These vent kits allow for either horizontal or vertical venting of the 
fi replace. The maximum allowable horizontal run is 20 feet. The 
maximum allowable vertical vent length is 40 feet. The maximum 
number of vent connections is two horizontally or three vertically 
(excluding the fi replace and the air terminal connections) when us-
ing fl exible venting.

For optimum fl ame appearance and fi replace performance, keep 
the vent length and number of elbows to a minimum.

 

REAR VENT

TOP VENT

CORNER

RIGID VENTING

FLEXIBLE 

VENTING

RIGID VENTING

FLEXIBLE 

VENTING

RIGID VENTING

FLEXIBLE 

VENTING

REQUIRED RISE ON HORIZONTAL VENTING

BGD36CF(G)  BGD42CF

0" / FT

0" / FT

0" / FT

0" / FT

0" / FT

0" / FT

0" / FT

0" / FT

0"

6"

0"

0"

 HORIZONTAL VENT SECTIONS:

 - 

A minimum clearance 

of 1" at the bottom and sides of the vent and 2" at the top on 
all horizontal runs to combustibles is required. The fi restop 
spacer (W010-1774) supplied with the unit must be used to 
maintain this clearance. 

VERTICAL VENT SECTIONS:

 - 

A minimum of 1" all around 

the vent pipe on all vertical runs to combustibles is required 
except for clearances in fi replace enclosures. See 

"MINIMUM 

ENCLOSURE CLEARANCES"

 section. Use fi restop spacer 

W500-0096 (not supplied).

BGD36CF(G)

BGD42CF

Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp or 
American Metal Amerivent venting components. Minimum and maxi-
mum vent lengths, for both horizontal and vertical installations, and 
air terminal locations for either system are set out in this manual and 
must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp and 
American Metal Amerivent, follow the installation procedure provided 
with the venting components.

A starter adaptor must be used with the following vent systems and 
may be purchased from the corresponding supplier: 

PART  

 

4"/7"               5"/8"  

SUPPLIER

Duravent W175-0053 

W175-0170 

Wolf 

Steel 

Amerivent 4DSC-N2  5DSC-N 

American 

Metal

Direct Temp 

4DT-AAN 

5DT-AA 

Selkirk 

For Simpson Dura-Vent, Selkirk Direct Temp and American Metal 
Amerivent, follow the installation procedure found on the website for 
your venting supplier.

VENTING SUPPLIER 

         WEBSITE

Simpson Dura-Vent 

         www.duravent.com

Selkirk Direct Temp 

         www.selkirkcorp.com

American Metal Amerivent      www.americanmetalproducts.com

For vent systems that provide seals on the inner exhaust fl ue, only the 
outer air intake joints must be sealed using a red high temperature 
silicone (RTV). This same sealant may be used on both the inner 
exhaust and outer intake vent pipe joints of all other approved vent 
systems except for the exhaust vent pipe connection to the fi replace 
fl ue collar which must be sealed using the black high temperature 
sealant Mill Pac.

BGD36CF(G)

When using Wolf Steel venting components, use only approved Wolf 
Steel rigid / fl exible components with the following termination kits: 
WALL TERMINAL KIT 

GD222

, or 1/12 to 7/12 PITCH ROOF TERMI-

NAL KIT

 GD110

, 8/12 to 12/12 ROOF TERMINAL KIT

 GD111

, FLAT 

ROOF TERMINAL KIT

 GD112 

or PERISCOPE KIT

 GD201 

(for wall 

penetration below grade). With fl exible venting, in conjunction with 
the various terminations, use either the 5 FOOT VENT KIT 

GD220

 

or the 10 FOOT VENT KIT 

GD330

BGD42CF 

When using Wolf Steel venting components, use only approved Wolf 
Steel fl exible components with the following termination kits: WALL 
TERMINAL KIT

 GD422

, or 1/12 to 7/12 PITCH ROOF TERMINAL 

KIT 

GD410

, 8/12 to 12/12 ROOF TERMINAL KIT 

GD411

, FLAT 

ROOF TERMINAL KIT 

GD412

 or PERISCOPE KIT 

GD401

 (for wall 

penetration below grade). With fl exible venting, in conjunction with 
the various terminations, use either the 5 FOOT VENT KIT 

GD420

 

or the 10 FOOT VENT KIT 

GD430

Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp or Ameri-
can Metal Amerivent venting systems must not be combined. 
Wolf Steel rigid and flexible venting systems must not be 
combined.

MODEL BGD36CF MAY BE VENTED EITHER AS A TOP VENT OR A REAR VENT. 

REFER TO THE SECTION APPLICABLE TO YOUR INSTALLATION.

 

VENTING LENGTHS

THE BGD36CF(G) USES: 4" EXHAUST / 7" AIR INTAKE VENT PIPE

THE BGD42CF USES: 5" EXHAUST / 8" AIR INTAKE VENT PIPE 

For safe and proper operation of the fi replace follow the venting instruction exactly. Deviation from the minimum vertical vent length 
can create diffi culty in burner start-up and/or carboning. Provide a means for visually checking the vent connection to the fi replace 
after the fi replace is installed. Vent lengths that pass through unheated spaces (attics, garages, crawl spaces) should be insulated 
with the insulation wrapped in a protective sleeve to minimize condensation.

VENTING

HORIZONTAL VENT SECTIONS:

 A minimum clearance of 2" 

all around the vent pipe on all horizontal runs to combustibles 
is required. Use fi restop spacer W010-1778 (supplied).

VERTICAL VENT SECTIONS:

 A minimum of 1" all around the 

vent pipe on all vertical runs to combustibles is required. Use 
fi restop spacer W500-0028 (not supplied).

 

For optimum performance, it is recommended that all horizontal 
runs have a 1" rise per foot.

NorthlineExpress.com

http://www.northlineexpress.com

Toll-Free 1-866-667-8454

Summary of Contents for BGD36CFGN

Page 1: ...AFTEY INFORMATION Do not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do no...

Page 2: ...burns or clothing ignition Supervise young children when they are in the same room as the fireplace Clothing or other flammable material should not be placed on or near the fireplace Due to high tempe...

Page 3: ...h as blowers gas valves thermal switch switches wiring remote controls ignitor gasketing and pilot assembly are covered and NAPOLEON will provide replacement parts free of charge during the first year...

Page 4: ...B149 Installation Codes Mobile home installation must conform with local codes or in the absence of local codes install to the current standard for gas equipped mobile housing CAN CSA ZA240 MH Series...

Page 5: ...S INLET FIGURE 5 INSTALLATION OVERVIEW FIGURE 7 See the section MINIMUM MANTEL AND ENCLOSURE CLEARANCES Side Wall See the section INSTALLATION FRAMING See the section VENTING and INSTALLATION See the...

Page 6: ...may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the replace ue collar which must be sealed usi...

Page 7: ...7 W415 0661 12 07 07 FIGURE 8 NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Page 8: ...se is a minimum 3 feet and a maximum 40 feet from the centre of the replace ue outlet NOTE When terminating vertically the restrictor plate W500 0205 must be installed Refer to Restricting Vertical Ve...

Page 9: ...run in addition to the 45 offset In this case zero rise is acceptable when using rigid See FIGURE 18 Flexible venting must maintain a 6 rise See FIGURE 19 PERISCOPE TERMINATION CORNER TERMINATION BGD...

Page 10: ...mum of 40 feet Horizontal run verti cal rise to maximum of 24 75 feet 4 2 times the verti cal rise equal to or greater than the horizontal run Vertical rise is equal to or greater than the horizontal...

Page 11: ...HT The shaded area within the lines represents acceptable values for HT and VT for the following symbols used in the venting calculations and examples are greater than equal to or greater than less t...

Page 12: ...TICAL RISE IN INCHES VT HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT and VT when HT VT Simple venting con guration only one 90 elbow...

Page 13: ...s FIGURE 25 H2 V1 V2 H3 90 90 90 90 H1 FIGURE 26 Example 5 V1 4 ft V2 1 5 ft VT V1 V2 4 1 5 5 5 ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows one 45 elbow 9...

Page 14: ...30 MAXIMUM VERTICAL R I S E I N FEET VT HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT and VT For vent con gurations requiring more tha...

Page 15: ...90 6 75 ft HT HR HO 12 75 6 75 19 5 ft HT VT 19 5 6 5 26 ft Formula 1 HT 3VT 3VT 3 x 6 5 19 5 ft 19 5 19 5 Formula 2 HT VT 40 feet 26 40 Since both formulas are met this vent con guration is accept ab...

Page 16: ...HT VT Simple venting con guration only one 45 and 90 elbow See graph to deter mine the required vertical rise VT for the required horizontal run HT REQUIRED VER TICAL RISE IN INCHES VT HORIZONTAL VEN...

Page 17: ...VT Formula 2 HT VT 40 feet Example 3 90 90 90 H1 V1 V2 45 H2 V1 5 ft V2 10 ft VT V1 V2 5 10 15 ft H1 3 ft H2 2 5 ft HR H1 H2 3 2 5 5 5 ft HO 03 one 45 elbow three 90 elbows 135 03 45 90 90 90 135 5 4...

Page 18: ...ceptable Formula 2 HT VT 40 feet 15 9 40 Since only formula 2 is met this vent con guration is unac ceptable and a new replace location or vent con guration will need to be established to satisfy both...

Page 19: ...combustibles is required Use restop spacer W010 1778 supplied VERTICAL VENT SECTIONS A minimum of 1 all around the vent pipe on all vertical runs to combustibles is required Use restop spacer W500 00...

Page 20: ...d secure over the opening in the ceiling A restop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through VERTICAL INSTALLATION BGD36CF G 9 3 4...

Page 21: ...the exible vent pipe through the restop maintaining the required clearance to combus tibles Holding the air terminal let tering in an upright readable position secure to the exterior wall and make wea...

Page 22: ...d upper edge of the shingles Ensure that the air terminal is properly centered within the ashing giving a 3 4 margin all around Fasten to the roof Do NOT nail through the lower portion of the ashing M...

Page 23: ...the type s of gas indicated on the rating plate Aconversion kit is supplied with the mobile home appliance This Mobile Manufactured Home listed appliance comes factory equipped with means to secure t...

Page 24: ...W010 1774 supplied with the unit must be used to maintain this clearance VERTICAL VENT SECTIONS A minimum of 1 all around the vent pipe on all vertical runs to combustibles is required except for clea...

Page 25: ...LOW FOR PROPER DOOR REMOVAL 12 TO COMBUSTIBLE MANTLE The finishing material can be installed below the top opening a maximum of 1 1 2 Enough clearance to the door latches must be maintained to allow f...

Page 26: ...vertical runs to combustibles is required except for clearances in replace enclosures See MINIMUM ENCLOSURE CLEARANCES section Use restop spacer W500 0096 not supplied MINIMUM CLEARANCE TO COMBUSTIBLE...

Page 27: ...ON BGD36CF G ONLY OPTIONAL CLEAN FACE TRIM KIT INSTALLATION FIGURE 83 CLEAN FACE SURROUND MINIMUM ENCLOSURE CLEARANCES 3 First secure the clean face surround to the replace front by hooking the ledge...

Page 28: ...FIGURE 92c MINIMUM CLEARANCE TO COMBUSTIBLE CONSTRUC TION FROM FIREPLACE AND VENT SURFACES Combustible framing Top sides back and bottom of the unit 0 to stand offs Non combustible nishing Top 6 1 2...

Page 29: ...8 5 Place the bottom of the right crossover log 6 against the right rebox side and pulled forward to the grate The top of the log should rest in the pocket provided on the center log 5 BGD42CF FINISHI...

Page 30: ...e glowing embers for a maximum glowing effect Log colours may vary During the initial use of the replace the colours will become more uniform as colour pigments burn in during the heat activated curin...

Page 31: ...the rebox 3 Unscrew the lens cover making sure the gasket stays in place Note Do not handle the lamp bulb with bare ngers protect with a clean dry cloth 4 The lamp will pull straight outofthesocket R...

Page 32: ...k washer and wing nut provided Ensure that the blower does not touch the replace base or the rebox 5 Remove the 8 perimeter screws as illustrated in Fig 112 and lift out the burner base The gas line e...

Page 33: ...th moving or hot objects To ease installation of the fan remove the hinge screen and valve control door lower louvres from the base of the replace Position the vibration reducing pad into the clip and...

Page 34: ...nd solid core wire through the electrical hole located at the bottom left side of the unit FIGURE 125 BATTERY HOLDER GAS VALVE PILOT ASSEMBLY IGNITION MODULE PILOT GAS LINE Orange I through independen...

Page 35: ...s on wire size WIRE SIZE MAX LENGTH 14 gauge 100 feet 16 gauge 60 feet 18 gauge 40 feet A 20 length of millivolt wire is connected to the gas valve for the light wall switch However if a greater lengt...

Page 36: ...Im mediately call a quali ed service technician to inspect the replace and replace any part of the control system and any gas control which has been under water WARNING The gas valve has an interlock...

Page 37: ...POWER TO THE FIREPLACE IF SERVICE IS TO BE PERFORMED 3 TURN MANUAL SHUTOFF VALVE CLOCKWISE TO OFF DO NOT FORCE NEXT STEP 8 CLOSE THE GLASS DOOR 9 TURN MANUAL SHUTOFF VALVE COUNTER CLOCKWISE TO ON 10 T...

Page 38: ...re the glass embers are away from the center of the screen exposing the burner before lifting glass ember tray out When replacing burner absolutely no glass can be in cup surrounding the ori ce HINT I...

Page 39: ...ly perform a visual check of the pilot and the burner ames Compare them to the gures shown If any ames appear abnormal call a service person FIGURE 137 It is important to periodically perform a visual...

Page 40: ...F STEEL LTD 29 W225 0058 BLACK DOOR FRAME 30 W455 0048 47 NATURAL GAS ORIFICE 30 W455 0047 56 PROPANE GAS ORIFICE 31 W010 0370 WALL SUPPORT ASSEMBLY 32 W010 0539 FLUE PIPE ASSEMBLY c w GASKET 33 W010...

Page 41: ...8 PERISCOPE GD401 109 WALL TERMINAL KIT GD422 BGD42CF ROOF TERMINAL KITS 110 1 12 TO 7 12 PITCH GD410 111 8 12 TO 12 12 PITCH GD411 112 FLAT ROOF GD412 113 W490 0074 5 8 INNER OUTER SLEEVE 114 W670 00...

Page 42: ...42 W415 0661 12 07 07 NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Page 43: ...rom the I terminal on the module If no spark the I terminal module must be replaced If there is a spark the I terminal is ne Inspect pilot assembly for a shorted wire or cracked insulator around the e...

Page 44: ...lve Conduct the following test to verify if the problem is the module or valve To measure voltages turn multimeter to DC place the red lead from multimeter on the screw on the terminal block for the w...

Page 45: ...ased The gas valve has an interlock device which will not allow the pilot burner to be lit until the thermo couple has cooled Allow approximately 60 seconds for the thermocouple to cool System is not...

Page 46: ...s been adhered to for any horizontal vent ing Air shutter has become blocked ensure air shutter opening is free of lint or other obstructions Flames are consist ently too large or too small Carboning...

Page 47: ...replace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name NorthlineExpress com http www northlinee...

Page 48: ...48 W415 0661 12 07 07 NOTES NorthlineExpress com http www northlineexpress com Toll Free 1 866 667 8454...

Reviews: