background image

18

W415-0221 / E /  04.09.02

NAILING
 TAB

NAILING TAB INSTALLATION

1)

 Attach the nailing tabs to the corner

posts using the 2 sheet metal screws
supplied. Secure through the centre of
the top and bottom slots in the nailing
tab and then through  the existing holes
in the corner posts.

If there are no existing holes, follow
these instructions:

Position the nailing tab so that the front
face is offset with the front edge of the
corner post (approx. ½").  Centre the
nailing tab vertically on the corner post.

Figure 34 a.

Drill through the centre of the top and
bottom slots in the nailing tab. Secure using
the two sheet metal screws supplied. This allows
the nailing tab to slide back and forth for desired framing.

Figure 34 b.

2)

 To determine the final location of the nailing tab you

must first determine the thickness of your finishing mate-
rial (i.e. drywall). This will determine the dimension from
the front edge of the corner post to the nailing tab.  Once
the nailing tab is in the desired location, drill through the
centre hole of the nailing tab. Secure with a sheet metal
screw*. 

Figure 34 c.

Additional set screws may be installed

.

FIGURES 35

Combustible mantle clearance can vary according to the
mantle depth. 

FIGURE 35. 

Use the graph to help evaluate

the clearance needed. Curtains, above the fireplace, must
not be positioned lower than the 5" distance required for
the 2" combustible mantle. 

These same requirements

apply to any combustibles protruding on either side of
the fireplace.

FIGURES  34a-c

TOP

 

SLOT

FINISHING

MATERIAL

CORNER

POST

NAILING

TAB

A

B

C

CENTRE

HOLE

Summary of Contents for BGD42NT

Page 1: ...ED FOR CANADA AND UNITED STATES USING ANSI AGA CGA METHODS Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death FOR YOUR SAFETY Do not store or use gasoline or other flammable vapours and liquids i...

Page 2: ...technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water Do not operate the fireplace with the glass door removed cracked or broken Replacement of the glass should be done by a licensed or qualified service person Use only with a glass door certified with the fireplace Do not strike or slam shut the fireplace glass door This f...

Page 3: ...rior approval of an authorized company official Labour costs to work however requires the prior approval of an authorized company official Labour costs to work however requires the prior approval of an authorized company official Labour costs to work however requires the prior approval of an authorized company official Labour costs to the account of the account of the account of the account of the...

Page 4: ...oom bedroom and bed sitting room installations and is suitable for mobile home installation The natural gas model can only be installed in a mobile home that is permanently positioned on its site and fueled with natural gas No external electricity 110 volts or 24 volts is re No external electricity 110 volts or 24 volts is re No external electricity 110 volts or 24 volts is re No external electric...

Page 5: ... the vent length and number of elbows to a minimum The air terminal must remain unobstructed at all times Examine the air terminal at least once a year to verify that it is unobstructed and undamaged Purge all gas lines with the glass door of the fireplace removed Assure that a continuous gas flow is at the burner before re installing the door Underextremeventconfigurations allowseveralminutes 5 1...

Page 6: ... or balcony Clearance to windows or doors that open Clearance to permanently closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to unventilated soffit Clearance to an outside corner wall Clearance to an inside non combustible corner wall or protruding non combustible obstructions chi...

Page 7: ...ed a minimum of 12 inches above grade The maximum allow able vent length depends on the fireplace as illustrated TYPICAL VENT INSTALLATIONS FIGURES 3 For optimum performance it is recommended that all horizontal runs have a 1 inch rise per foot When terminating vertically the vertical rise is a minimum 36 inches and a maximum 40 feet from the centre of the fireplace flue out let SPECIAL VENT INSTA...

Page 8: ...rise is less than is less than is less than is less than is less than horizontal horizontal horizontal horizontal horizontal run run run run run horizontal horizontal horizontal horizontal horizontal run verti run verti run verti run verti run verti cal rise to cal rise to cal rise to cal rise to cal rise to maximum of maximum of maximum of maximum of maximum of 24 75 feet 24 75 feet 24 75 feet 24...

Page 9: ...e venting configuration only one 90 elbow VERTICAL RISE IN FEET VT TOP EXIT HORIZONTAL TERMINATION FIGURE5 See graph to determine the required vertical rise VT for the required horizontal run HT For vent configurations requiring more than one 90 el bow the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet Example 1 90 90 V1 3ft V2 8ft VT V1 V2 3 8 11 ft H1 2 5ft H2 2ft HR H1 H2 2 5 ...

Page 10: ...onfigurations requiring more than one 90 elbow the following formulas apply Formula 1 HT 4 2 VT Formula 2 HT VT 24 75 feet Example 2 Example 3 V1 4ft V2 1 5ft VT V1 V2 4 1 5 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90 8 1 ft HT HR HO 5 5 8 1 13 6 ft HT VT 13 6 5 5 19 1 ft Formula 1 HT 4 2 VT 4 2 VT 4 2 x 5 5 23 1 ft 13 6 23 1 Formula 2 HT ...

Page 11: ...2 H3 1 3 2 5 6 5 ft HO 03 four 90 elbows 90 03 90 90 90 90 90 8 1 ft HT HR HO 6 5 8 1 14 6 ft HT VT 14 6 15 29 6 ft Formula 1 HT VT 14 6 15 Formula 2 HT VT 40 feet 29 6 40 Since both formulas are met this vent configuration is ac ceptable Simple venting configurations FIGURE10 FIGURE11 For vent configurations requiring elbows the following for mulas apply Formula 1 HT VT Formula 2 HT VT 40 feet Se...

Page 12: ...13 5 ft 16 1 13 5 Since this formula is not met this vent configuration is unacceptable Formula 2 HT VT 40 feet 20 6 40 Since only formula 2 is met this vent configuration is unac ceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas Example 6 V1 1 5ft V2 5ft VT V1 V2 1 5 5 6 5 ft H1 1ft H2 1ft H3 1ft H4 10 75 ft HR H1 H2 H3 H4 1 1 1 10 75...

Page 13: ...e vent pipe liner is installed in its final position apply sealant between the pipe liner and the firestop spacer FIGURE17 FIGURE18 FORSAFEANDPROPEROPERATIONOFTHEFIREPLACE FOLLOW THE VENTING INSTRUCTIONS EXACTLY AHEATSHIELDMUSTBEUSEDIFTHEWALLTERMINALIS INSTALLED ON COMBUSTIBLE EXTERIOR SURFACES NOTE Only a clearance to combustibles of 1 all around the vent pipe is required HORIZONTAL INSTALLATION ...

Page 14: ... Apply a heavy bead of the high temperature sealant supplied with the unit to the inside of the 5 liner approxi mately 1 from the end Slip the liner a minimum of 2 over the fireplace vent collar and secure with 3 8 screws 6 Using the 8 diameter flexible aluminium liner apply sealant slide a minimum of 2 over the fireplace combus tion air collar and secure with 3 8 screws 7 If more liner needs to b...

Page 15: ...lers to the air terminal 3 Install the air terminal See item 3 of the Horizontal Air Terminal Installation Extend the 5 telescopic sleeve connect to the air terminal assembly Fasten with self tapping screws and seal Repeat using the 8 telescopic sleeve FIGURE25 TELESCOPIC SLEEV VENTING 20 COUPLER AIR TERMINAL FIGURE26 USING RIGID VENT COMPONENTS 5 Remove nails from the shingles above and to the si...

Page 16: ... of the air terminal Slip a 5 diameter coupler a minimum of 2 over the sleeve and secure using 3 screws 4 Apply high temperature seal ant to the outer edge of the of the outside sleeve of the air terminal Slip a 8 diameter coupler over the sleeve and secure as before FIG URE 25 Trim the 8 coupler even with the 5 coupler end 5 Thread the air terminal pipe assembly down through the roof support and ...

Page 17: ...rtically See Vertical Venting or Horizontal Air Terminal Installation for installation The fireplace is equipped with two 1 4 diameter holes located in the front left and right corners of the base For mobile home installations the fireplace must be fastened in place Use 10 hex head screws inserted through the holes in the base to secure It is recommended that the fireplace be secured in all instal...

Page 18: ...rth for desired framing Figure 34 b 2 To determine the final location of the nailing tab you must first determine the thickness of your finishing mate rial i e drywall This will determine the dimension from the front edge of the corner post to the nailing tab Once the nailing tab is in the desired location drill through the centre hole of the nailing tab Secure with a sheet metal screw Figure 34 c...

Page 19: ...tom of the logs 1 FIGURES37a d 2 3 GLOWING EMBERS 4 5 6 a DOORLATCH UPPERLOUVRE SLOT HINGESCREEN LOWER LOUVRES VALVE CONTROL DOOR b 3 Tear the glowing embers into pieces and place along the front row of ports covering all of the burner area in front of the small logs 2 3 Care should be taken to shred the embers into thin small irregular pieces as only the exposed edges of the fibre hairs will glow...

Page 20: ...Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the securing stud at the bot tom left of the unit using a lock washer and wing nut Ensure that the thermodisc touches the firebox wall Attach the connectors from the black and red wires to the blower Attach and secure the vari able speed switch using the nut provided Plug the harness cord in...

Page 21: ... dealer With the thermostatic sensor option the fan when turned on becomes thermally activated and will automatically run approximately 15 30 minutes after the fireplace has been lit and for approximately 30 45 minutes after the fireplace has been turned off If the fireplace was not previously equipped with a fan route a grounded 2 wire 60hz power cable to the junction box At this point it must be...

Page 22: ...ormation on this label 2 Turn off all electric power to the fireplace 3 Turn the gas knob clockwise to off 4 Wait five 5 minutes to clear out any gas If you smell gas including near the floor Stop Follow B in the above safety information on this label If you don t smell gas go the next step 5 Turn gas knob counter clockwise to pilot 6 Depress slightly and hold gas knob while lighting the pilot wit...

Page 23: ...tter will cause a more yellow flame but can lead to carboning Opening the air shutter will cause a more blue flame but can cause flame lifting from the burner ports The flame may not appear yellow immediately allow 15 to 30 minutes for the final flame colour to be estab lished Air shutter adjustment must only be done by a qualified installer To access the air shutter remove the two screws that se ...

Page 24: ...70 BLACK DOOR C W GLASS W455 0004 36 NATURAL GAS ORIFICE W455 0066 51 PROPANE GAS ORIFICE W361 0014 VERMICULITE W500 0028 FIRESTOP SPACER FLEX VENTING FLEXIBLE VENT KITS GD420 5 FT PART NO DESCRIPTION W010 0772 5 FLEXIBLE ALUMINIUM LINER 5 FT C W SPACERS W730 0012 8 FLEXIBLE ALUMINIUM LINER 5 FT GD430 10 FT PART NO DESCRIPTION W730 0013 8 FLEXIBLE ALUMINIUM LINER 10 FT W010 0773 5 FLEXIBLE ALUMINI...

Page 25: ...R W660 0013 NG GD825P MODULATING VALVE REGULATOR FOR W660 0013 P W500 0163 FIRESTOP SPACER RIGID VENTING GD501 HEAT GUARD W585 0096 SOFFIT HEAT SHIELD W010 0810 WALL SUPPORT ASSEMBLY W175 0170 DURA VENT ZERO CLEARANCE ADAPTOR W170 0086 VENT PIPE COLLAR W585 0092 VENT PIPE SHIELD GZ550 1KT BLOWER KIT GD65 FAN KIT GD36 THERMOSTATIC SENSOR CONTROL KIT FOR USE WITH GD65 ONLY W500 0033 VARIABLE SPEED S...

Page 26: ...rect length or wire gauge Faulty thermostat or switch replace 5 flexible vent has become disconnected from fireplace Pilot goes out when the gas knob is re leased The gas valve has an interlock device which will not allow the pilot burner to be lit until the ther mocouple has cooled Allow ap proximately 60 seconds for the thermocouple to cool System is not correctly purged purge the gas line with ...

Page 27: ...EAN GLASS WHEN HOT If deposits are not cleaned off regularly the glass may become permanently marked Main burner flame is a blue lazy transparent flame Blockage in vent remove blockage In really cold conditions ice buildup may occur on the terminal and should be removed as required refer to Figure 23 to ensure correct location of storm collars Incorrect installation check that the logs are correct...

Page 28: ...28 W415 0221 E 04 09 02 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name ...

Reviews: