Napoleon GD40-N Installation And Operation Instructions Manual Download Page 20

20

WS-415-091 / 06.26.00

4. 

Install the rigid black pipe, ½" type-L copper tubing or,

if local codes permit,  a

 3

/

8

" flex connector and shutoff valve

to the gas line and the fireplace gas valve. Seal and tighten
securely. An adapter fitting is required between the gas
valve and the copper tubing or flex connector.

Do not kink flexible connector.

5. 

Check for gas leaks by brushing on a soap and water

solution.

Do not use open flame.

GAS SUPPLY CONNECTION

1.

 Move the fireplace into position and secure to the floor

using #10 hex head screws (not supplied).

2. 

Route a 3/8" N.P.T. black iron gas line, 1/2" type-L

copper tubing or equivalent to the fireplace.

3. 

For ease of accessibility, an optional remote wall switch

or millivolt thermostat may be installed in a convenient
location. Route 2-strand (solid core) millivolt wire through
the electrical hole located at the bottom left side of the unit.

The recommended maximum lead length depends on

wire size:

WIRE SIZE

MAX. LENGTH

14 gauge

100 feet

16  gauge

 60 feet

18  gauge

 40 feet

Do not connect either the wall  switch, thermostat or
gas valve to electricity (110 volts).

Attach the two leads to terminals 1 and 3 located on the

gas valve.

FIGURE 37

P

I

PI

3

1

2

LOT

N

O

L

O

T

H I

LO

FF

O

FIGURE 36

7" MANTLE

3" MANTLE

TOP EXTENTION

TOP OF THE UNIT

FIGURES 38

FINISHING

MANTLE INSTALLATION

Combustible mantle clearance can vary according to the
mantle depth. Use the graph to help evaluate the clear-
ance needed. The three-sided top extension frame may be
removed if framing is faced with a non-combustible mate-
rial.

Summary of Contents for GD40-N

Page 1: ...apoleon Rd Barrie ON Canada L4M 4Y8 705 721 1212 R 2000 WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury...

Page 2: ...thing ignition Supervise young children when they are in the same room as the fireplace Due to high temperatures the fireplace should be located out of traffic and away from furniture and draperies Cl...

Page 3: ...3 WS 415 091 06 26 00 RIGHT OPEN END MODEL LEFT OPEN END MODEL PENINSULA MODEL SEE THRU MODEL...

Page 4: ...ial Labour costs to the however requires the prior approval of an authorized company official Labour costs to the account of account of account of account of account of NAPOLEON NAPOLEON NAPOLEON NAPO...

Page 5: ...as well as having a 1 inch air gap After the insulation sleeve a 2 air gap must be maintained between the re maining vent system and combustibles FIGURE 39 GENERAL INFORMATION FOR YOUR SATISFACTION A...

Page 6: ...r 2 feet must be wrapped in the 1 inch thick insu lation sleeve supplied as well as having a 1 inch air gap Use a firestop when penetrating interior walls floor or ceiling The fireplace must be instal...

Page 7: ...a sidewalk or paved driveway which is located between two sin gle family dwellings and serves both dwellings Local codes or regulations may require different clearances All horizontal runs must have a...

Page 8: ...foot and 18 feet FIGURES 7 VENTING OPTION 4 Use this chart to calculate the vertical rise when using a total of 2 horizontal runs that consist of 8 feet maximum or 2 feet maximum length when the vert...

Page 9: ...installation may be vented hori zontally or vertically In the United States it may only be installed vertically See Vertical Venting or Horizontal Air Terminal Installation for installation The firep...

Page 10: ...EET Clearance above grade veranda porch deck or balcony Clearance to windows or doors that open Clearance to permanently closed windows Vertical clearance to ventilated soffit located above the termin...

Page 11: ...installation A horizontal vent installation requires a minimum height of 42 including the 2 clearance to combustibles FIGURE 12 A FIGURE11 TOP EXTENTION TOP OF THE UNIT FIGURE14 42 38 FIGURE12 COUNTE...

Page 12: ...system Objects placed in front of the fireplace should be kept a minimum of 48 away from the front face FINISHING Refer to page 20 for complete instructions regarding man tle requirements and install...

Page 13: ...k insulation sleeve supplied as well as having a 1 inch air gap FRAMING It is best to frame your fireplace after it is positioned and the vent system is installed Use 2x4 s and frame to local building...

Page 14: ...stible material brick stone or ceramic tile may protrude in these areas It is not necessary to install a hearth extension with this fireplace system Objects placed in front of the fireplace should be...

Page 15: ...ust be wrapped in the 1 inch thick insulation sleeve supplied as well as having a 1 inch air gap FRAMING It is best to frame your fireplace after it is positioned and the vent system is installed Use...

Page 16: ...specific kit required 1 Determine the air terminal location cut and frame 11 inch openings in the ceiling and the roof to provide the minimum 2 inch clearance between the fireplace pipe liner and any...

Page 17: ...de and or secure to the floor using screws inserted through the two diameter holes in the front left and right corners of the base The liners should be flush with the exterior wall The air terminal mo...

Page 18: ...oof caulking 2 inches above the flashing Slide the storm collar around the air terminal and down to the caulking Tighten to ensure that a weather tight seal between the air terminal and the collar is...

Page 19: ...d piping Secure with screws and seal Repeat using a 7 telescopic pipe 9 Run a bead of high temperature sealant around the outside of the 4 elbow Pull the adjustable pipe a mini mum 2 onto the elbow Se...

Page 20: ...optional remote wall switch or millivolt thermostat may be installed in a convenient location Route 2 strand solid core millivolt wire through the electrical hole located at the bottom left side of th...

Page 21: ...rs into pieces and place along the perimeter of the runner burners as well as covering all of the burner area beneath and in front of the hollowed out section of log 1 2 Care should be taken to shred...

Page 22: ...xt Attach magnets to the top and bottom door trim approximately 4 from either end Lift up the top trim and hook over the top of the door The bottom trim is inserted into the bottom door sill Push in t...

Page 23: ...ow the blower to be positioned away from the intended gas supply hole Secure the blower using the lock washers and wing nuts provided Remove the thermodisc from the Z shaped mount ing bracket and re a...

Page 24: ...to clear out any gas If you smell gas including near the floor Stop Follow B in the above safety information on this label If you don t smell gas go the next step 5 Turn gas knob counter clockwise to...

Page 25: ...ely allow 15 to 30 minutes for the final flame colour to be established FIGURE52 P I P I PILOT SCREW L O T N O L O T HI L O F F O FIGURE50 FLAME MUST ENVELOP UPPER 3 8 TO 1 2 OF THERMOCOUPLE THERMOPIL...

Page 26: ...OR HEAT SHIELD GA GD 020 042 PKG OF 5 DOOR SCREWS GA GD 475 161 REAR BRICK PANEL GA GD 225 045 BLACK END DOOR FRAME GA GD 322K BLACK END DOOR c w GLASS WS 300 027 END DOOR GLASS ONLY GD 010 540 END DO...

Page 27: ...N OFF SWITCH GA GD 100 048 LEFT RUNNER BURNER GA GD 100 049 RIGHT RUNNER BURNER WS 100 042 MAIN BURNER WS 680 04 THERMOPILE WS 680 05 THERMOCOUPLE WS 725 26 PROPANE GAS VALVE WS 725 25 NATURAL GAS VAL...

Page 28: ...NDOW KIT SIDE DOOR ONLY WS 660 2 HAND HELD WIRELESS REMOTE SWITCH WS 660 010 REMOTE CONTROL ADVANTAGE WS 660 011 REMOTE CONTROL ADVANTAGE PLUS WS 175 1 4 COUPLER WS 175 13 7 COUPLER KB35 VARIABLE SPEE...

Page 29: ...E READINGS BE SURE TO TURN SCREWS CLOCKWISE FIRMLY TO RESEAL DO NOT OVERTORQUE Leak test with a soap and water solution Unit is over fired or under fired P I A B P I L O T N O L O T HI L O F F O Main...

Page 30: ...re is connected to the push button ignitor check if the push button ignitor needs tightening replace the wire if the wire insulation is broken or frayed replace the electrode if the ceramic insulator...

Page 31: ...WS 415 091 06 26 00 Wolf Steel Fireplace Service History This fireplace must be serviced at least annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Na...

Page 32: ...32 WS 415 091 06 26 00 NOTES...

Reviews: