www.nassarelectronics.com

5

PM-23 PUMP MONITOR MANUAL

The  display shows the time left to restart the motor. If 
it’s  required  to  restart  without  waiting,  press  the 
“Reset” button to start the motor immediately.

MANUAL RESET

If the PM-23 is set to manual reset it will not restart the 
motor until the RESET button is pressed and the fault 
condition is no longer present. 

FAILURE MEMORY

Failures  are  stored  in  the  internal  memory.  When  a 
failure is detected a letter “F” will appear in the first line 
on  the  right  upper  side  of  the  display  indicating  a 
failure has occured.

  MANUAL RESET 

PRESS RESET

  LAST FAILURE

RAPID CYCLING

  234 V  34  Amp.   

F

Power  6,745 W

To check what failure occured, press the LAST FAILURE 
button. The last failure will be shown for  3 s and then it 
will be erased automatically.

UNDERLOAD PROTECTION

The PM-23  protects the motor when a loss of suction is 
detected.  When  this  happens,  the  motor  uses  less 
power and the PM-23  shuts down the motor after a 5 s  
trip delay.

The  underload  setup  is  set  at  65  %  of  the  power 
consumption during automatic calibration, but it can 
also be  adjusted manually.
In the unusual event that the system has a wide power 
variation and it’s consumption goes below 65%  there 
will be a false  triggering of the underload protection. 
In this case underload should be adjusted manually to 
a lower value in the setup menu . 

The  overload  trip  point  is  set  to  125%  of  the  power 
consumption during automatic calibration, but it can 
also be  adjusted manually.

UNDER VOLTAGE PROTECTION

The  PM-23  protects  the  motor  if  the  voltage  drops 
from normal conditions. It shuts down the motor after 
a 5 s  trip delay.
The under voltage protection is user-adjustable. The 
default value for this setup in the PM-23 model is 200V. 

To reset from this fault, the voltage has to increase 2% 
above the under voltage value.

OVER VOLTAGE PROTECTION

The  PM-22  protects  the  motor  if  the  voltage  is  over 
from normal conditions. It shuts down the motor after 
a 5 s   trip delay. The over voltage protection is user-
adjustable.

To reset from this fault, the voltage has to decrease 2% 
above the over voltage value.

RAPID CYCLING PROTECTION

Pumps heat up if they are started very frequently. Such 
heating could damage the pump even if an overload is 
not present.

When the PM-23 detects that the pump starts more 
than 4 times per minute, it will shutdown the pump to 
prevent any damage.

100 

125 

150 

175

200

225

250

275

5

10

15

20

25

OVERLOAD %

TRIP

 DELA

Y

 Sec.

OVER LOAD TRIP DELAY 

OVERLOAD PROTECTION

The  PM-23  protects  the  motor  when  an  overload  is 
detected,  when  this  happens  the  motor  uses  more 
power and the PM-23 shuts down the motor after a trip 
delay as shown in the graphic below. 