Isolation Voltages

Channel-to-channel

None

Channel-to-earth ground up to 2,000 m altitude

Continuous

250 V RMS, Measurement Category II

Withstand

2,300 V RMS, verified by a 5 s withstand test

Channel-to-earth ground up to 5,000 m altitude

Continuous

60 V DC, Measurement Category I

Withstand

1,000 V RMS, verified by a 5 s withstand test

Safety Guidelines for Hazardous Locations

The NI-9203 is suitable for use in hazardous locations; , and hazardous locations;

and nonhazardous locations only. Follow these guidelines if you are installing the

NI-9203 in a potentially explosive environment. Not following these guidelines may

result in serious injury or death.

Caution

 Do not disconnect I/O-side wires or connectors unless power has

been switched off or the area is known to be nonhazardous.

Caution

 Do not remove modules unless power has been switched off or

the area is known to be nonhazardous.

Caution

 Substitution of components may impair suitability for Class I,

Division 2, or Zone 2.

Caution

 The system must be installed in an enclosure certified for the

intended hazardous (classified) location, having a tool secured cover/door,

where a minimum protection of at least IP54 is provided.

ni.com

4

NI-9203 Getting Started

Summary of Contents for NI 9203

Page 1: ...NI 9203 Getting Started 2022 07 06...

Page 2: ...or Hazardous Locations 4 Electromagnetic Compatibility Guidelines 5 Special Conditions for Marine Applications 6 Preparing the Environment 6 Connecting the NI 9203 6 Overvoltage Protection 7 Connectin...

Page 3: ...s Refer to the documentation for each component in the system to determine the safety and EMC ratings for the entire system Safety Guidelines Caution Observe all instructions and cautions in the user...

Page 4: ...lines if you are installing the NI 9203 in a potentially explosive environment Not following these guidelines may result in serious injury or death Caution Do not disconnect I O side wires or connecto...

Page 5: ...he system shall be mounted in an ATEX IECEx certified enclosure with a minimum ingress protection rating of at least IP54 as defined in IEC EN 60079 15 Caution The enclosure must have a door or cover...

Page 6: ...te link Notice In order to meet the EMC requirements for marine applications install the product in a shielded enclosure with shielded and or filtered power and input output ports In addition take pre...

Page 7: ...M that is internally connected to the isolated ground reference of the module Overvoltage Protection The NI 9203 provides overvoltage protection for each channel Note Refer to the NI 9203 Specificatio...

Page 8: ...velopment self help such as tutorials and examples Visit ni com services to learn about NI service offerings such as calibration options repair and replacement Visit ni com register to register your N...

Reviews: