NI 9221 with Screw Terminal and NI 9221 with
Spring Terminal Safety Voltages
Connect only voltages that are within the following limits.
Channel-to-COM
±60 VDC maximum
Channel-to-channel
None
Channel-to-earth ground
Continuous
250 Vrms, Measurement
Category II
Withstand
2,300 Vrms, verified by a 5 s
dielectric withstand test
Measurement Category II is for measurements performed on
circuits directly connected to the electrical distribution system.