background image

6

WS-415-63 / 11.24.98

Use only Napoleon or Simpson Dura-Vent Model DV-GS venting components. Minimum and maximum vent lengths, for
both horizontal and vertical installations, and air terminal locations for either system are set out in this manual and must
be adhered to. For Simpson Dura-Vent, follow the installation procedure provided with the venting components.
When using Napoleon venting components, use only the following vent kits: WALL TERMINAL KIT 

GD175 

(7-1/2' of

venting included), or 1/12 TO 7/12 PITCH ROOF TERMINAL KIT

 GD110

, 8/12 TO 12/12 ROOF TERMINAL KIT

 GD111

,

FLAT ROOF TERMINAL KIT

 GD112 

or STOVE PERISCOPE KIT

 GD180 

(for wall penetration below grade)

 

in conjunction

with the appropriate venting components.
These vent kits allow for either horizontal or vertical venting of the stove. 

FIGURES 2, 3, & 4

. The maximum number of 4"

flexible connections is two horizontally or three vertically (excluding the stove and the air terminal connections).

Use an adjustable pipe as the final length of rigid piping to the stove for ease of installation.

For optimum flame appearance and stove performance, keep the vent length and number of elbows to a minimum. On
extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after lighting. The air terminal must
remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and
undamaged.

THE MAXIMUM HORIZONT

THE MAXIMUM HORIZONT

THE MAXIMUM HORIZONT

THE MAXIMUM HORIZONT

THE MAXIMUM HORIZONTAL RUN IS 34 INCHES WITH A 90

AL RUN IS 34 INCHES WITH A 90

AL RUN IS 34 INCHES WITH A 90

AL RUN IS 34 INCHES WITH A 90

AL RUN IS 34 INCHES WITH A 90

o

o

o

o

o

 ELBOW LOCA

 ELBOW LOCA

 ELBOW LOCA

 ELBOW LOCA

 ELBOW LOCATED

TED

TED

TED

TED

29" ABOVE THE STOVE.

29" ABOVE THE STOVE.

29" ABOVE THE STOVE.

29" ABOVE THE STOVE.

29" ABOVE THE STOVE.

THE MAXIMUM HORIZONT

THE MAXIMUM HORIZONT

THE MAXIMUM HORIZONT

THE MAXIMUM HORIZONT

THE MAXIMUM HORIZONTAL RUN WITH A 57 INCH VERTICAL RISE IMMEDI-

AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI-

AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI-

AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI-

AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI-

A

A

A

A

ATEL

TEL

TEL

TEL

TELY ABOVE THE STOVE IS 20 FEET

Y ABOVE THE STOVE IS 20 FEET

Y ABOVE THE STOVE IS 20 FEET

Y ABOVE THE STOVE IS 20 FEET

Y ABOVE THE STOVE IS 20 FEET.....

IF VERTICAL RISES GREA

IF VERTICAL RISES GREA

IF VERTICAL RISES GREA

IF VERTICAL RISES GREA

IF VERTICAL RISES GREATER THAN 57 INCHES ARE NECESSARY

TER THAN 57 INCHES ARE NECESSARY

TER THAN 57 INCHES ARE NECESSARY

TER THAN 57 INCHES ARE NECESSARY

TER THAN 57 INCHES ARE NECESSARY, THE INCREASED

, THE INCREASED

, THE INCREASED

, THE INCREASED

, THE INCREASED

RISE MUST BE DEDUCTED FROM THE HORIZONT

RISE MUST BE DEDUCTED FROM THE HORIZONT

RISE MUST BE DEDUCTED FROM THE HORIZONT

RISE MUST BE DEDUCTED FROM THE HORIZONT

RISE MUST BE DEDUCTED FROM THE HORIZONTAL RUN.

AL RUN.

AL RUN.

AL RUN.

AL RUN.

When terminating vertically, the minimum vertical rise is 34 inches above the stove and the
maximum vertical rise is 15 feet. 

FIGURE 4.

 

Deviation from the minimum vertical vent length

can create difficulty in burner start-up and/or carboning.

When a horizontal run is introduced, even though the terminal may be vertical, the installation
must be considered 

HORIZONTAL

.

Use the chart on this page to calculate horizontal runs for vertical rises between 29 and 57 inches. 

FIGURE 5.

When calculating maximum run lengths, include 10 feet for each 90° elbow or 5 feet for each 45° elbow. (DO NOT
INCLUDE THE FIRST ELBOW DIRECTLY OFF THE UNIT.)

HORIZONTAL RUN NOT TO
EXCEED VERTICAL RISE

FIGURE 2

FIGURES 3

REQUIRED VER

REQUIRED VER

REQUIRED VER

REQUIRED VER

REQUIRED VERTICAL RISE

TICAL RISE

TICAL RISE

TICAL RISE

TICAL RISE

FROM FIREPLACE TO FIRST

FROM FIREPLACE TO FIRST

FROM FIREPLACE TO FIRST

FROM FIREPLACE TO FIRST

FROM FIREPLACE TO FIRST

ELBOW IN 

ELBOW IN 

ELBOW IN 

ELBOW IN 

ELBOW IN INCHES

INCHES

INCHES

INCHES

INCHES

CALCULA

CALCULA

CALCULA

CALCULA

CALCULATED HORIZONT

TED HORIZONT

TED HORIZONT

TED HORIZONT

TED HORIZONTAL VENT RUN IN 

AL VENT RUN IN 

AL VENT RUN IN 

AL VENT RUN IN 

AL VENT RUN IN FEET

FEET

FEET

FEET

FEET

FIGURE 4

FIGURE 5

Summary of Contents for GDS 3700-P

Page 1: ...722 6031 Email ask napoleon on ca Web www napoleon on ca Wolf Steel Ltd RR 1 9 Napoleon Rd Barrie ON Canada L4M 4Y8 705 721 1212 R 2000 Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department W W W W WARNING ARNING ARNING ARNING ARNING If the information in these instructions is not followed e...

Page 2: ...rtical Venting Installation Stove Vent Connection 10 10 10 10 10 GAS INST GAS INST GAS INST GAS INST GAS INSTALLA ALLA ALLA ALLA ALLATION TION TION TION TION 11 11 11 11 11 FINISHING FINISHING FINISHING FINISHING FINISHING Log Placement Charcoal Embers PG PG PG PG PG 12 12 12 12 12 OPERA OPERA OPERA OPERA OPERATION MAINTENANCE TION MAINTENANCE TION MAINTENANCE TION MAINTENANCE TION MAINTENANCE Ope...

Page 3: ...pproval of an authorized company official Labour costs work however requires the prior approval of an authorized company official Labour costs to the account of to the account of to the account of to the account of to the account of NAPOLEON NAPOLEON NAPOLEON NAPOLEON NAPOLEON are based on a predetermined rate schedule and any repair are based on a predetermined rate schedule and any repair are ba...

Page 4: ... or the ANSI NFPA 70 1990 NATIONAL ELECTRICAL CODE in the United States The blower power cord must be connected into a properly grounded receptacle The grounding prong must not be removed from the cord plug Provide adequate ventilation and combustion air Provide adequate accessibility clearance for servicing and operating the stove Never obstruct the front opening of the stove GENERAL INFORMA GENE...

Page 5: ...nts burners and circulating blower and its passageway in the stove and venting system are kept clean The stove and its venting system should be inspected before use and at least annually by a qualified service person More frequent cleaning may be required due to exces sive lint from carpeting bedding material etc The stove area must be kept clear and free from combustible materials gasoline and ot...

Page 6: ...SE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI A A A A ATEL TEL TEL TEL TELY ABOVE THE STOVE IS 20 FEET Y ABOVE THE STOVE IS 20 FEET Y ABOVE THE STOVE IS 20 FEET Y ABOVE THE STOVE IS 20 FEET Y ABOVE THE STOVE IS 20 FEET IF VERTICAL RISES GREA IF VERTICAL RISES GREA...

Page 7: ...LA ALLA ALLA ALLATION EXAMPLE TION EXAMPLE TION EXAMPLE TION EXAMPLE TION EXAMPLE If a first run of 48 inches is required using the First Vent Run chart shows that a 51 inch vertical rise is necessary and a maximum second run of 32 inches is allowable IF NECESSAR IF NECESSAR IF NECESSAR IF NECESSAR IF NECESSARY Y Y Y Y THE FIRST RUN AND THE SECOND RUN MA THE FIRST RUN AND THE SECOND RUN MA THE FIR...

Page 8: ... as illustrated in FIGURE 9 FIGURE9 G Seven feet above public walkways unless fitted with heat shield kit GD301 H One foot below windows that open I One foot from the side of doors and windows that open J One foot from permanently closed windows K One foot above grade L NOT above a regulator meter assembly or within three feet horizontally from the vertical centre line of the assembly M Six feet f...

Page 9: ... 12 3 Slip the first section of 7 diameter stove pipe a minimum of 2 over the outer sleeve of the air terminal Secure to the sleeve using 3 screws Seal the joint and screw heads using high temperature sealant 4 Install the firestop wall plate to the finished interior wall maintain ing a 1 clearance to combustibles Insert the liners through the firestop Holding the air terminal lettering in an upri...

Page 10: ...E INSTALLA ALLA ALLA ALLA ALLA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORATIVE BRASS BAND IS A TIVE BRASS BAND IS A TIVE BRASS BAND IS A TIVE BRASS BAND IS A TIVE BRASS BAND IS AV V V V VAILABLE FOR THIS AILABLE FOR THIS AILABLE FOR THIS AILABLE FOR THIS AILA...

Page 11: ...cated on the rear wall of the combustion chamber The notch situated at the lower left of the back log should be centered evenly above the pilot assembly FIGURE 21 3 While supporting the back log to prevent it from falling forward set the three smaller logs into the pockets and grooves of the front and back logs respectively Log colours may vary During the initial use of the fireplace the colours w...

Page 12: ...s supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department FOR YOUR SAFETY READ BEFORE OPERATING A This fireplace is equipped with a pilot which must be lit by hand while following these instructions exactly B Before operating smell all around the fireplace area for gas and next to the floor because some gas is heavier ...

Page 13: ...d will run for approximately 30 minutes after the stove has been turned off Use of the fan in creases the output of heat 1 Mount the variable speed switch insert the rheostat stem through the 3 8 diameter hole in the pedestal and from the front secure with the pal nut Add the knob 2 Remove the blower housing located at the rear of the stove Attach the bracket holding the heat sensor as shown to th...

Page 14: ...ISCOPE TERMINAL KIT GD180 PERISCOPE TERMINAL KIT GD180 PERISCOPE TERMINAL KIT PART PART PART PART PART DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION PART PART PART PART PART DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION BM6790 90 ELBOW 7 DIAMETER GD201 PERISCOPE BM67ADJ 30 TO 53 ADJUSTABLE PIPE 7 DIAMETER GDS 500 77 FIRESTOP WALL PLATE GDS 020 32 HARDWARE BRTC7 BRASS TR...

Page 15: ...15 WS 415 63 11 24 98 included with GD180 included with GD175 I H L O L F F N T I O O P O ...

Page 16: ...cooled Allow approximately 60 seconds for the thermocouple to cool Pilot flame is not large enough turn up the pilot flame Pilot flame is not engulfing the thermocouple turn up pilot flame replace pilot assembly Thermocouple shorting loosen and tighten thermocouple clean thermocouple and valve connection replace thermocouple replace valve Faultly thermocouple replace Faulty valve replace System is...

Page 17: ...emoved as required refer to Figure 16 to ensure correct location of storm collars Incorrect installation Main burner goes out pilot goes out REFER TO MAIN BURNER GOES OUT PILOT STAYS ON Thermocouple shorting or faulty check joint seals and installation Vent re circulating loosen and tighten thermocouple clean thermocouple and valve connection replace thermocouple replace valve PROBLEM PROBLEM PROB...

Page 18: ...18 WS 415 63 11 24 98 NOTES ...

Reviews: