FP-AI-112 and cFP-AI-112
4
ni.com
You can use an external power supply to power field devices.
Connect the positive lead of the external power supply to both
V terminals and the negative lead to both C terminals. Ensure that
the current through both V terminals can never exceed 2 A.
Install 2 A maximum, fast-acting fuses between the external power
supply and the V terminals. The wiring diagrams in this document
show fuses where appropriate.
Table 1 lists the terminal assignments for the signals associated
with each channel. The terminal assignments are the same for the
FP-TB-
x
terminal bases and the cFP-CB-
x
connector blocks.
Table 1.
Terminal Assignments
Channel
Terminal Numbers
V
IN
V
SUP
COM
0
1
17
18
1
2
17
18
2
3
19
20
3
4
19
20
4
5
21
22
5
6
21
22
6
7
23
24
7
8
23
24
8
9
25
26
9
10
25
26
10
11
27
28
11
12
27
28
12
13
29
30
13
14
29
30
14
15
31
32
15
16
31
32