Napoleon B36DFP Installation And Operation Instructions Manual Download Page 6

6

W415-0484 / A / 07.26.06

Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct
Temp or American Metal Amerivent venting components.

For Simpson Dura-Vent, Selkirk Direct Temp and American
Metal Amerivent, follow the installation procedure provided
with the venting components.

All outer pipe joints of these venting systems must be
sealed using Red RTV Hight Temperature Sealant.

Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp and
American Metal Amerivent venting systems must not be
combined.

A starter adaptor must be used and may be purchased
from the corresponding supplier:

PART

5"/8"

SUPPLIER

Duravent

W175-0170

Wolf Steel

Amerivent

5DSC-N

American Metal

Direct Temp

5DT-AAN

Selkirk

For vent systems that provide seals on the inner exhaust
flue, only the outer air intake joints must be sealed using a
red high temperature silicone (RTV). This same sealant
maybe used on both the inner exhaust and outer intake
vent pipe joints of all other approved vent systems except
for the exhaust vent pipe connection to the fireplace flue
collar which must be sealed using the black high tempera-
ture sealant Mill Pac.
When using Wolf Steel venting components, use only ap-
proved Wolf Steel rigid / flexible components with the fol-
lowing termination kits: WALL TERMINAL KIT 

GD422

, or

1/12 TO 7/12 PITCH ROOF TERMINAL KIT

 GD410

, 8/12 TO

12/12 ROOF TERMINAL KIT

 GD411

, FLAT ROOF TERMI-

NAL KIT

 GD412 

or PERISCOPE KIT

 GD401 

(for wall pen-

etration below grade). With flexible venting, in conjunction
with the various terminations, use either the 5 foot vent kit

GD420

 or the 10 foot vent kit 

GD430

.

These vent kits allow for either horizontal or vertical venting
of the fireplace. 

FIGURES 3 & 5. 

The maximum allowable

horizontal run is 20 feet. The maximum allowable vertical
vent length is 40 feet. The maximum number of 5" vent
connections is two horizontally or three vertically (exclud-
ing the fireplace and the air terminal connections) when
using aluminum flexible venting.

For optimum flame appearance and fireplace performance,
keep the vent length and number of elbows to a minimum.

The air terminal must remain unobstructed at all times.
Examine the air terminal at least once a year to verify that
it is unobstructed and undamaged.

Purge all gas lines with the glass door of the fireplace
removed. Assure that a continuous gas flow is at the burner
before re-installing the door.

Under extreme vent configurations, allow several minutes (5-
15) for the flame to stabilize after ignition.

Eight (8") inches is the minimum bend radius allowed for
the 8" diameter flexible liner.

For optimum performance it is recommended that all hori-
zontal runs have a 1 inch rise per foot when using Napoleon
flexible vent components.

A terminal shall not terminate directly above a sidewalk or
paved driveway which is located between two single family
dwellings and serves both dwellings. Local codes or regu-
lations may require different clearances.

Do not allow the inside liner to bunch up on horizontal or
vertical runs and elbows. Keep it pulled tight. A 1¼" air gap
all around between the inner liner and outer liner is required
for safe operation. Use a firestop when penetrating interior
walls, floor or ceiling.

Objects placed in front of the fireplace must be kept a
minimum of 48" away from the front face of the unit.

FIGURE 1

Horizontal runs may have a 0 inch rise per foot in all cases
using SIMPSON DURA-VENT or  NAPOLEON RIGID OR
FLEXIBLE venting components when venting as illustrated
in Figures 3, and 4.

VENTING

VENTING LENGTHS

Minimum clearance to combustible con-

struction from fireplace and vent sur-

faces:

sides, back and bottom

0" (to stand off)

top (framing)

8"

finishing

0"

recessed depth

21"

sides and bottom of the vent pipe

1"

top of vent

2"

For safe and proper operation of the fireplace follow the
venting instruction exactly.

Deviation from the minimum vertical vent length can
create difficulty in burner start-up and/or carboning.

Provide a means for visually checking the vent connection
to the fireplace after the fireplace is installed.

Vent lengths that pass through unheated spaces (attics,
garages, crawl spaces) should be insulated with the
insulation wrapped in a protective sleeve to minimize
condensation.

Summary of Contents for B36DFP

Page 1: ...1 W415 0484 A 07 23 06 W415 0484 A 07 26 06...

Page 2: ...WHAT TO DO IF YOU SMELL GAS WARNINGS SAFETY PRECAUTIONS...

Page 3: ...rt of the control system and any gas control which has been under water Do not operate the fireplace with the glass door removed cracked or broken Replacement of the glass should be done by a licensed...

Page 4: ...are covered and eting and pilot assembly are covered and eting and pilot assembly are covered and eting and pilot assembly are covered and NAPOLEON NAPOLEON NAPOLEON NAPOLEON NAPOLEON will provide re...

Page 5: ...tates FOR YOUR SATISFACTION THIS FIREPLACE HAS BEEN TEST FIRED TO ASSURE ITS OPERATION AND QUALITY Maximum input is 23 000 BTU hr for natural gas and propane When the fireplace is installed at elevati...

Page 6: ...ce performance keep the vent length and number of elbows to a minimum The air terminal must remain unobstructed at all times Examine the air terminal at least once a year to verify that it is unobstru...

Page 7: ...tly closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to unventilated soffit Cleara...

Page 8: ...m of 12 inches above grade The maximum allow able vent length depends on the fireplace as illustrated FIGURES3a c FIGURE4 TYPICAL VENT INSTALLATIONS SPECIAL VENT INSTALLATIONS NOTE When terminating ve...

Page 9: ...ntal run Horizontal run verti cal rise to maximum of 40 feet Vertical rise is less than horizontal run Horizontal run verti cal rise to m a x i m u m of 24 75 feet 4 2 times the vertical rise equal to...

Page 10: ...offset 135 in feet VT combined vertical vent lengths in feet feet inches 1 0 03 0 5 15 0 45 6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the first 45 and 90 offset has a zero value and is shown in the fo...

Page 11: ...ET HT when HT VT Simple venting configuration only one 45 and 90 elbow Example 2 V1 4ft V2 1 5ft VT V1 V2 4 ft 1 5 ft 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 one 45...

Page 12: ...s are met this vent configuration is ac ceptable when HT VT Simple venting configurations FIGURE9 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET HT FIGURE10 For vent config...

Page 13: ...eptable Formula 2 HT VT 40 feet 15 9 40 Since only formula 2 is met this vent configuration is unac ceptable and a new fireplace location or vent configuration will need to be established to satisfy b...

Page 14: ...nce the vent pipe liner is installed in its final position apply sealant between the pipe liner and the firestop spacer FIGURE16 This application occurs when vent ing through an exterior wall Having d...

Page 15: ...runs Use noncombustible strapping to maintain the minimum 1 clearance to combustibles FIGURE19 HORIZONTAL AIR TERMINAL INSTALLATION VERTICAL AIR TERMINAL INSTALLATION 4 Insert the liners through the...

Page 16: ...use open flame Do not connect either the wall switch thermostat or gas valve to electricity 110 volts Purge all gas lines with the glass door of the fireplace removed Assure that a continuous gas flow...

Page 17: ...for use with other gases unless a certified kit is used Conversion Kits The mobile home appliance is field convertible between Natural Gas NG and Propane LP To convert from Natural Gas to Propane ord...

Page 18: ...32b 2 To determine the final location of the nailing tab you must first determine the thickness of your finishing mate rial i e drywall This will determine the dimension from the front edge of the cor...

Page 19: ...g Secure using a screw through the centre slot LOWER LOUVRES Insert the hinge clips into the slots located at the bottom left and right corners of the unit To remove the louvres pull the back tabs of...

Page 20: ...ll of the burner area in front of the small logs 2 3 Care should be taken to shred the embers into thin small irregular pieces as only the exposed edges of the fibre hairs will glow The ember material...

Page 21: ...ireplace base or the firebox Attach the connectors from the black and white wires to the thermodisc and secure the thermodisc bracket to the unit at the bottom left of the unit using the ground screw...

Page 22: ...Steel Napoleon dealer With the thermostatic sensor option the fan when turned on becomes thermally activated and will automatically run approximately 15 30 minutes after the fireplace has been lit and...

Page 23: ...smell gas including near the floor Stop Follow B in the above safety information on this label If you don t smell gas go the next step 5 Turn gas knob counter clockwise to pilot 6 Depress slightly and...

Page 24: ...yellow flame but can lead to carboning Opening the air shutter will cause a more blue flame but can cause flame lifting from the burner ports The flame may not appear yellow immediately allow 15 to 30...

Page 25: ...KIT ARCHED BLACK 55 DK36 AG DOOR KIT ARCHED GOLD PLATED 56 DK36 W DOOR KIT WEBBED BLACK 56 DK36 WG DOOR KIT WEBBED GOLD PLATED 57 GA 566 HOT AIR KIT 58 GA 72 HOT AIR EXHAUST KIT 59 GA 70 EXTENSION KI...

Page 26: ...ouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd AT TE NT ION CH AU D CA UT ION HO T 5 4 6 3 22 46 49 50 53 52 51 38 21 54 57 55 28 23 5...

Page 27: ...an interlock device which will not allow the pilot burner to be lit until the ther mocouple has cooled Allow ap proximately 60 seconds for the thermocouple to cool System is not correctly purged purge...

Page 28: ...aned off regularly the glass may become permanently marked Main burner flame is a blue lazy transparent flame Blockage in vent remove blockage In extremely cold conditions ice buildup may occur on the...

Page 29: ...29 W415 0484 A 07 23 06 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Page 30: ...30 W415 0484 A 07 26 06 NOTES...

Reviews: