Appendix C
Fieldbus Parameters
©
National Instruments Corporation
C-17
FieldPoint FP-3000 User Manual
RCAS_OUT
The back calculation output used by the host when establishing a Remote
cascade loop.
RESET
The time constant for the integral component of the PID block. It is
measured in seconds per repeat.
RESTART
Allows the user to restart the device remotely. Table C-12 lists restart
values.
Caution
Using
Restart to Default
causes all your configured parameters in the
FP-3000 to revert to their factory default settings.
ROUT_IN
The cascade input set by a remote host. This is propagated to the output of
the block when it is in
ROut
mode. If the block is in
ROut
mode and this
parameter is not updated in
SHED_ROUT
time (a parameter in the resource
block), the block enters mode shedding. Mode shedding allows the block to
degrade from
ROut
mode into some higher priority mode. For more
information on mode shedding, refer to Appendix D,
.
ROUT_OUT
This is the back calculation output used by the host when trying to establish
a remote output loop. While the loop is being established, it is the current
value of the output channel and can be used by the host to initialize for
smooth transfer of control.
Table C-12.
Restart Values
Value
Behavior
Restart
Resource
Restarts the device.
Restart to
Defaults
Restarts the device, restoring all parameter values to
default values.
Restart
Processor
Restarts the device as if the power was cycled.