background image

© 

National Instruments Corp.

7

FP-AI-112 and cFP-AI-112

(

number of input ranges with 60 Hz filter

×

 0.10 s +

(

number of channels with 500 Hz filter

×

 0.007 s + 

(

number of input ranges with 500 Hz filter

×

 0.012 s + 0.16 s 

Update Period

For the fastest performance, configure all unused channels for the 
500 Hz filter setting and for an input range in use on one or more 
other channels with the 500 Hz filter setting. For example, if 
10 channels are configured for 0–10 V input and 500 Hz, four 
channels are configured for 0–5 V and 60 Hz, and two channels 
are unconnected, use the FieldPoint software to configure the 
unconnected channels for 0–10 V input and 500 Hz filter setting.

Some combinations of two input ranges count as only one range for 
calculating update rates. Those combinations are 

±

60 mV and 

±

300 mV; 0–1 V and 0–5 V; and 

±

1 V and 

±

5 V.

The update rate does not affect the rate at which the network 
module reads the data. Set up your application so that the update 
rate is faster than the rate at which the network module polls the 
[c]FP-AI-112 for data.

Status Indicators

The [c]FP-AI-112 has two green status LEDs, 

POWER

 and 

READY

. After you insert the [c]FP-AI-112 into a terminal base or 

backplane and apply power to the connected network module, the 
green 

POWER

 indicator lights and the [c]FP-AI-112 informs the 

network module of its presence. When the network module 
recognizes the [c]FP-AI-112, it sends initial configuration 
information to the [c]FP-AI-112. After the [c]FP-AI-112 receives 
this initial information, the green 

READY

 indicator lights and the 

module is in normal operating mode.

Upgrading the FieldPoint Firmware

You may need to upgrade the FieldPoint firmware when you add 
new I/O modules to the FieldPoint system. For information on 
determining which firmware you need and how to upgrade your 
firmware, go to 

ni.com/info

 and enter 

fpmatrix

.

Summary of Contents for FieldPoint cFP-AI-112

Page 1: ... c FP AI 112 is a FieldPoint analog input module with the following features 16 analog voltage input channels Eight voltage input ranges 0 1 V 0 5 V 0 10 V 60 mV 300 mV 1 V 5 V and 10 V 16 bit resolution 50 and 60 Hz filter settings 250 Vrms CAT II continuous channel to ground isolation verified by 2 300 Vrms 1 minute dielectric withstand test 40 to 70 C operation Hot swappable Installing the FP A...

Page 2: ...place Figure 1 Installing the FP AI 112 Installing the cFP AI 112 The cFP AI 112 mounts on a Compact FieldPoint backplane cFP BP x which provides operating power to the module Installing the cFP AI 112 onto a powered backplane does not disrupt the operation of the FieldPoint bank To install the cFP AI 112 refer to Figure 2 and complete the following steps 1 Align the captive screws on the cFP AI 1...

Page 3: ...tions for each of the 16 input channels and for an optional external power supply to power field devices The cFP CB x connector block provides the same connections Each channel has one input terminal VIN for voltage input All 16 inputs are referenced to the COM terminals which are internally connected to each other and to the C terminals The channels share eight VSUP terminals all of which are int...

Page 4: ...xternal power supply and the V terminals The wiring diagrams in this document show fuses where appropriate Table 1 lists the terminal assignments for the signals associated with each channel The terminal assignments are the same for the FP TB x terminal bases and the cFP CB x connector blocks Table 1 Terminal Assignments Channel Terminal Numbers VIN VSUP COM 0 1 17 18 1 2 17 18 2 3 19 20 3 4 19 20...

Page 5: ...tage source without an external power supply to one channel of the c FP AI 112 Figure 3 Voltage Source without External Power Supply Figure 4 shows how to connect a voltage source with an external power supply to one channel of the c FP AI 112 Figure 4 Voltage Source with External Power Supply VSUP VIN V C 100 MΩ Input Impedance COM c FP AI 112 Voltage Source Input Circuitry VSUP VIN V C 100 MΩ In...

Page 6: ...lable for each channel The filters on the c FP AI 112 input channels are comb filters that provide notches of rejection at multiples or harmonics of a fundamental frequency You can select a fundamental frequency of 50 60 or 500 Hz At the 50 and 60 Hz settings the c FP AI 112 applies 95 dB of rejection at the fundamental frequency and at least 60 dB of rejection at each of the harmonics In many cas...

Page 7: ...and 5 V The update rate does not affect the rate at which the network module reads the data Set up your application so that the update rate is faster than the rate at which the network module polls the c FP AI 112 for data Status Indicators The c FP AI 112 has two green status LEDs POWER and READY After you insert the c FP AI 112 into a terminal base or backplane and apply power to the connected n...

Page 8: ...cuits that can be at hazardous potentials under normal conditions unless the product is specifically designed for such an application as is the c FP AI 112 Even though the c FP AI 112 is designed to handle applications with hazardous potentials follow these guidelines to ensure a safe total system There is no isolation between channels on the c FP AI 112 If a hazardous voltage is present on any ch...

Page 9: ...n most cases Occasionally however a temporary conductivity caused by condensation must be expected Do not operate FieldPoint products in an explosive atmosphere or where there may be flammable gases or fumes If you need to operate FieldPoint products in such an environment the FieldPoint products must be in a suitably rated enclosure Operate the c FP AI 112 at or below Installation Category II Ins...

Page 10: ...Hz 60 mV 65 mV 3 µV 25 µV 300 mV 325 mV 16 µV 100 µV 1 V 1 04 V 40 µV 300 µV 5 V 5 2 V 190 µV 1500 µV 10 V 10 4 V 380 µV 3000 µV 0 1 V 0 1 04 V 20 µV 300 µV 0 5 V 0 5 2 V 95 µV 1500 µV 0 10 V 0 10 4 V 190 µV 3000 µV Includes quantization errors and typical rms noise Characteristic Filter Settings 50 Hz 60 Hz 500 Hz Update period 1 25 1 75 s 1 05 1 45 s 0 27 0 32 s Input bandwidth 3 dB 13 Hz 16 Hz ...

Page 11: ...ranted Accuracy at 15 to 35 C of Reading of Full Scale 60 mV 0 03 0 05 0 05 0 3 300 mV 0 03 0 015 0 05 0 1 1 V 0 03 0 008 0 05 0 04 5 V 0 03 0 005 0 05 0 02 10 V 0 03 0 005 0 05 0 02 0 1 V 0 03 0 005 0 05 0 03 0 5 V 0 03 0 003 0 05 0 01 0 10 V 0 03 0 003 0 05 0 01 Nominal Input Range Typical Accuracy at 40 to 70 C of Reading of Full Scale Warranted Accuracy at 40 to 70 C of Reading of Full Scale 6...

Page 12: ...Continuous 250 Vrms Installation Category II Dielectric withstand 2 300 Vrms 1 minute Channel to channel isolation None Environmental FieldPoint modules are intended for indoor use only For outdoor use they must be mounted inside a sealed enclosure Operating temperature 40 to 70 C Storage temperature 50 to 85 C Humidity 10 to 90 RH noncondensing Maximum altitude 2 000 m at higher altitudes the iso...

Page 13: ...is product is designed to meet the requirements of the following standards of safety for electrical equipment for measurement control and laboratory use IEC 61010 1 EN 61010 1 UL 61010 1 CAN CSA C22 2 No 61010 1 Note For UL hazardous locations and other safety certifications refer to the product label or visit ni com certification search by model number or product line and click the appropriate li...

Page 14: ...ompliance information To obtain the DoC for this product visit ni com certification search by model number or product line and click the appropriate link in the Certification column Mechanical Dimensions Figure 5 shows the mechanical dimensions of the FP AI 112 installed on a terminal base If you are using the cFP AI 112 refer to the Compact FieldPoint controller user manual for the dimensions and...

Page 15: ...lephone support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 0 662 45 79 90 0 Belgium 32 0 2 757 00 20 Brazil 55 11 3262 3599 Canada Calgary 403 274 9391 Canada Ottawa 613 233 5949 Canada Québec 450 510 3055 Canada Toronto 905 785 0085 Canada Vancouver 604 685 7530 China 86 21 6555 7838 Czech Republic 420 224 235 774 Denmark 45 45 76 26 00 Finland 38...

Page 16: ... com are trademarks of National Instruments Corporation Product and company names mentioned herein are trademarks or trade names of their respective companies For patents covering National Instruments products refer to the appropriate location Help Patents in your software the patents txt file on your CD or ni com patents ...

Reviews: