background image

NOTE : Les modifi cations, autres qu’éditoriales, sont indiquées par une ligne verticale dans la marge.

TABLE DES MATIÈRES

1.0 

VUE D’ENSEMBLE DE L’INSTALLATION 

63

2.0 INTRODUCTION 

64

2.1 DIMENSIONS 

65

2.2 INSTRUCTIONS 

GÉNÉRALES 

66

2.3 INFORMATION 

GÉNÉRALE 

67

2.4 

INFORMATION SUR LA PLAQUE D’HOMOLOGATION 

67

3.0 ÉVACUATION 

68

3.1 

LONGUEURS DES CONDUITS D’ÉVACUATION ET COMPOSANTS 

68

3.2 INSTALLATIONS 

TYPIQUES 

D’ÉVENTS 

69

3.3 

INSTALLATIONS PARTICULIÈRES D’ÉVENTS 

71

3.3.1 ENSEMBLE 

PÉRISCOPIQUE 

71

3.3.2 

INSTALLATION EN COIN 

71

3.4 

EMPLACEMENTS ET DÉGAGEMENTS MINIMAUX DE LA TERMINAISON 

72

3.5 

CHARTE D’APPLICATION DES ÉVACUATIONS 

73

3.6 LÉGENDE 

73

3.7 

VALEURS DU COUDE EN LONGUEURS D’ÉVENT 

74

3.8 

ÉVACUATION SUR LE DESSUS - TERMINAISON HORIZONTALE 

74

3.9 

ÉVACUATION À L’ARRIÈRE - TERMINAISON HORIZONTALE 

76

3.10 

ÉVACUATION SUR LE DESSUS OU À L’ARRIÈRE - TERMINAISON VERTICALE 

78

3.11 

CONVERSION EN ÉVACUATION À L’ARRIÈRE 

81

4.0 INSTALLATION 

82

4.1 

PROTECTION DU MUR ET DU PLAFOND 

82

4.1.1 INSTALLATION 

HORIZONTALE 

83

4.1.2 INSTALLATION 

VERTICALE 

84

4.2 

UTILISATION DE COMPOSANTS FLEXIBLES D’ÉVACUATION 

84

4.2.1 

INSTALLATION DE LA TERMINAISON HORIZONTALE 

85

4.2.2 

INSTALLATION DE LA TERMINAISON VERTICALE 

86

4.2.3 

RACCORDEMENT DES ÉVENTS À L’APPAREIL 

87

4.3 

UTILISATION DE COMPOSANTS RIGIDES D’ÉVACUATION 

87

4.3.1 

INSTALLATION DE LA TERMINAISON HORIZONTALE 

88

4.3.2 

INSTALLATION DE LA TERMINAISON HORIZONTALE PROLONGÉE AJUSTABLE 

88

4.3.3 

INSTALLATION DE LA TERMINAISON VERTICALE 

89

4.4 

TERMINAISON VERTICALE À TRAVERS UNE CHEMINÉE EXISTANTE 

90

4.5 

INSTALLATION DANS UNE MAISON MOBILE 

91

4.6 

BRANCHEMENT DU GAZ 

92

4.7 

INTERRUPTEUR MURAL OPTIONNEL 

92

5.0 OSSATURE 

93

5.1 

DÉGAGEMENTS MINIMAUX AUX MATÉRIAUX COMBUSTIBLES 

94

5.1.1 

ÉVACUATION À L’ARRIÈRE 

96

5.1.2 

ÉVACUATION SUR LE DESSUS 

96

5.2 

DÉGAGEMENTS MINIMAUX AUX ENCEINTES COMBUSTIBLES 

97

5.3 

DÉGAGEMENTS MINIMAUX DE LA TABLETTE 

98

6.0 BRANCHEMENT 

ÉLECTRIQUE 

99

7.0 

SCHÉMA DE CÂBLAGE 

100

8.0 FINITIONS 

101

8.1 PORTE 

VITRÉE 

101

8.2 

MISE EN PLACE DU LOGO 

101

8.3 

INSTALLATION DU BRÛLEUR 

101

8.4 

INSTALLATION ET ENLÈVEMENT DE LA FAÇADE 

102

8.4.1 FAÇADE 

102

8.4.2 FAÇADE 

CONTEMPORAINE 

102

9.0 

INSTALLATION DE LA SOUFFLERIE OPTIONNELLE 

103

10.0 FONCTIONNEMENT 

104

10.1 

FONCTIONS DES COMMANDES 

105

11.0 RÉGLAGES 

105

11.1 

REMPLACEMENT DE L’INJECTEUR DE VEILLEUSE ET DE L’INJECTEUR DE BRÛLEUR 

105

11.2 

VÉRIFICATION DE LA PRESSION 

106

11.3  

ÉTRANGLEMENT DES ÉVENTS VERTICAUX 

106

12.0 ENTRETIEN 

107

12.1 ENTRETIEN 

ANNUEL 

107

12.2 

REMPLACEMENT DE LA VITRE DE PORTE 

108

12.3 

SOINS DE LA VITRE 

108

12.4 

REMPLACEMENT DE LA LUMIÈRE DE VEILLE 

109

12.4.1 

REMPLACEMENT DE L’AMPOULE 

109

12.4.2 

INSTALLATION DE L’ASSEMBLAGE DE LENTILLE 

109

12.4.3 

REMPLACEMENT DE L’ASSEMBLAGE DE LENTILLE 

109

13.0 RECHANGES 

110

14.0 VUE 

D’ENSEMBLE 

111

15.0 ACCESSORIES 

112

16.0 

L’ASSEMBLAGE DE LA SOUPAPE 

113

17.0 VENTILATION 

114

18.0 

GUIDE DE DÉPANNAGE 

115

19.0 GARANTIE 

117

20.0 HISTORIQUE 

D’ENTRETIEN 

118

21.0 NOTES 

119

FR

W415-1351 / 09.02.14

66  

Summary of Contents for GD19-1N

Page 1: ...ectrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the...

Page 2: ...ING CHIMNEY 29 4 5 MOBILE HOME INSTALLATION 30 4 6 GAS INSTALLATION 31 4 7 OPTIONAL WALL SWITCH 31 5 0 FRAMING 32 5 1 MINIMUM CLEARANCE TO COMBUSTIBLES 33 5 1 1 REAR VENT 34 5 1 2 TOP VENT 34 5 2 MINI...

Page 3: ...ION AND REMOVAL section Front face see FRONT FACING AND INSET KIT INSTALLATION section Top vent see REAR VENT CONVERSION section Venting see VENTING section Blower see OPTIONAL BLOWER INSTALLATION sec...

Page 4: ...d at least annually by a qualified service person More frequent cleaning may be required due to excessive lint from carpeting bedding material etc The appliance area must be kept clear and free from c...

Page 5: ...m ELECTRICAL ACCESS 213 4 552mm 193 4 502mm 7 178mm 4 102mm 341 8 867mm 13 4 45mm 21 2 64mm 5 127mm 91 2 241mm 9 229mm 7 178mm 4 102mm 263 8 670mm 13 330mm 201 2 521mm 193 4 502mm 331 8 841mm 337 8 86...

Page 6: ...uld choose a location where the vent will pass through the house without cutting a floor or roof joist If the appliance is installed directly on carpeting vinyl tile or other combustible material othe...

Page 7: ...T ONLY FOR USE ONLY WITH BARRIER W565 0170 FOLLOW THE INSTALLATION INSTRUCTIONS LOCATED IN THE INSTALLATION MANUAL WARNING DO NOT ADD ANY MATERIAL TO THE APPLIANCE WHICH WILL COME IN CONTACT WITH THE...

Page 8: ...TAINED THESE SPACERS MUST NOT BE REMOVED 3 1 VENTING LENGTHS AND COMPONENTS Use only Wolf Steel Simpson Dura Vent Selkirk Direct Temp American MetalAmerivent or Metal Fab venting components Minimum an...

Page 9: ...ot be combined These vent kits allow for either horizontal or vertical venting of the appliance The maximum allowable horizontal run is 20 feet 6 1m The maximum allowable vertical vent length is 40 fe...

Page 10: ...W415 1351 08 29 14 10 EN 26 3 8 670MM 26 3 8 670MM MINIMUM PLUS RISE 20 508MM MAXIMUM See VENTING section 35 FT 11M MAXIMUM 3 FT 1M MINIMUM 16 406MM MINIMUM...

Page 11: ...nimum 12 304 8mm above grade The maximum allowable vent length is 10 3 1m for a fireplace and 8 2 4m for a stove 9 4A 12 305MM MINIMUM TO GRADE 33 1 8 841MM 20 508mm MAXIMUM 6 152 4mm RISE 3 3 2 CORNE...

Page 12: ...12 304 8mm Clearance under a veranda porch deck or balcony N 16 406 4mm 16 406 4mm Clearance above the roof O 2 0 6m 2 0 6m Clearance from an adjacent wall including neighbouring buildings P 8 2 4m 8...

Page 13: ...n Vertical rise is equal to or greater than the horizontal run Vertical rise is less than horizontal run Vertical rise is equal to or greater than the horizontal run Vertical rise is less than horizon...

Page 14: ...RISE IN FEET METERS VT HORIZONTAL VENT RUN PLUS OFFSET IN FEET METERS HT For vent configurations requiring more than one 90 elbow the following formulas apply Formula 1 HT VT Formula 2 HT VT 35 feet 1...

Page 15: ...rmula 2 HT VT 24 75 FT 7 5m 16 7FT 5 1m 24 75 7 5m Since both formulas are met this vent configuration is acceptable 0 5 1 5 15 4 6 20 6 1 100 2540 50 1270 150 3810 12 5 3 8 19 1 2 495 3 57 1447 8 147...

Page 16: ...the lines represents acceptable values for HT and VT HT VT 16 6_2B For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT VT Formula 2 HT VT 35 feet 10 7m...

Page 17: ...r vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT 3 5VT Formula 2 HT VT 24 75 feet 7 5m Example V1 4 FT 1 2m V2 1 5 FT 0 5m VT V1 V2 4 FT 1 2m 1 5 FT 0...

Page 18: ...le V1 3 FT 0 9m V2 6 FT 1 8m V3 8 FT 2 4m VT V1 V2 V3 3FT 0 9m 6FT 1 8m 8FT 2 4m 17FT 5 2m H1 2 FT 0 6m H2 2 5 FT 0 8m HR H1 H2 2FT 0 6m 2 5FT 0 8m 4 5FT 1 4m HO 03 four 90 elbows 90 03 360 90 8 1 FT...

Page 19: ...apply Formula 1 HT 3 VT Formula 2 HT VT 35 feet 10 7m Example V1 2 FT 0 6m V2 1 FT 0 3m V3 1 5 FT 0 5m VT V1 V2 V3 2FT 0 6m 1FT 0 3m 1 5FT 0 5m 4 5FT 1 4m H1 6 FT 1 8m H2 2 FT 0 6m HR H1 H2 6FT 1 8m 2...

Page 20: ...3 1FT 0 3m 1FT 0 3m 10 75FT 3 3m 12 75 FT 3 9m HO 03 four 90 elbows one 45 elbow 90 03 360 45 90 6 75 FT 2 1m HT HR HO 12 75FT 3 9m 6 75 FT 2 1m 19 5 FT 5 9m HT VT 19 5FT 5 9m 6 5FT 2m 26FT 7 6m Formu...

Page 21: ...ear exit remove components as illustrated When reinstalling in the alternate position Check gaskets for tears replace if necessary to ensure a proper seal 4 102mm Collar 4 102mm Gasket 7 178mm Collar...

Page 22: ...ASPHYXIATION IMPROPER SUPPORT OF THE ENTIRE VENTING SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE USE VENT RUN SUPPORTS AND CONNECT VENT SECTIONS PER INSTALLATION INSTRUCTIONS RISK OF FIRE DO NOT ALLOW LO...

Page 23: ...rom your authorized dealer distributor See accessories to order specific kits required A Determine the air terminal location cut and frame a square opening as illustrated in the ceiling and the roof t...

Page 24: ...he additional length needed for the finished wall surface Apply a heavy bead of the high temperature sealant W573 0007 Mill Pac not supplied to the inner sleeve of the air terminal Slip the vent pipe...

Page 25: ...ving a min 3 4 19mm of the air terminal connector showing above the top of the flashing Slide the flashing underneath the sides and upper edge of the shingles Ensure that the air terminal connector is...

Page 26: ...igh temperature silicone sealant W573 0002 not supplied or black high temperature sealant W573 0007 Mill Pac not supplied with the exception of the appliance exhaust flue collar which must be sealed u...

Page 27: ...g with caulking not supplied The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of the return flange 26 3 SCREWS 10x2 OUTER RIGID PIPE CAULKING...

Page 28: ...shingles above and to the sides of the air terminal connector Place the flashing over the air terminal connector and slide it underneath the sides and upper edge of the shingles Ensure that the air te...

Page 29: ...ectly off the appliance Follow vent manufacturer s installation instructions Different manufacturer s venting components must not be combined Once the preferred manufacturer s appliance adaptor has be...

Page 30: ...base to secure For free standing products contact your local authorized dealer distributor for the appropriate securing kit For mobile home installations the appliance must be fastened in place It is...

Page 31: ...INE SHOULD BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN ASSURE THAT A CONTINUOUS GAS FLOW IS AT THE BURNER BEFORE CLOSING THE DOOR ENSURE ADEQUATE VENTILATION FOR GAS AND ELECTRICAL LOCATIONS SEE DI...

Page 32: ...E 136 STANDARD TEST METHOD FOR BEHAVIOUR OF MATERIALS IN A VERTICAL TUBE FURNACE AT 1382 F 750 C AND UL763 SHALL BE CONSIDERED NON COMBUSTIBLE MATERIALS MINIMUM CLEARANCE TO COMBUSTIBLES MUST BE MAINT...

Page 33: ...51mm to top of the vent pipe Combustible Finishing 0 to rear 0 to front face top and sides 13 330mm recessed depth Rear Vent 39 1 8 994mm to enclosure top from base of the unit 45 1 8 1146mm to ceilin...

Page 34: ...m MINIMUM 2 2 1 4 5 6 5 m m 3 3 1 2 8 5 1 m m OUTSIDE CHASE INSIDE CHASE 221 4 565mm PROTRUSION SIDE WALL 131 4 337mm 5 1 1 REAR VENT 221 4 565mm 2 51mm 2 51mm 4 102mm 4 102mm 6 152mm INSIDE CHASE 131...

Page 35: ...ating vertically on a top vented appliance the height clearance can be reduced to 39 1 8 994mm 2 51mm 1 25mm 263 8 670mm MINIMUM PLUSRISE 1 25mm 0 IFNON COMBUSTIBLE FINISHINGISUSEDSUCH ASBRICKANDSTONE...

Page 36: ...LEARANCES TO COMBUSTIBLES FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY CAUSE A FIRE OR CAUSE THE APPLIANCE TO OVERHEAT ENSURE ALL CLEARANCES I E BACK SIDE TOP VENT MANTEL FRONT ETC ARE CLEARLY MAINTA...

Page 37: ...UALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH LOCAL CODES IN THE ABSENCE OF LOCAL CODES USE THE CURRENT CSA22 1 CANADIAN ELECTRIC CODE IN CANADA OR THE CURRENT NATIONAL ELECTRIC CODE ANSI NFPA...

Page 38: ...Volt Red Black WIRE HARNESS NOTE WIRE TAGS ARE BRACKETED Brown SWI Black Red Green x2 TH Orange x2 THTP Black Yellow Blue Black TP MODULE PLUG RELAY PLUG Black Green Orange Black 12 Volt To Accent Lig...

Page 39: ...3 E Place the front facing onto the appliance and install the rest of the top trim and control panel as shown in Figure 4 THE COMPONENTS IN THIS KIT ARE HEAVY USE CARE WHEN LIFTING AND ENSURE THEY ARE...

Page 40: ...W415 1351 08 29 14 40 EN SCREEN SAFETY SAFETY SCREEN FIG 4...

Page 41: ...brackets ensure the front face is on a soft surface to avoid any damages during bracket instalation see Figure 1 C Install the lower side bracket on the front as shown in Figure 2 D Install the safety...

Page 42: ...e door to release B Slide the door forward off its support C Reverse steps to re install the glass door Slide the front with safety screen onto the hooks over the top of the spacers and then let it sl...

Page 43: ...ee separate instructions accompanying the burner assembly sold separately Keep those instructions along with this manual Position the remote receiver in the valve compartment close to the electrical j...

Page 44: ...e current CSA C22 1 Canadian Electrical Code in Canada or the current ANSI NFPA 70 National Electrical Code in the United States If an optional blower is to be used the blower must be connected to the...

Page 45: ...touch any electric switch do not use any phone in your building 1 Stop Read the above safety information on this label 2 Turn remote wall switch to off position 3 Turn off all electrical power to the...

Page 46: ...as supply to the appliance B Remove the cast front safety screen glass viewing door and log set C Remove the 2 securing screws Slide the burner assembly to the right and lift out D Using a deep socket...

Page 47: ...painted If overspray or painting of the pilot assembly has occurred remove the paint from the pilot assembly or replace Fine emery cloth or sandpaper can be used to remove the paint from the pilot hoo...

Page 48: ...ntake system is disassembled re install and re seal per the instructions provided for the initial installation I Cleaning the safety barrier may be necessary due to excessive lint dust from carpeting...

Page 49: ...CARE MUST BE TAKEN WHEN REMOVING AND DISPOSING OF ANY BROKEN DOOR GLASS OR DAMAGED COMPONENTS BE SURE TO VACUUM UP ANY BROKEN GLASS FROM INSIDE THE APPLIANCE BEFORE OPERATION DO NOT STRIKE SLAM OR SC...

Page 50: ...needs to be replaced follow these instructions A Turn off all electrical supply B Remove the safety screen front and door from the firebox C Unscrew the lens cover making sure the washer stays in plac...

Page 51: ...REQUIRED TO HONOUR THE CLAIM When ordering replacement parts always give the following information Model Serial Number of appliance Installation date of appliance Part number Description of part Fini...

Page 52: ...8 W350 0126 JUNCTION BOX HOUSING 08 21 14 FOR REPLACEMENT PARTS REFER TO VALVE TRAIN ASSEMBLY 3 4 5 6 GD19 OVERVIEW 7 11 12 13 8 9 10 16 17 14 15 18 17 15 16 1 2 FOR REPLACEMENT PARTS REFER TO B19NL F...

Page 53: ...TONE BRICK PANEL X2 GD839KT W475 0520 LS SANDSTONE BRICK PANEL GD839KT W475 0518 REAR SANDSTONE BRICK PANEL GD839KT W475 0519 RS SANDSTONE BRICK PANEL GD839KT W090 0153 SIDE PORCELAIN PANEL X2 PRP19 1...

Page 54: ...69 PILOT ASSEMBLY NG W456 0052 BURNER ORIFICE 52 NG W725 0032 ELECTRONIC IGNITION VALVE NG W725 0041 GAS VALVE W707 0005 TRANSFORMER W010 2517 ELEC IGNITION ASSEMBLY W432 0063 3 8 MANIFOLD W035 0159 B...

Page 55: ...ART NUMBER DESCRIPTION 1 2 3 4 5 6 7 8 W010 1653 PAN BURNER ASSEMBLY W135 0322 REAR LOG GL 622 W135 0323 LEFT LOG GL 622 W135 0324 RIGHT LOG GL 622 W135 0325 CENTRE LOG GL 622 GL 622 LOG SET W550 0001...

Page 56: ...NO PART NUMBER DESCRIPTION 1 2 3 4 5 W010 2493 PAN BURNER ASSEMBLY W010 2498 FRONT ROCK TRIM ASSEMBLY X2 W655 0378 ROCK BURNER SUPPORT W135 0424 SMALL GREY ROCKS MKR W010 2499 ROCK BOWL ASSEMBLY 1 2...

Page 57: ...T GUARD RP4 RESTRICTOR PLATE 4 8 9 15 16 17 1 11 1 13 W010 0300 4 x 10 FLEX LINER C W SPACERS 1 15 1 16 W025 0001 DECORATIVE BRASS BAND W025 0003 DECORATIVE BLACK BAND 11 12 13 10 18 19 20 21 22 1 14...

Page 58: ...d plugged into the module Check voltage of the transformer under load at the spade connections on the module with the ON OFF switch in the ON position Acceptable readings of a good transformer are bet...

Page 59: ...e rectification Verify correct pilot orifice is installed and inlet gas specifications to manual Remember the flame carries the rectification current not the gas If the flame lifts from pilot hood the...

Page 60: ...or plate See RESTRICTING VENTS section if applicable Main burner flame is a blue lazy transparent flame Blockage in vent Remove blockage In really cold conditions ice buildup may occur on the terminal...

Page 61: ...damaging chemicals or cleaners will not be the responsibility of NAPOLEON All parts replaced under the President s Limited Lifetime Warranty Policy are subject to a single claim During the first 10 y...

Page 62: ...W415 1351 08 29 14 62 EN 43 1 22 0 SERVICE HISTORY...

Page 63: ...W415 1351 08 29 14 63 EN 44 1 23 0 NOTES...

Page 64: ...ces Outdoor Fireplaces Gourmet Grills Fireplaces Heating Cooling call 705 721 1212 Grills call 705 726 4278 napoleonproducts com 24 Napoleon Road Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie...

Page 65: ...ice des incendies L installation et l entretien doivent tre faits par un installateur qualifi une agence d entretien ou le fournisseur Cet appareil peut tre install dans une maison pr fabriqu e mobile...

Page 66: ...N HORIZONTALE PROLONG E AJUSTABLE 88 4 3 3 INSTALLATION DE LA TERMINAISON VERTICALE 89 4 4 TERMINAISON VERTICALE TRAVERS UNE CHEMIN E EXISTANTE 90 4 5 INSTALLATION DANS UNE MAISON MOBILE 91 4 6 BRANCH...

Page 67: ...STALLATION DU CON TOUR ET DES PANNEAUX ORNEMENTAUX vacuation sur le dessus voir la section CONVERSION EN VACUATION L ARRI RE vacuation voir la section VACUATION Soufflerie voir la section INSTALLATION...

Page 68: ...liste en entretien Un entretien plus fr quent pourrait tre n cessaire en raison des peluches provenant des tapis literie etc L emplacement de l appareil doit tre gard libre de tous mat riaux combustib...

Page 69: ...mm 7 178mm 4 102mm 341 8 867mm 13 4 45mm 21 2 64mm 5 127mm 91 2 241mm 9 229mm 7 178mm 4 102mm 263 8 670mm 13 330mm 201 2 521mm 193 4 502mm 331 8 841mm 337 8 860mm 12 305mm 13 330mm GASLINE ACCESS ELEC...

Page 70: ...couper des solives de plancher ou de toit Si l appareil est install directement sur un tapis sur une surface de vinyle ou tout autre rev tement de plancher combustible autre que le bois l appareil de...

Page 71: ...STALLATION DE PROPRIETAIRE POUR L EVACUATION PRECISE LES LONGUEURS VERTICALES MINIMALES ET MAXIMALES SONT3 PIEDS ET 35 PIEDS RESPECTIVEMENT UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILSE AVEC CET APPAR...

Page 72: ...REQUIS AU D BUT AU MILIEU ET LA FIN DE CHAQUE COUDE AFIN DE MAINTENIR CET ESPACE VIDE N ENLEVEZ PAS CES ESPACEURS 3 1 LONGUEURS DES CONDUITS D VACUATION ET COMPOSANTS Utilisez uniquement des composant...

Page 73: ...inez pas de composants rigides ou flexibles ni de composants d vacuation provenant de fabricants diff rents Ces ensembles d vents permettent soit une vacuation verticale soit une vacuation horizontale...

Page 74: ...16 406MM MINIMUM 35 PI 11M MAXIMUM 3 PI 1M MINIMUM 26 3 8 670MM 26 3 8 670MM MINIMUM PLUS L L VATION 20 508MM MAXIMUM Voir la section VACUATION FR W415 1351 09 02 14 74...

Page 75: ...RTICULI RES D VENTS 3 3 1 ENSEMBLE P RISCOPIQUE 12 305MM MINIMUM AU NIVEAU DU SOL 12 305MM MINIMUM AU NIVEAU DU SOL 24 610MM MINIMUM 24 610MM MINIMUM 33 1 8 841MM 3 3 2 INSTALLATION EN COIN Lorsque l...

Page 76: ...ssus du toit O 2 0 6m 2 0 6m D gagement des murs adjacents incluant les maisons voisines P 8 2 4m 8 2 4m Le toit doit tre incombustible et sans ouvertures Q 3 0 9m 3 0 9m Voir le tableau pour les dime...

Page 77: ...us petite que la course horizontale La course verticale est plus grande ou gale la course horizontale La course verticale est plus petite que la course horizontale La course horizontale la course vert...

Page 78: ...IEDS M TRES VT LONGUEUR DES COURSES HORIZONTALES PLUS LES D VIATIONS EN PIEDS M TRES HT Lorsque la configuration de l vacuation exige plus qu un coude de 90 les formules suivantes s appliquent Formule...

Page 79: ...H2 3PI 0 9m 5PI 1 5m 8PI 2 4m HO 03 two 90 elbows 90 03 180 90 2 7PI 0 8m HT HR HO 8PI 2 4m 2 7PI 0 8m 10 7PI 3 3m HT VT 10 7PI 3 3m 6PI 1 8m 16 7PI 5 1m Formule 1 HT 4 2 VT 4 2 VT 4 2PI 1 3m x 6PI 1...

Page 80: ...tables pour HT et VT HT VT 16 6_2B 90 V1 V2 H1 H2 90 90 90 H3 Lorsque la configuration de l vacuation exige plus que deux coudes de 90 les formules suivantes s appliquent Formule 1 HT VT Formule 2 HT...

Page 81: ...eds Exemple V1 4 PI V2 1 5 PI VT V1 V2 4 1 5 5 5 PI H1 2 PI H2 1 PI H3 1 PI H4 1 5 PI HR H1 H2 H3 H4 2 1 1 1 5 5 5 PI HO 0 03 quatre coudes 90 un coude 45 90 0 03 90 90 90 90 45 90 9 45 PI HT HR HO 5...

Page 82: ...4m 17FT 5 2m H1 2 FT 0 6m H2 2 5 FT 0 8m HR H1 H2 2FT 0 6m 2 5FT 0 8m 4 5FT 1 4m HO 03 four 90 elbows 90 03 360 90 8 1 FT 2 5m HT HR HO 4 5FT 1 4m 8 1FT 2 5m 12 6FT 3 8m HT VT 12 6FT 3 8m 17FT 5 2m 29...

Page 83: ...ormula 2 HT VT 35 feet 10 7m Example V1 2 FT 0 6m V2 1 FT 0 3m V3 1 5 FT 0 5m VT V1 V2 V3 2FT 0 6m 1FT 0 3m 1 5FT 0 5m 4 5FT 1 4m H1 6 FT 1 8m H2 2 FT 0 6m HR H1 H2 6FT 1 8m 2FT 0 6m 8FT 2 4m HO 03 fo...

Page 84: ...FT 3 3m 12 75 FT 3 9m HO 03 four 90 elbows one 45 elbow 90 03 360 45 90 6 75 FT 2 1m HT HR HO 12 75FT 3 9m 6 75 FT 2 1m 19 5 FT 5 9m HT VT 19 5FT 5 9m 6 5FT 2m 26FT 7 6m Formula 1 HT 3 VT 3 VT 3FT 0 9...

Page 85: ...Inspectez les joints d tanch it pour des d chirures remplacez les si n cessaire pour assurer une bonne tanch it Collet de 4 102mm Joint d tanch it de 4 102mm Collet de 7 178mm Joint d tanch it de 7 17...

Page 86: ...ME DE CONDUIT D VENT N EST PAS AD QUATEMENT SOUTENU IL RISQUE DE FL CHIR OU DE SE S PARER UTILISEZ DES SUPPORTS DE CONDUIT ET RACCORDEZ LES SECTIONS DE CONDUITS SELON LES INSTRUCTIONS D INSTALLATION...

Page 87: ...e la profondeur du mur combustible A Appliquez un joint de calfeutrage non fourni tout autour de la bordure de la face int rieure de l espaceur coupe feu installez l espaceur coupe feu contre le trou...

Page 88: ...ustible Essayez de positionner le conduit d vent michemin entre deux solives pour ne pas tre oblig de les couper Utilisez du fil plomb pour aligner le centre des ouvertures Un protecteur de conduit d...

Page 89: ...vis 8 Scellez avec du scellant haute temp rature W573 0002 non fourni C Ins rez les gaines dans le coupe feu tout en conservant le d gagement n cessaire aux mat riaux combustibles En soutenant la ter...

Page 90: ...nt un minimum de 3 4 19 1mm de connecteur de terminaison visible au dessus du haut du solin Glissez le solin sous les c t s et le bord sup rieur des bardeaux Assurez vous que le connecteur de terminai...

Page 91: ...D VACUATION Le syst me d vacuation doit tre soutenu peu pr s tous les 3 pieds 0 9m de courses verticales et horizontales Utilisez l ensemble de support mural Wolf Steel ou des supports incombustibles...

Page 92: ...R CALFEUTRAGE CHEVAUCHEMENT DE 2 50 8mm SCELLANT HAUTE TEMP RATURE CONDUIT RIGIDE INT RIEUR A Mettez l appareil en place Mesurez la longueur d vent requise entre la terminaison et l appareil en tenant...

Page 93: ...ar dessus le connecteur de terminaison et glissez le sous les c t s et le bord sup rieur des bardeaux Assurez vous que le connecteur de terminaison est bien centr dans le solin en laissant une marge d...

Page 94: ...n du fabricant du syst me d vacuation Des composants d vacuation de diff rents fabricants ne doivent pas tre combin s Une fois que l adaptateur de votre choix est install le reste du syst me d vacuati...

Page 95: ...vant gauche et droit de la base Lors d une installation dans une maison mobile l appareil doit tre fix au plancher Fixez l aide de vis 10 t te hexagonale ins r es dans les trous de la base teignez tou...

Page 96: ...DOIT TRE EFFECTU E PAR UN TECHNICIEN QUALIFI ASSUREZ VOUS QUE L ARRIV E DE GAZ AU BR LEUR EST CONTINUE AVANT DE FERMER LA PORTE ASSUREZ VOUS D UNE VENTILATION AD QUATE POUR LES EMPLACEMENTS DE L ENTR...

Page 97: ...E FOURNAISE AVEC TUBE VERTICAL 1382 F 750 C ET LA NORME UL763 SONT CONSID R S COMME TANT DES MAT RIAUX NON COMBUSTIBLES AFIN D VITER UN RISQUE D INCENDIE LES D GAGEMENTS MINIMAUX AUX MAT RIAUX COMBUST...

Page 98: ...ion combustible 0 0mm l arri re 0 0mm des c t s et du dessus en fa ade 13 330mm profondeur de l enclave vacuation l arri re 39 1 8 994mm du haut de l enceinte jusqu la base de l appareil 45 1 8 1146mm...

Page 99: ...2 1 4 565mm MUR LAT RAL ENCEINTE INT RIEURE ENCEINTE EXT RIEURE 2 51mm 4 102mm 6 152mm 2 51mm 4 102mm PROJECTION 13 1 4 337mm 22 1 4 565mm 22 1 4 565mm 2 51mm 4 102mm 6 152mm MUR LAT RAL PROJECTION EN...

Page 100: ...ppareil vacuation sur le dessus la hauteur de d gagement peut tre r duite 39 1 8 841mm Voir la section VACUATION Voir la section VACUATION 263 8 670mm MINIMUMPLUS L L VATION 1 25mm 1 25mm 331 8 841mm...

Page 101: ...GAGEMENTS MINIMAUX DE LA TABLETTE AVERTISSEMENT RISQUE D INCENDIE CONSERVEZ TOUS LES D GAGEMENTS AUX MAT RIAUX COMBUSTIBLES SP CIFI S NE PAS RESPECTER CES INSTRUCTIONS PEUT CAUSER UN INCENDIE OU UNE...

Page 102: ...ODES LOCAUX EN L ABSENCE DE CODES LOCAUX UTILISEZ LA VERSION COURANTE DU CODE CANADIEN DE L LECTRICIT CSA C22 1 AU CANADA OU LE NATIONAL ELECTRICAL CODE ANSI NFPA 70 AUX TATS UNIS ALLUMEZ TOUJOURS LA...

Page 103: ...DE FILS SWI Noir Rouge Vert x2 TH Orange x2 THTP Noir Jaune Bleu Noir TP PRISE DU MODULE PRISE DU RELAIS Noir Vert Orange Noir 12 volts la lumi re de veille et l interrupteur de la lumi re de veille l...

Page 104: ...DE PROTECTION ET PORTE VITR E B Installez les supports c te assurez vous que le fa ade est placez face vers le bas sur une surface douce pour viter tout dommage pendant l installation des supports voi...

Page 105: ...FR W415 1351 09 02 14 105 PROTECTION CRAN DE CRAN DE PROTECTION FIG 4...

Page 106: ...s le bas sur une surface douce pour viter tout dommage pendant l installation des supports voir Figure 1 C Installez les support de la partie inf rieure sur la face avant voir Figure 2 D Installez l c...

Page 107: ...la porte B Pivotez ensuite le haut de la porte vers l avant jusqu ce que vous puissiez saisir les c t s C Inversez ces tapes pour r installer l cran de protection et la porte Glisser le fa ade avec cr...

Page 108: ...BR LEUR Consultez les instructions incluses avec l assemblage du br leur vendu s par ment 35 25 PLACER LE T L COMMANDE SUR CETTE TIQUETTE BASE DU FOYER BO TE DE D RIVATION Positionner le t l commande...

Page 109: ...tricit CSA C22 1 au Canada ou le National Electrical Code ANSI NFPA 70 aux tats Unis Si une soufflerie optionnelle est utilis e la soufflerie doit tre branch e l alimentation lectrique principale Ache...

Page 110: ...n utilisez aucun t l phone dans votre immeuble 1 ARR TEZ Lisez les consignes de s curit sur l tiquette de fonctionnement 2 Mettez l interrupteur mural la position OFF 3 Coupez l alimentation lectrique...

Page 111: ...l appareil B Retirez la fa ade en fonte la porte vitr e et les b ches C Retirez les deux vis de fixation glissez le br leur vers la droite soulevez puis retirez D Retirez l injecteur de br leur princ...

Page 112: ...la veilleuse n a pas t peint S il y a des traces de peinture ou de surpulv risation enlevez les de l assemblage de la veilleuse ou remplacez le Une toile d meri ou du papier sabl fins peut tre utilis...

Page 113: ...lant autoris G V rifiez si les joints d tanch it sur les c t s le haut et le bas de la porte ne sont pas bris s ou manquants Remplacez si n cessaire H Si pour une raison quelconque le syst me d vents...

Page 114: ...ORTE VITR E NE FAITES PAS FONCTIONNER L APPAREIL LORSQUE LA PORTE VITR E EST ENLEV E FISSUR E BRIS E OU GRATIGN E 56 1A 12 3 SOINS DE LA VITRE 5 5 1 L appareil est muni d une 5mm en verre c ramique Re...

Page 115: ...appareil C D vissez le couvercle de la lentille en vous assurant que la rondelle demeure en place NOTE Lorsque vous manipulez l ampoule ne la laissez pas entrer en contact direct avec vos doigts prot...

Page 116: ...DE Lorsque vous commandez des pi ces donnez toujours l information suivante Mod le et num ro de s rie de l appareil Date d installation de l appareil Num ro de la pi ce Description de la pi ce Fini ID...

Page 117: ...LES PI CES DE REMPLACEMENT VOIR B19NL POUR LES PI CES DE REMPLACEMENT VOIR B19NS 10 11 12 13 W010 2556 W660 0019 W380 0021 W660 0009 W475 0528 W585 0235 W750 0185 W500 0042 W387 0011 CES ARTICLES PEUT...

Page 118: ...BRIQUE DU VICTORIEN ARRI RE GD839KT W475 0519 PANNEAU DE BRIQUE DU VICTORIEN C T DROITE GD839KT W090 0153 PANNEAU DE PORCELAINE DU C T X2 PRP19 1 2 3 4 5 6 7 W090 0152 PANNEAU DE PORCELAINE DE L ARRI...

Page 119: ...UMAGE DU SOUPAPE LECTRONIQUE W725 0041 SOUPAPE DU GAZ W707 0005 TRANSFORMATEUR W010 2517 L ASSEMBLAGE DE ALLUMAGE DU SOUPAPE LECTRONIQUE W432 0063 COLLECTEUR 3 8 W035 0159 BASE DU BR LEUR W105 0001 BA...

Page 120: ...SSEMBLAGE DE BR LEUR PLATEAU W135 0322 B CHE DE L ARRI RE GL 622 W135 0323 B CHE DE GAUCHE GL 622 W135 0324 B CHE DE DROITE GL 622 W135 0325 B CHE DE CENTRAL GL 622 GL 622 ENSEMBLE DE B CHES W550 0001...

Page 121: ...RT NO DESCRIPTION 1 2 3 4 5 W010 2493 ASSEMBLAGE DE BR LEUR PLATEAU W010 2498 ASSEMBLAGE DE MOULURES X2 W655 0378 SUPPORT DE BR LEUR ROCHE W135 0424 ROCHES GRIS LES PETITS MKR W010 2499 ASSEMBLAGE DU...

Page 122: ...500 0077 1 25 1 23 W500 0103 PLAQUE DE TERMINALE EXTENSION AVS47KT COUPE FEU MANCHON DE CONDUIT 1 24 1 26 1 26 1 26 27 GS 150KT 14 W290 0054 JOINT D TANCH IT 7 28 W290 0056 JOINT D TANCH IT 4 CES ARTI...

Page 123: ...les d un bon transformateur se situent entre 3 2 et 2 8 volts C A Syst me de d pannage piles s il y a panne de courant V rifiez les piles Une connexion desserr e ou causant un court circuit Retirez et...

Page 124: ...rant de la flamme V rifiez si le bon injecteur de veilleuse est install et que l alimentation en gaz est conforme aux sp cifications du manuel Souvenez vous que la flamme transporte le courant redress...

Page 125: ...u produits d entretien nuisibles ne seront pas la responsabilit de NAPOL ON Toutes les pi ces remplac es en vertu de la politique de Garantie vie limit e du Pr sident ne peuvent faire l objet que d un...

Page 126: ...UE D ENTRETIEN Date 43 1 Probl mes particuliers Travail effectu Nom du technicien D taillant Historique d entretien Wolf Steel Cet appareil doit tre entretenu annuellement selon son usage FR W415 1351...

Page 127: ...23 0 NOTES 44 1 FR W415 1351 09 02 14 127...

Page 128: ...s lectriques Foyers ext rieurs Grils gaz de qualit Foyers Chauffage et Climatisation Grils composez 514 737 6294 napoleonproducts com 7200 Route Transcanadienne Montr al Qu bec H4T 1A3 24 Napoleon Roa...

Reviews: