3
PM-23 PUMP MONITOR MANUAL
UL=8125 OL=15525
CAL. P=12500 W
Setup
Reset
Last
Failure
CALIBRATION
AUTO CALIBRATION
WAIT 5 SEC.
SET: RESET DELAY
60 Min.
SET RESET:
MANUAL
Automatic calibration
Before the PM-23 unit is ready to be used it MUST BE
CALIBRATED. Calibration may be performed as many
times as desired.
Important Note: Please make sure the PM-23 is
calibrated during normal pumping conditions.
While the pump is operating press and hold both
arrow buttons until LCD displays the calibration.
The PM-23 measures the power and sets the
calibration for underload (UL) at 65% of the power
consumption and at 125% for overload (OL). These are
the recommended values, but they can be manually
adjusted later if desired.
The calibration is permanently stored, it does not
need to be recalibrated if power is lost.
Verify that the pump is running normally (i.e. the
system is pumping water and the motor current is
normal). Try to achieve the maximum water flow rate.
Calibration on a fully recovered well is recommended.
The calibration may be repeated to assure that setup
was done when the pump was running under normal
conditions.
Setup
Press the SETUP button to select between manual or
automatic reset.
Press the downwards arrow button to choose
MANUAL reset or the upwards arrow button to choose
AUTOMATIC reset.
RESET DELAY
Press the SETUP button again. If the AUTOMATIC
option is selected the reset delay setup will be shown.
Press the up or down arrow buttons to adjust the
desired reset delay from 1 to 120 minutes.
Dimensions
DANGER!
Potentially hazardous voltages are present. Electrical
shock can cause death or serious injury.
Installation should be done by qualified personnel
following all National, State & Local Codes.
BE SURE TO REMOVE ALL POWER SUPPLYING THIS
EQUIPMENT BEFORE CONNECTING OR DISCONNECTING
THE WIRING.
READ THE INSTRUCTIONS BEFORE INSTALLING OR
OPERATING THIS DEVICE.
KEEP THIS MANUAL FOR FUTURE REFERENCE.