Operation manual V 3.2 for AcmeG series
- 22 -
If the floating voltage is not set correctly i.e. too low or not amend according to
the temperature, the battery system will have an insufficient charge state for a
long period of time. When the electricity is cut, the battery may not be able to
work because the active material is saltilized and the capacity is decreased.
2.2
Over Charge
Please ensure the rectifier transfers floating charge to equalization charge. If the
rectifier is not able to transfer charge modes, the battery system will always be in
an equalization charge state which may cause battery water loss, decrease in
service life, overheating and deformation.
2.3
Extreme Temperature
Maintain the correct temperature to ensure the performance of the battery.
Extremities in temperature will be detrimental to the battery life and performance.
2.4
Low End Voltage
The end voltage is an important parameter for battery. The normal end voltage is
10.5V and in some cases 9.6V. The battery will stop discharging when it reaches a
certain voltage. If the end voltage is too low, it will be difficult to recharge the
battery and decrease the charging efficiency, thus affecting the battery life.
2.5
Charging Battery Immediately after Discharge
If the battery is left uncharged for a long period of time i.e. > 2 hours after
discharging, it will affect the capacity and battery life. This is due to large size
PbSO
4
being created in the negative and will be difficult to transfer to active Pb.
3. After-sales Service / Customer Service Hotline
NARADA POWER SOURCE CO.,LTD.
Building A, No.822 Wen'er West Road, Hangzhou, Zhejiang, China
Tel: +86-571-56975980 Fax: +86-571-56975955
Website: www.naradapower.com E -mail: [email protected]
NARADA ASIA PACIFIC PTE. LTD.
Block 9 Khaki Bukit Road 1 #02-10 Eunos Technolink, Singapore 415938
Email: [email protected] Tel: +65-6848 1191 Fax: +65-6749 3498
Website: www.narada-ap.com
NARADA EUROPE (UK) LIMITED
Spectrum House, Dunstable Road, Redbourn, St. Albans, Herts Al3 7PR
Tel: +44 (0)845 612 2031
E-mail: [email protected]
Ac
meG
O
peration
Manual
–
V
3
.2
–
EN
(V
er
.3
.2
S
ep
.
20
15
)
–
Su
bje
ct
to
r
ev
ision
wit
hout
prior
no
tic
e
E.
&O.
E.