardous locations you must use the device in an NI chassis that has been evaluated as Ex nC IIC...

Page 6: ...in the product documentation Furthermore any changes or modifications to the product not expressly approved by National Instruments could void your authority to operate it under your local regulatory...

Page 7: ...AI3 AI1 Vsup Vsup Vsup Vsup Vsup AI6 AI4 AI2 AI0 Vsup Vsup Vsup Vsup Vsup AI7 AI5 AI3 AI1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 Table 1 Si...

Page 8: ...ing an External Power Supply You must connect an external power supply with a 0 to 30 V voltage range to the NI 9207 This power supply provides the current for the devices you connect to the module Yo...

Page 9: ...ire Current Transducer OUT NI 9207 COM AI8 External Power Supply Vsup COM Vsup 2 A Max NI 9207 Connection Guidelines Make sure that devices you connect to the NI 9207 are compatible with the module sp...

Page 10: ...9207 Specifications on ni com manuals for more information about overvoltage protection Where to Go Next CompactRIO NI CompactDAQ RELATED INFORMATION C Series Documentation Resources ni com info cser...

Page 11: ...gister to register your NI product Product registration facilitates technical support and ensures that you receive important information updates from NI NI corporate headquarters is located at 11500 N...

Reviews: