Nassar PM-23 User Manual Download Page 4

www.nassarelectronics.com

4

PM-23 PUMP MONITOR MANUAL

SET:UNDER LOAD

 UL=12,312 W

UNDERLOAD

Proceed  by  pressing  again  the  SETUP  button,  the 
underload  trip  value  will  be  displayed.  This  setup 
allows  to  modify  the  underload  protection  if  the 
a u t o m a t i c   c a l i b r a t i o n   a d j u s t m e n t   w a s   n o t  
appropriate. The  PM-23  will  disconnect  the  pump  if 
the power is below the selected value.

Use the arrow buttons to set up the desired value in 
10W increments. If the button is kept pressed it will 
move by 100W  increments.

OVERLOAD

When pressing the SETUP button the overload setup is 
displayed.  This  setup  allows  to  modify  the  overload 
protection  if  the  automatic  calibration  adjustment 
was not   appropriate. The PM-23 will disconnect the 
pump if the power is above the selected value.

SET:OVER LOAD

 OL=28,340 W

Use the arrow buttons to set up the desired value in 
10W increments. If the button is kept pressed it will 
move by 100W  increments. The overload value should 
not be less than the underload value. If this happens 
an error will be displayed until the overload setting is 
increased.

UNDER VOLTAGE

 Press the SETUP button and the under voltage setup 
will be displayed , if the voltage is under this value the 
pump will shut down.

SET: UNDER

 VOLTAGE= 200 V

SET:OVER

 VOLTAGE= 245 V

Use the arrow buttons to adjust the desired voltage.
Press SETUP again to exit.

Operation

NORMAL CONDITIONS

The Pump LED is ON when   the pump start, and the 
Failure  LED  is  OFF,  the  display  shows  the  voltage, 
current and power consumption.

FAULTS:

If a failure occurs the 

Failure

 LED turns ON and the LCD 

diplays the fault during trip delay. After the trip delay 
the pump will shut down.

  234 V      34  Amp.

Power  6,762 W

  FAILURE

UNDER VOLTAGE

Fault Examples

  POWER  6,056 W

UNDER LOAD

  POWER  14,856 W

OVER LOAD

  FAILURE

RAPID CYCLING

If  the  pump  presents  an  overload  or  underload 
condition, the power consumption will be displayed 
on the screen. This is useful when the system presents 
considerable  load  variation  and  the  automatic 
calibration values need to be adjusted.
 

AUTOMATIC RESET

After  a  failure  has  occured  (except  under  /over 
voltage), the PM-23  will start to count down the time 
set  on  the  restart  delay  (if  the  automatic  reset  is 
enabled).  The  pump  will  restart  when  the  timer 

  RESET DELAY

6  MIN. LEFT

OVERVOLTAGE

Finally, press the SETUP button and the over voltage 
setup will be displayed , if the voltage is over this value 
the pump will shut down.

Reviews: