CYLINDER SIZE
OPENING A AREA OPENING B AREA
20 lb (9.1 kg)
20 in
2
(130 cm
2
)
10 in
2
(65 cm
2
)
30 lb (13.6 kg)
30 in
2
(195 cm
2
)
15 in
2
(100 cm
2
)
The design of the enclosure shall be such that (1) the LP gas supply cylinder(s) can be connected,
disconnected and the connections inspected and tested outside the cylinder enclosure; and (2) those
connections which could be disturbed when installing the cylinder(s) in the enclosure can be leak tested
inside the enclosure.
The enclosure for the LP-gas cylinder shall isolate the cylinder from the burner compartment to provide:
a. Shielding from radiation;
b. A flame barrier; and
c. Protection from foreign material.
Be certain to mount or set the LP gas cylinder on a flat surface and restrain it using a cylinder retaining
bracket to prevent it from tipping.
OPENING
B
NON LOCKING DOOR
PARTITION TO ISOLATE CYLINDER
FROM PATIO FLAME
34” (864 mm)
RECOMMENDED
2” (51 mm)
MINIMUM
OPENING
A
5” (127 mm)
MAXIMUM
5” (127 mm)
MAXIMUM
1” (25.4 mm)
MAXIMUM