background image

6

DSI INTEGRATED CONTROL MODULE

CONTROL 

STATUS

GREEN LED

STEADY ON

FAST FLASH

1 FLASH
2 FLASH
3 FLASH
4 FLASH

STEADY OFF

Normal operation, no call for heat

Normal operation, call for heat

In lockout from failed ignition or flame loss

Pressure switch does not close within 30 seconds

Limit switch or rollout switch open

Limit switch is closed before venter is energized

Internal control fault or no power

FLAME

STATUS

YELLOW LED

STEADY ON

SLOW FLASH

FAST FLASH

Flame sensed

Weak flame (current below 1.0 microamps = +/-50%)

Undesired flame (valve open and no call for heat)

OPERATION SEQUENCE

SET THERMOSTAT AT LOWEST SETTING.

1. 

TURN ON MANUAL GAS VALVE.

2. 

TURN ON POWER TO UNIT.

3. 

SET THERMOSTAT AT DESIRED SETTING.

4. 

THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.

5. 

VENTER PRESSURE SWITCH CLOSES, FIRING UNIT.

6. 

BURNER FLAME IS SENSED, AND IN 30 SECONDS THE FAN MOTOR IS ENERGIZED.

7. 

IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION, THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND MUST BE RE-

8. 

SET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT (SEE LIGHTING INSTRUCTIONS).

NOTES

THE FOLLOWING CONTROL IS A FIELD-INSTALLED OPTION: THERMOSTAT.

1. 

DOTTED WIRING INSTALLED BY OTHERS.

2. 

CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL 

3. 

HAVING A TEMPERATURE RATING OF AT LEAST 105°C EXCEPT FOR SENSOR LEAD WIRE AND LIMIT WIRING WHICH MUST BE 150°C.

USE 18 GAUGE WIRE FOR ALL LOW VOLTAGE WIRING ON THE UNIT OR FOLLOW CHART ABOVE.

4. 

LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.

5. 

GROUND WIRE IS USED ONLY ON MODEL 64 UNITS.

6. 

Legend

FAN OFF DELAY

TIME

SWITCH

1

2

90

OFF

ON

120

OFF

OFF

160

ON

OFF

180

ON

ON

FIELD CONTROL WIRING

TOTAL WIRE 

LENGTH

DISTANCE 

FROM UNIT 

TO CONTROL

MIN. RECOMMENDED

WIRE GAUGE

150’
250’
350’

75’

125’
175’

#18 GAUGE WIRE
#16 GAUGE WIRE
#14 GAUGE WIRE

TEST

Y

FLAME 

LED

G

OK

 LED

5

Summary of Contents for 14208303/HS064

Page 1: ...539 Dunksferry Road Bensalem PA 19020 215 244 1400 1 800 523 7138 Fax 215 244 9579 14299573 03 10 14299575 10 29 2014 National Comfort Products 539 Dunksferry Road Bensalem PA 19020 215 244 1400 1 800...

Page 2: ...FOR MAXIMUM PERFORMANCE IT IS IMPERATIVE THAT THE COOLING CHASSIS AIR DIVIDER BE SEALED TO THE CABINET AIR SEAL ANY LEAKAGE WILL ALLOW OUTSIDE UNCONDITIONED AIR TO INFILTRATE AND MIX WITH THE CONDITIO...

Page 3: ...em Do not modify alter or connect to the vent system in the unit The gas furnace comes completely assembled wired mounted and factory tested inside the Comfort Pack cabinet The furnace includes an int...

Page 4: ...y air duct should be equipped with a removable inspection panel to allow for future inspections of the heat exchanger The Comfort Pack unit contains a 16 x 25 x 1 air filter 12 located on the cooling...

Page 5: ...Integrated Control Board w Cooling Relay High Temperature Limit Thermostat Pressure Switch High Altitude Pressure Switch Combination Gas Valve Venter Tube Assembly Venter Wheel Motor Assembly Heat Ex...

Page 6: ...nd Mtr 230V COIL Fan Herm Compressor C S R Dual Capacitor FLAME SENSOR Roll Out Press Sw To Thermostat Inducer Mtr Contactor RD BK Blue Blue Blue Yellow WT WT BK Y G Red Red White Yellow White Black B...

Page 7: ...ond Mtr 230V COIL Fan Herm Compressor C S R Dual Capacitor FLAME SENSOR Roll Out Press Sw To Thermostat Inducer Mtr Contactor RD BK Blue Blue Blue Blue WT WT BK Y G Red Red White Yellow White Black Bl...

Page 8: ...IZED 7 IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND MUST BE RE 8 SET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT SEE LIGHTING INST...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...COMFORT PACK R 410A Gas Furnace Instructions Rev 14299575 10 29 2014...

Reviews: