background image

5

W415-0583 / D / 07.24.07

24"

16"

8"

Do not use abrasive cleaners to clean glass. Buff lightly with 
a clean dry cloth. The glass is 3/16” ceramic glass available 
from your Napoleon® / Wolf Steel Ltd. dealer. DO NOT SUB-
STITUTE MATERIALS. Clean the glass after the fi rst 10 hours 
of operation with a recommended gas fi replace glass cleaner. 
Thereafter clean as required. DO NOT CLEAN GLASS WHEN 
HOT! If the glass is not kept clean permanent discolouration 
and / or blemishes may result.  Decorative panel may disco-
lour after time.

This fi replace may 

be installed in an aftermarket permanently 

located, manufactured (mobile) home, where not prohibited 
by local codes.
This fi replace is only for use with the type of gas indicated 
on the rating plate. This fi replace is not convertible for use 
with other gases, unless a certifi ed kit is used.

No external electricity (110 volts or 24 volts) is required for 
the gas system operation.  

Expansion / contraction noises during heating up and cooling 
down cycles are normal and are to be expected. Change in 
fl ame appearance from “HI” to “LO” is more evident in natural 
gas than in propane.
This fi replace is approved for bathroom, bedroom and bed-
sitting room installations and is suitable for mobile home 
installation. The natural gas model can only be installed  in a 
mobile home that is permanently positioned on it’s site

FIGURES 2A-C

Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp 
or American Metal Amerivent venting components.

Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp and 
American Metal Amerivent venting systems must not be 
combined.

Follow the installation procedure provided with the venting 
components. 

For vent systems that provide seals on the inner exhaust fl ue, 
only the outer air intake joints must be sealed using a red high 
temperature silicone (RTV). This same sealant maybe used 
on both the inner exhaust and outer intake vent pipe joints 
of all other approved vent systems except for the exhaust 
vent pipe connection to the fi replace fl ue collar which must 
be sealed using the black high temperature sealant Mill Pac.
A starter adaptor must be used and may be purchased from 
the corresponding supplier: 

Supplier 4 

7

Duravent W175-0053
Amerivent 4DSC-N2
Direct Temp 

4DT-AAN

When using Napoleon® venting components, use only 
approved Wolf Steel Ltd. rigid / fl exible vent components with 
the following termination kits: WALL TERMINAL KIT 

GD222R

or 1/12 TO 7/12 PITCH ROOF TERMINAL KIT

 GD110

8/12 TO 12/12 ROOF TERMINAL KIT

 GD111

, FLAT ROOF 

TERMINAL KIT

 GD112 

or PERISCOPE KIT

 GD201 

(for wall 

penetration below grade). With fl exible venting,

 

in conjunction 

with the various terminations, use either the 5 foot vent kit 

GD220

 or the 10 foot vent kit 

GD330

. These vent kits allow 

for either horizontal or vertical venting of the fi replace. 

FIGURE 3

CARE OF GLASS

Horizontal runs may have a 0 inch rise per foot in all cases 
using SIMPSON DURA-VENT or NAPOLEON® RIGID OR 
FLEXIBLE venting components when venting as illustrated 
in Figures 2a, 2b, and 2c.

VENTING

VENTING LENGTHS & AIR TERMINAL 

LOCATIONS

When venting, the horizontal run must be kept to a minimum 
of 16 inches or a maximum of  20 feet. If a 20 foot horizontal 
run is required, the fi replace must have a minimum vertical rise 
immediately off the fi replace of 57 inches.  (Fig. 2a-c)  When 
terminating vertically, the vertical rise is a minimum 34 inches 
and a maximum 40 feet above the fi replace. (Fig. 3)

For optimum performance, it is recommended that all 
horizontal runs have a minimum ¼ inch rise per foot.

Do not allow the inside liner to bunch up on horizontal or 
vertical runs and elbows. Keep it pulled tight. A 1¼” air gap 
between the inner and outer liner all around is required for 
safe operation.
Use a firestop when penetrating interior walls, floor or 
ceiling.  

For safe and proper operation of the fi replace follow the 
venting instruction exactly.

Deviation from the minimum vertical vent length can create 
diffi culty in burner start-up and/or carboning.
Provide a means for visually checking the vent connection to 
the fi replace after the fi replace is installed.
Vent lengths that pass through unheated spaces (attics, 
garages, crawl spaces) should be insulated with the insulation 
wrapped in a protective sleeve to minimize condensation.

The air terminal must remain unobstructed at all times. 
Examine the air terminal at least once a year to verify that it 
is unobstructed and undamaged.

and fueled with natural gas.

For optimum fl ame appearance and fi replace performance, 
keep the vent length and number of elbows to a minimum.

The inner stainless steel looking fi rebox back will discolour 
with heat, turning a light brown, straw like colour that is to be 
considered normal.

The

 

maximum allowable vertical vent length is 40 feet 

using fl exible venting. 

The maximum number of allowable 

4” vent connections is 

three horizontally

 or 

vertically

 

(excluding the fi replace and the air terminal connections).

Note: If for any reason the vent air intake system is 
disassembled; reinstall per the instructions provided for 
the initial installation.

Summary of Contents for Tureen GD82NT-T

Page 1: ...e or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and...

Page 2: ...d period of time Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces These screens and guards must be fastened to the floor Any safety screen or guard removed for servicing must be replaced prior to operating the fireplace It is imperative that the control compartments burners and circulating blower and its passageway in the firepla...

Page 3: ...anty This limited warranty further does not cover any scratches dents corrosion or discolouring caused by excessive heat abrasive and chemical cleaners nor chipping on porcelain enamel parts mechanical breakage of PHAZER logs and embers nor any venting components used in the installation of the fireplace NAPOLEON warrants its stainless steel burners against defects in workmanship and material for l...

Page 4: ...ger than 36 inches The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product A carbon monoxide detector is required in all rooms containing gas fired appliances WARNING This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of Massachusetts In absence of local codes install to ...

Page 5: ... ROOF TERMINAL KIT GD110 8 12 TO 12 12 ROOF TERMINAL KIT GD111 FLAT ROOF TERMINAL KIT GD112 or PERISCOPE KIT GD201 for wall penetration below grade With flexible venting in conjunction with the various terminations use either the 5 foot vent kit GD220 or the 10 foot vent kit GD330 These vent kits allow for either horizontal or vertical venting of the fireplace FIGURE 3 CARE OF GLASS Horizontal runs ...

Page 6: ...ent configuration is acceptable FIGURE 5 90 H1 V2 H2 V1 HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT and VT for the following symbols used in the venting calculations and examples are greater than equal to or greater than less than equal to or less than HT total of both horizontal vent lengths HR and offsets HO in feet HR combined h...

Page 7: ...rmulas apply Formula 1 HT 4 2 VT Formula 2 HT VT 24 75 feet Example 2 ceptable Example 3 V1 4 ft V2 1 5 ft VT V1 V2 4 1 5 5 5 ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90 8 1 ft HT HR HO 5 5 8 1 13 6 ft HT VT 13 6 5 5 19 1 ft Formula 1 HT 4 2 VT 4 2 VT 4 2 x 5 5 23 1 ft 13 6 23 1 Formula 2 HT VT 24 75 feet 19 1 24 75 FIGURE 6 FIGURE 7 REQUI...

Page 8: ...ne the required vertical rise VT for the required horizontal run HT FIGURE 11 Example 7 V1 2 ft V2 1 ft V3 1 5 ft VT V1 V2 V3 2 1 1 5 4 5 ft H1 6 ft H2 2 ft HR H1 H2 6 2 8 ft HO 03 four 90 elbows 90 03 90 90 90 90 90 8 1 ft HT HR HO 8 8 1 16 1 ft HT VT 16 1 4 5 20 6 ft Formula 1 HT 3VT 3VT 3 x 4 5 13 5 ft 16 1 13 5 Since this formula is not met this vent configuration is unacceptable Formula 2 HT V...

Page 9: ...9 W415 0583 D 07 24 07 FIGURE 12 ...

Page 10: ...he pipe INSTALLATION WALL AND CEILING PROTECTION VERTICAL INSTALLATION VENT PIPE SHIELD VENT PIPE COLLAR FIGURE 15 FIGURE 14 11 11 FIGURE 13 For optimum performance it is recommended that all horizontal runs have a minimum inch rise per foot using flexible venting For safe and proper operation of the fireplace follow the venting instructions exactly HORIZONTAL TERMINATION A clearance to combustibles...

Page 11: ...cessed into a wall or siding 1 Cut or frame a hole in an exterior wall with a minimum round or square opening of 111 2 W x 111 2 H if within 24 of the fireplace collars If beyond 24 then a 91 2 W x 91 2 H opening is acceptable Secure the firestop spacer over the opening to the interior wall Secure the terminal to the terminal extension plate if required see figure 18 The cover plate of the GD 222R te...

Page 12: ...ce and any 1 overlaps between venting components 2 Apply high temperature sealant W573 0007 not pro vided to the outer edge of the 4 inner collar of the fireplace Attach the first vent component and secure using 3 self tapping screws Repeat using 7 piping 3 Holding the air terminal with the air deflectors to the top and the lettering in an upright readable position insert the terminal into both vent ...

Page 13: ...pen end of the shield and tighten This will prevent any materials such as insulation from filling up the 1 air space around the pipe GAS INSTALLATION Vertical terminations may display a very active flame If this appearance is not desirable the vent exit must be restricted using restrictor plate W500 0205 This reduces the velocity of the exhaust gases slowing down the flame pattern and creating a more...

Page 14: ...r barrier coming in contact with the fireplace body it is recommended that the walls of the fireplace enclosure be finished ie drywall sheetrock as you would finish any other outside wall of a home This will ensure that clearance to combustibles is maintained within the cavity For convenience the stand offs have been shipped flat Be fore framing ensure the stand offs are opened and screwed in place It ...

Page 15: ...g the unit It is necessary to hard wire this fireplace Permanently framing the fireplace with an enclosure requires the fireplace junction box to be hardwired This fireplace must be electrically connected and grounded in accordance with local codes In the absence of local codes use the current CSA C22 1 CANADIAN ELECTRICAL CODE in Canada or the ANSI NFPA 70 1996 NATIONAL ELECTRICAL CODE in the United ...

Page 16: ... forward slightly and lift from the 2 shoulder screws near the bottom front Note Fronts are heavy so when the second turn button is turned the front will want to fall forward OPTIONAL FRONT REMOVAL FIGURE 34 Lift the panel from the slots This will allow access and removal of the remote receiver and spark module If valve replacement is necessary follow step 1 above then proceed with the following S...

Page 17: ...nd corner of the panel and pull forward gently Slide your hand down along the edge of the panel allowing it to come out of its place in the firebox and to rest on the edge of the firebox opening Repeat on the left side Guide the panel out of the firebox by rotating it carefully from the left to the right being sure to stay clear of the burner Fig 40 Note Be careful when bending the panel not to bend ...

Page 18: ...T 1 Remove the optional front In structions on Pg 17 2 Tilt the control panel forward al lowing access to the electode box which is screwed to the base of the firebox Fig 43 BOWL BURNER CURVED DECORATIVE PANEL BURNER BOTTOM BURNER BASE SEE THRU W I N D O W ELECTRODE BOX AA Battery Required CONTROL PANEL CONTROL PANEL FIGURE 43 Your comes equipped with a heat circulating blower The blower is pre wir...

Page 19: ...be running and the gas valve turned to the ON position Ensure that the receiver has power and the backup switch is in the auto position OPERATION MAINTENANCE FIREPLACE OPERATION FIGURE 46 TIME OUT If the appliance is turned on and the Receiver does not re ceive any command for 24 hours it automatically turns the appliance 1 Install the batteries AAA into the remote control transmitter The HOUSE ic...

Page 20: ...ppliance on or off to maintain the selected temperature FIGURE 47 FIGURE 48 HAND HELD REMOTE OPERATIONS TIME OUT If the appliance is turned on and the Receiver does not receive any command for 24 hours it automatically turns the appliance and the Remote Control off To operate this fireplace using the remote the pilot must be running and the gas valve turned to the ON position Ensure that the receiv...

Page 21: ...nction is active when the lock icon is lit To activate this function press the ON OFF button and within one second the UP key To reactivate the remote control buttons follow the same sequence press ON OFF key and within one second press the UP button POWER FAILURE During main power loss it is not possible to turn on the appli ance with the Remote Control It is possible to turn the appli ance on ma...

Page 22: ...the address of the Transmitter press the UP key to increase and DOWN to decrease it A beep from the Receiver will confirm the same address as the Transmitter Press LEFT key to exit this function Note The address of the Receiver is acquired only at its power on Changing the address while the Receiver is powered will not have any effect To change the address of the Receiver disconnect the power cable...

Page 23: ...23 W415 0583 D 07 24 07 DIP SWITCH NUMBER 0 ON 1 OFF FIGURE 57 ...

Page 24: ...insta llation instructions When lighting and re lighting the gas knob cannot be turned from pilot to off unless the knob it depressed slightly 1 STOP read the safety information on the operating label 2 Turn off all electric power to the fireplace 3 Turn the gas knob clockwise to off 4 Wait 5 minutes to clear out any gas If you smell gas including near the floor STOP Follow B on the op erating label...

Page 25: ...ee that the pilot flame is large enough to engulf the thermocouple and thermopile and reaches toward the burner with the third jet 5 Replace the cleaned bowl and rockset 6 Check to see that the main burner ignites completely on all openings when the gas knob for the burner is turned on A 5 to 10 second total light up period is satisfactory If ignition takes longer consult your Napoleon dealer distr...

Page 26: ...5 32 allen key to unscrew the injector Replace the pilot injector with the one supplied Replace the pilot hood onto the assembly ensuring key position for proper alignment 8 Before replacing the burner assembly adjust the burner shutter opening to 1 2 for propane and 1 16 for natural gas 9 Replace and re secure the burner assembly ensuring that the venturi fits over the burner orifice 10 To convert ...

Page 27: ...dered through your Napoleon dealer or distributor When ordering replacement parts always give the following information 1 MODEL SERIAL NUMBER OF FIREPLACE 2 INSTALLATION DATE OF FIREPLACE 3 PART NUMBER 4 DESCRIPTION OF PART 5 FINISH FOR WARRANTY REPLACEMENT PARTS A PHOTOCOPY OF THE ORIGINAL INVOICE WILL BE REQUIRED TO HONOUR THE CLAIM REPLACEMENTS IDENTIFIES ITEMS WHICH ARE NOT ILLUSTRATED FOR FUR...

Page 28: ...28 W415 0583 D 07 24 07 35 34 16 48 46 45 22 19 28 18 20 AUX ON 0 00 00 ON OFF FEATURE SELECT 21 25 23 24 26 1 2 17 4 11 9 13 12 10 54 40 41 42 43 55 39 3 5 ...

Page 29: ...to improve the flame pattern around the thermocouple Pilot flame is not engulfing the thermocouple Thermocouple shorting faulty loosen and tighten thermocouple clean thermocouple and valve connection replace thermocouple replace valve Faulty valve replace Main burner flame is a blue lazy transparent flame Blockage in vent remove blockage In really cold conditions ice buildup may occur on the terminal a...

Page 30: ...k replace the battery check to make sure the electrode is connected to the ignitor box No spark at pilot burner fill the tank Out of propane gas Spark gap is incorrect spark gap should be 0 150 to 0 175 5 32 to 11 64 approx from the electrode tip and the pilot burner To ensure proper electrode location tighten securing nut finger tight plus 1 4 turn No gas at the pilot burner check that the manual v...

Page 31: ...31 W415 0583 D 07 24 07 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS ...

Page 32: ...32 W415 0583 D 07 24 07 NOTES ...

Reviews: